BTCPower 200 KW EVSE Installation manual
Rev K
Page 12 of 26
Input AC Over voltage
detection
1msec non-latched
1msec non-latched
Input AC Under voltage
detection
1msec non-latched
1msec non-latched
Input AC Over Current
1msec latched
1msec latched
Input AC fused
Input AC GFCI
GFCI module range 30 mA.
GFCI module range 30 mA.
Output DC over voltage
1070 VDC latched
1070 VDC latched
Output DC short circuit
Shut down
Shut down
CAN communication loss
1 sec shut down upon loss of
connection
1 sec shut down upon loss of
connection
AC input surge
6 KV requirement per UL 2231,
EMC requirements
6 KV requirement per UL 2231,
EMC requirements
External Remote E-Stop
Remove high power if external
E-stop is activated
Remove high power if external
E-stop is activated
GROUNDING INSTRUCTIONS – This unit is to be connected to a grounded,
metal, permanent wiring system; or an equipment-grounding conductor is to be
run with circuit conductors and connected to equipment-grounding terminal or
lead on a battery charger. Connections to a battery charger shall comply with
all local codes and ordinances.
TERMINAL BLOCKS
TOWER AC Input – Input terminal lugs
MODEL NUMBERS: PC200235, PC200135, PC200435, PC200265, PC200165, PC200465
A Single AC input terminal block is used to connect the AC utility to the AC to DC Power Converter
AC Line Side
Part Number
(Input side terminal block)
Wire Range
Opening per pole
Terminal Lug
Torque requirement
6 AWG
–
350 KCMIL
(Copper wire only)
1
350L2
325 IN - LB
500 KCMIL
(Aluminum wire)
1
600L2
550 IN - LB