Troubleshooting
Problem
Solving
Battery exhausted warning
Replace the batteries
Zone fault warning
Check if any other problems are present
(Maintenance >Diagnostic >Update)
A zone signals “Error on probe”
The probe does not respond:
- check whether it is correctly connected (green LED
shining steadily or flashing slowly) and configured
(correct zone number and mode).
A zone signals “Actuator KO”
An actuator does not respond:
- check whether the actuators are correctly connected
and configured (test the actuators with the local key);
- with standard configuration, check that the
configuration has been performed correctly in the
control unit Maintenance>Configure zone>Configure).
A zone signals “Pump KO”
“Pump KO”
The actuator configured for the control of the circulation
pump (Zone = 00) does not respond:
- check whether the actuator is correctly connected and
check whether the actuator is correctly connected and
configured (test the actuator with the local key)
- check the correct configuration of the pump
check the correct configuration of the pump
pump
(Maintenance > Configure zones > Pumps)
A zone signals “Slave probe KO”
A slave probe does not respond:
- check whether it is correctly connected (green LED
check whether it is correctly connected (green LED
shining steadily or flashing slowly) and configured
(correct zone number, SLA mode);;
- check the correct configuration of the slaves to be
check the correct configuration of the slaves to be
managed on the Master probe..
A zone signals “T out of limits”
The temperature measured by the probe is too low or
too high:
- check that the probe is installed correctly (e.g. not too
check that the probe is installed correctly (e.g. not too
close to heat sources);
- set the probe
set the probe
(Maintenance>Probe setting) measuring the room
temperature with a thermometer;
- if the problem continues, replace the probe;
if the problem continues, replace the probe;
- if it is the local zone that is showing a temperature
outside the set limits, completely reset and then
reacquire the system.
A zone signals “R/W EEPROM KO”
If there is an internal problem on the probe:
- replace the probe.
The Control unit is frozen after
connection to the PC
Carry out the RESET procedure as indicated in the
TiThermoBasic software manual.