background image

TROUBLESHOOTING

Table 4 — Troubleshooting

PROBLEM

SOLUTION

Display on thermostat not
illuminated.

Check for 24 vac at the R terminal connection. Terminal R must be connected
for proper thermostat operation.

Cooling will not energize.

Select COOL mode. Decrease cooling set point to 10 degrees below room tem-
perature. Check for 24 vac at Y1 terminal. If present, thermostat is operating
correctly and problem is with wiring or equipment. If 24 vac is not present, re-
place the thermostat. Check for Compressor Cycle per Hour Limit. Cooling may
be locked out.

Heating will not energize.

Select HEAT mode. Increase heating set point to 10 degrees above room tem-
perature. Check for 24 vac at W1/O/B terminal. If present, thermostat is operat-
ing correctly and problem is with wiring or equipment. If 24 vac is not present,
replace the thermostat.

When using 4 wires (R,G,W,Y), the cooling equip-
ment tries repeatedly to turn on, but cannot. At
times the display dims or disappears.

There is not enough power available. Connect a 270 ohm, 10 watt power resis-
tor at the air conditioning equipment between terminals W and C (non-heat
pump applications only).

When using 4 wires (R,G,W,Y), the heating equip-
ment tries repeatedly to turn on, but cannot. At
times the display dims or disappears.

There is not enough power available. Connect a 270 ohm, 10 watt power resis-
tor at the air-conditioning equipment between terminals Y and C (non-heat
pump applications only).

When controlling a heat pump, heat comes on
during cooling cycle.

Configure thermostat for heat pump operation
(Table 2, Step 5).

When calling for cooling,
both heating and cooling are energized.

The thermostat is configured for a heat pump. Configure the thermostat for non-
heat pump operation (Table 2, Step 5).

When controlling a commercial heat pump unit,
unit runs in reverse or heating is
always on.

Some commercial heat pumps require that Heat Pump Option on thermostat is
turned OFF. Refer to unit installation instructions for more information.

—7—

Содержание TSTATBBPSP2-WC

Страница 1: ...ams for 3 different days Saturday Sunday and Mon day through Friday Batteries are not required During power interruption the internal NEVERLOST memory stores pro grammed schedules for an unlimited time while the clock con tinues to run for at least 48 hours The thermostat can be configured to accept several different equipment configurations including heat pump operation NOTE The thermostat is not...

Страница 2: ...r from the unit The thermostat will be powered by 24 v nominal 18 to 30 vac Terminals R 24 v W1 O B first stage heat or reversing valve Y1 first stage cool ing and G fan relay will always be connected Some applications will use C common Y2 second stage cool ing or W2 second stage heating WIRING TERMINAL BLOCK HOLE FOR WIRING MOUNTING HOLE MOUNTING HOLE C Y1 W2 G R W1 B O Y2 3 1 8 3 1 8 1 Fig 1 The...

Страница 3: ...orner of the thermostat screen Use the Mode button to advance through the steps See Table 2 Press the Mode and Override buttons at the same time to exit the Advanced Setup mode NOTE Refer to Set Clock section on this page for an expla nation of Advanced Setup Steps 1 and 2 A Display Blanking Step 3 When Display Blanking is set to OFF the thermostat will display the time of day current temperature ...

Страница 4: ...hermostat Refer to the Add A Wire accessory installation instructions for more information VII PROGRAM THERMOSTAT SCHEDULES Before programming the thermostat plan the thermostat daily schedule The schedule is divided into 3 different day sched ules Monday through Friday Saturday and Sunday The sched ules for Monday Tuesday Wednesday Thursday and Friday are the same Each day has from 2 to 4 time pe...

Страница 5: ... Press the Mode and UP ARROW buttons at the same time to exit Programming mode NOTE The thermostat will continue to follow the schedule until a new one is entered If only one occupied schedule is selected the Occupied 2 and 3 schedules are skipped If the start time is set later in the day than the stop time the program will run from midnight of that day to the stop time and then from the start tim...

Страница 6: ...he deadband plus 2 degrees III CLOCK BACKUP In the event of a power loss the thermostat will keep time for a minimum of 48 hours without external power or batteries IV FAN OPERATION If Fan On is selected the fan will run continuously during occupied schedule except when Mode is switched to OFF The fan will be off during unoccupied schedule except during heating or cooling operation If Fan On is no...

Страница 7: ...repeatedly to turn on but cannot At times the display dims or disappears There is not enough power available Connect a 270 ohm 10 watt power resis tor at the air conditioning equipment between terminals W and C non heat pump applications only When using 4 wires R G W Y the heating equip ment tries repeatedly to turn on but cannot At times the display dims or disappears There is not enough power av...

Страница 8: ...Copyright 1999 Bryant Heating Cooling Systems CATALOG NO 809 619 Printed in U S A ...

Отзывы: