4. Press the DOWN ARROW button until the cooling set

point is 10 F lower than the current room temperature.
Cooling and fan should be energized.

5. If heating, cooling, or fan operation do not energize, check

wiring and consult Table 4.

X. FINAL CHECKLIST

1. Put away tools and instruments. Clean up debris and

packaging.

2. Review Owner’s Guide with occupant or owner.

3. Leave the manuals with owner.

OPERATION

The Mode button selects the operating mode of the thermo-
stat. If OFF is selected, the thermostat will not enter Heat-
ing or Cooling mode. If HEAT is selected, the thermostat will
only enter Heating mode (if the room temperature is below
the heating set point). If COOL is selected, the thermostat
will only enter Cooling mode (if the room temperature is above
the cooling set point). If AUTO is selected, the thermostat will
enter Heating or Cooling mode based on the room tempera-
ture and the heating and cooling set points. If PROGRAM
ON is selected, the stored schedule is enabled and the ther-
mostat will follow the Occupied and Unoccupied schedules
stored in its memory.

I. AUTO-CHANGEOVER

When the thermostat mode is set to AUTO, the thermostat
will provide automatic changeover from Heating to Cooling
mode and Cooling to Heating mode when required. The ther-
mostat will automatically switch to maintain the desired tem-
perature setting. The thermostat does not need to be manu-
ally changed from heating to cooling or cooling to heating
operation.

II. TWO-STAGE OPERATION

The second stage of heat or cool is turned on when the first
stage has been on for a minimum of 2 minutes and the tem-
perature differential from the set point is equal to or greater
than the set point plus the deadband plus 2 degrees.

III. CLOCK BACKUP

In the event of a power loss, the thermostat will keep time
for a minimum of 48 hours without external power or
batteries.

IV. FAN OPERATION

If Fan On is selected, the fan will run continuously during
occupied schedule (except when Mode is switched to OFF).
The fan will be off during unoccupied schedule except during
heating or cooling operation.

If Fan On is not selected, the fan will only operate during
heating or cooling operation.

V. EMERGENCY HEAT

Emergency heat is available for heat pump applications. This
option is only available if Advanced Setup Step 5 (Heat Pump)
is set to ON. To turn on emergency heat, press and hold the
Override button. While holding the Override button, press
the UP button. An ‘‘EH’’ will be displayed. During emergency
heat, the fan will operate and the second stage of heat will be
energized (locking out the first stage compressor). To exit emer-
gency heat, press and hold the Override button. While hold-
ing the Override button, press the UP button. During emer-
gency heat, only OFF and HEAT modes are available.

VI. ELECTRIC HEAT

When the Electric Heat option in the advanced setup is set
to ON (configured by installer), the thermostat will turn on
the fan immediately any time there is a heat demand. This
feature should only be used on electric heating applications.
Do not use with gas heat.

VII. KEYPAD LOCK

To prevent unauthorized use of the thermostat, the front panel
buttons can be disabled. To disable or lock the keypad, press
and hold the Mode button. While holding down the Mode but-
ton, press the UP and DOWN ARROW buttons simulta-
neously. The ‘‘Locked’’ icon will appear on the display.

The thermostat is unlocked by performing the same proce-
dure. Press and hold the Mode button. While holding down
the Mode button, press the UP and DOWN ARROW buttons
simultaneously. The ‘‘Locked’’ icon will be removed from the
display.

—6—

Содержание TSTATBBPSP2-WC

Страница 1: ...ams for 3 different days Saturday Sunday and Mon day through Friday Batteries are not required During power interruption the internal NEVERLOST memory stores pro grammed schedules for an unlimited time while the clock con tinues to run for at least 48 hours The thermostat can be configured to accept several different equipment configurations including heat pump operation NOTE The thermostat is not...

Страница 2: ...r from the unit The thermostat will be powered by 24 v nominal 18 to 30 vac Terminals R 24 v W1 O B first stage heat or reversing valve Y1 first stage cool ing and G fan relay will always be connected Some applications will use C common Y2 second stage cool ing or W2 second stage heating WIRING TERMINAL BLOCK HOLE FOR WIRING MOUNTING HOLE MOUNTING HOLE C Y1 W2 G R W1 B O Y2 3 1 8 3 1 8 1 Fig 1 The...

Страница 3: ...orner of the thermostat screen Use the Mode button to advance through the steps See Table 2 Press the Mode and Override buttons at the same time to exit the Advanced Setup mode NOTE Refer to Set Clock section on this page for an expla nation of Advanced Setup Steps 1 and 2 A Display Blanking Step 3 When Display Blanking is set to OFF the thermostat will display the time of day current temperature ...

Страница 4: ...hermostat Refer to the Add A Wire accessory installation instructions for more information VII PROGRAM THERMOSTAT SCHEDULES Before programming the thermostat plan the thermostat daily schedule The schedule is divided into 3 different day sched ules Monday through Friday Saturday and Sunday The sched ules for Monday Tuesday Wednesday Thursday and Friday are the same Each day has from 2 to 4 time pe...

Страница 5: ... Press the Mode and UP ARROW buttons at the same time to exit Programming mode NOTE The thermostat will continue to follow the schedule until a new one is entered If only one occupied schedule is selected the Occupied 2 and 3 schedules are skipped If the start time is set later in the day than the stop time the program will run from midnight of that day to the stop time and then from the start tim...

Страница 6: ...he deadband plus 2 degrees III CLOCK BACKUP In the event of a power loss the thermostat will keep time for a minimum of 48 hours without external power or batteries IV FAN OPERATION If Fan On is selected the fan will run continuously during occupied schedule except when Mode is switched to OFF The fan will be off during unoccupied schedule except during heating or cooling operation If Fan On is no...

Страница 7: ...repeatedly to turn on but cannot At times the display dims or disappears There is not enough power available Connect a 270 ohm 10 watt power resis tor at the air conditioning equipment between terminals W and C non heat pump applications only When using 4 wires R G W Y the heating equip ment tries repeatedly to turn on but cannot At times the display dims or disappears There is not enough power av...

Страница 8: ...Copyright 1999 Bryant Heating Cooling Systems CATALOG NO 809 619 Printed in U S A ...

Отзывы: