background image

6. Use up and down buttons to select another Option, or press

FAN button to exit configuration mode.

M.

Option 19 — Equipment Present

This selection informs the thermostat of the heat, cool, and fan
capabilities of the installed equipment. Select number 2, 3, or 4.
Default is 4.
For equipment with both heat and cool capability and fan selection,
choose 4.
For equipment with only heat or cool, but with fan selection,
choose 3.
For equipment with only heat or cool and no fan selection, choose
2.
TO SELECT:

1. Enter configuration mode (if not already there).

2. Use up and down buttons to display Option 19. The SET

icon should be off.

3. Press MODE button once. The SET icon will come on. The

display now shows Option 19 setting.

4. Use up and down buttons to move between available Option

19 choices of 2 through 4. Factory default is 4.

5. Press MODE button again to return to Option 19. The SET

icon will now be off.

6. Use up and down buttons to select another Option, or press

FAN button to exit configuration mode.

N.

Option 21 — Keypad Lockout

In OF (off) mode, the keypad is not locked out and has full
functionality. In ON mode, the keypad is locked out and the lock
icon on the display is illuminated. To unlock the keypad, the user
must press and hold the up and down buttons simultaneously for
approximately 5 seconds. The lock icon is turned off and the
keypad will remain unlocked as long as the user presses a button
at least every 30 seconds or for the entire duration of the installer
test mode. If keypad remains idle for 30 seconds and the installer
test mode is not in operation, the keypad will return to the locked
state and the lock icon will illuminate on the screen.
TO SELECT:

1. Enter configuration mode (if not already there).

2. Use up and down buttons to display Option 21. The SET

icon should be off.

3. Press MODE button once. The SET icon will come on. The

display now shows Option 21 setting.

4. Use up and down buttons to move between available Option

21 choices of ON or OF. Factory default is OF.

5. Press MODE button again to return to Option 21. The SET

icon will now be off.

6. Use up and down buttons to select another Option, or press

FAN button to exit configuration mode.

O.

Installer Test Mode

Installer test will be initiated by pressing the fan button for 20
seconds (15 seconds will enter installer setup. InS will appear on
the screen and the SERVICE icon will be illuminated.

In installer test mode, pressing the MODE button will change the
system operating mode. Note that AUTO mode is not available in
installer test. Heating and cooling modes must be tested indepen-
dently.

a. If the mode is set to HEAT, the first stage of heating will

be energized for three minutes (180 seconds), and then
the first and second stages (if a second stage exists) will
turn on for an additional three minutes. Installer test will
always attempt to run a second stage output whether it is
attached or not, providing a minimum of 6 minutes of
first stage operation. At the end of the 6 minute period,
the MODE will return to OFF.

b. Pressing the FAN button while the heating or cooling

equipment is not running will turn on the FAN relay and
display the FAN icon.

c. If the mode is set to COOL, the first stage of cooling

turns on for three minutes, then first and second stages (if
a second stage exists) will turn on for three minutes.

d. If the mode is set to EHEAT, auxiliary heat turns on for

three minutes, then the mode returns to OFF.

Terminating Installer Test

After 15 minutes of inactivity (no button presses by the installer),
thermostat will automatically revert to normal operation. Pressing
RESET FILTER any time during installer test will terminate
installer test and return the thermostat to normal operation.

V.

CHECK THERMOSTAT OPERATION

A.

Fan Operation

1. Press FAN button, starting continuous fan operation. FAN

icon turns on.

2. Press FAN button again, stopping fan operation. FAN icon

turns off. (Some fan coils have 90 sec fan off delay, so fan
may not stop immediately.)

B.

Outdoor Temperature Sensor

If system is equipped with an outdoor temperature sensor, check its
operation by pressing both, the temperature UP and DOWN
buttons simultaneously. Outdoor temperature will be displayed for
about 5 sec. If

--

is displayed, the outdoor temperature sensor is

absent or not properly connected.

C.

Checklist

1. Run equipment through several heating and cooling cycles

to ensure proper operation.

2. If equipment is to be left in operation, set point and

operating mode must be properly selected.

3. Put away tools and instruments, and clean up debris.

4. Review Homeowner’s Guide with owner.

5. Leave literature packet with owner.

—5—

Содержание TSTATBBN2S01-C

Страница 1: ...lication Models are AC 1 stage cool 1 stage heat for AC systems only HP 1 stage cool 2 stage heat for either HP or AC with 2 stage heat 2S 2 stage cool 2 stage heat for 2 speed AC systems or 2 stage c...

Страница 2: ...on page 11 for explanation IV SET THERMOSTAT CONFIGURATION Configuration options are intended to be selected at installation and are normally not modified by the home owner These options are not disc...

Страница 3: ...D Option 04 G Fan On With W W1 Output This selection determines whether the G fan output is to be ON or OFF when any W furnace or strip heat output is ON Most furnaces and fan coils manage their own b...

Страница 4: ...ween 5 and 5 Factory default is 0 This adjusted value will be used as actual temperature for both display and control action For example if 2 is selected 72 F actual will read 74 F If setpoint is 72 t...

Страница 5: ...ler test will be initiated by pressing the fan button for 20 seconds 15 seconds will enter installer setup InS will appear on the screen and the SERVICE icon will be illuminated In installer test mode...

Страница 6: ...R CONDITIONER See notes 6 10 and 11 Y G W2 E W3 HEAT STAGE 1 FAN A98453 Fig 2 Single Speed Air Conditioner with Single Stage Furnace A04006 24 VAC HOT 24 VAC COMM HEAT STAGE 1 COOL STAGE 1 FAN R C G W...

Страница 7: ...ED AIR CONDITIONER See notes 2 4 6 10 and 11 Y G O W2 B W2 E W3 A98455 Fig 9 Two Speed Air Conditioner with 2 Stage or Variable Speed Furnace A04010 24 VAC HOT 24 VAC COMM HEAT STAGE 1 COOL STAGE 2 FA...

Страница 8: ...2 4 5 6 8 10 and 11 Y G O W2 B W2 R Y2 E W3 A98459 Fig 13 Single Speed Air Conditioner with Variable Speed FK4D FV 40FK Fan Coil A98464 24 VAC HOT HEAT STAGE 1 24 VAC COMM COOL STAGE 1 FAN R G W W1 Y...

Страница 9: ...n Coil A98466 24 VAC HOT 24 VAC COMM FAN COOL HEAT STAGE 1 HEAT STAGE 2 R Y Y2 R C C C R MODEL HP THERMOSTAT EASY SELECT TERMINAL BOARD SINGLE SPEED HEAT PUMP J1 JUMPER J2 JUMPER See notes 7 8 and 11...

Страница 10: ...eat Refer to indoor equipment Installation Instructions for proper setup 5 Refer to outdoor equipment Installation Instructions for latent kit requirements if any 6 Terminals marked with may not be pr...

Страница 11: ...s the model configuration via the following 2 digit code AC 1 speed air conditioner HP 1 speed heat pump A2 2 speed air conditioner H2 2 speed heat pump ERROR CODES If the thermostat cannot properly r...

Страница 12: ...AC Configuration 6 Cooling Lockout Off or On factory default Off 7 Zoning Selection Off or On factory default Off 8 Auxiliary Heat Lockout Off or 5 55 F factory default Off 9 N A 10 O Reversing Valve...

Отзывы: