rate. However, a limiting feature will not allow more than 6
equipment cycles per hour, regardless of setting. Values can range
from 1 to 9. Factory default setting is 3. This default selection will
provide optimum performance in nearly all installations. Try it
first. Do not change setting unless there is evidence of need to do
so.

Unlike conventional anticipators, this setting is not to be deter-
mined by current draw. There is no need to measure, know, or
compensate for current. There is also no droop with this thermo-
stat, regardless of anticipator setting. This adjustment controls only
sensitivity and cycle rate up to the maximum of 6 cycles per hr.

TO ADJUST:

1. Enter configuration mode (if not already there).

2. Use up and down buttons to display Option 01. The SET

icon should be off.

3. Press MODE button once. The SET icon will come on. The

display now shows Option 01 setting.

4. Use up and down buttons to move between the available

Option 01 values of 1 to 9. Factory default is 3.

5. Press MODE button again to return to Option 01. The SET

icon will now be off.

6. Use up and down buttons to select another Option, or press

FAN button to exit configuration mode.

B.

Option 02—Clean Filter Timer

This option selects the number of hours of blower operation
(heating, cooling, or fan) before SERVICE FILTER icon is
displayed. With OF selected, the icon will never come on,
disabling this feature. Time selection can be from 400 to 3600
hours by selecting numbers 1 through 9. (Time is 400 X number
selected.) Factory default is 2 (800 hours). Recommended selec-
tions are: disposable filter 800 hr, media filter 1200 to 1600 hr, or
electronic air cleaner 1600 to 2400 hr of blower operation.

TO ADJUST:

1. Enter configuration mode (if not already there).

2. Use up and down buttons to display Option 02. The SET

icon should be off.

3. Press MODE button once. The SET icon will come on. The

display now shows Option 02 setting.

4. Use up and down buttons to move between the available

Option 02 values of OF and 1 through 9. Factory default is
2.

5. Press MODE button again to return to Option 02. The SET

icon will now be off.

6. Use up and down buttons to select another Option, or press

FAN button to exit configuration mode.

C.

Option 03—Fahrenheit/Celsius Selection

This option selects Fahrenheit or Celsius operation.

TO SELECT:

1. Enter configuration mode (if not already there).

2. Use up and down buttons to display Option 03. The SET

icon should be off.

3. Press MODE button once. The SET icon will come on. The

display now shows Option 03 setting.

4. Use up and down buttons to move between the available

Option 03 choices of F (Fahrenheit) or C (Celsius). Factory
default is F.

5. Press MODE button again to return to Option 03. The SET

icon will now be off.

6. Use up and down buttons to select another Option, or press

FAN button to exit configuration mode.

D.

Option 04—G (Fan) On With W/W1 Output

This selection determines whether the G (fan) output is to be ON
or OFF when any W (furnace or strip heat) output is ON. Most
furnaces and fan coils manage their own blowers and do not
require a separate G signal. For these applications, select OFF.
Some auxiliary heaters require a separate G signal to turn on the
blower. In this case, select On. Factory default is OF (off).
TO SELECT:

1. Enter configuration mode (if not already there).

2. Use up and down buttons to display Option 04. The SET

icon should be off.

3. Press MODE button once. The SET icon will come on. The

display now shows Option 04 setting.

4. Use up and down buttons to move between available Option

04 choices of ON or OF. Factory default is OF.

5. Press MODE button again to return to Option 04. The SET

icon will now be off.

6. Use up and down buttons to select another Option, or press

FAN button to exit configuration mode.

E.

Option 05 — HP and 2S / AC Configuration

This configuration is available on HP and 2S models only.
Selecting AC allows the installer to use an HP or 2S thermostat in
an AC application.
TO SELECT:

1. Enter configuration mode (if not already there).

2. Use up and down buttons to display Option 05. The SET

icon should be off.

3. Press MODE button once. The SET icon will come on. The

display now shows Option 05 setting.

4. Use up and down buttons to move between available Option

05 choices of AC or HP. Factory default is HP.

5. Press MODE button again to return to Option 05. The SET

icon will now be off.

6. Use up and down buttons to select another Option, or press

FAN button to exit configuration mode.

F.

Option 06—Cooling Lockout

An outdoor air sensor is required for this function. In OF mode,
cooling is available regardless of outdoor temperature. In ON
mode, cooling will not be initiated if the outdoor air temperature is
below 55° F. If the compressor is already operating and the
outdoor air temperature drops below 55° F, the compressor will
continue to operate until the cooling cycle has completed. If the
mode has been set to ON and the outdoor air sensor fails, an E3
error will be displayed.
TO SELECT:

1. Enter configuration mode (if not already there).

2. Use up and down buttons to display Option 06. The SET

icon should be off.

3. Press MODE button once. The SET icon will come on. The

display now shows Option 06 setting.

4. Use up and down buttons to move between available Option

06 choices of OF or ON. Factory default is OF.

5. Press MODE button again to return to Option 06. The SET

icon will now be off.

6. Use up and down buttons to select another Option, or press

FAN button to exit configuration mode.

G.

Option 07—Zoning On/Off Configuration

This selection enables or defeats the cycle timer, the staging timer,
and the compressor timeguard. (See "Operational Information" on
page 11 for details.) These timers MUST be enabled (zoning OFF)
for normal operation and disabled (zoning ON) for zoning appli-
cations. In zoning applications, the zone control center performs
these timing functions. Factory default is OF.

—3—

Содержание TSTATBBN2S01-C

Страница 1: ...lication Models are AC 1 stage cool 1 stage heat for AC systems only HP 1 stage cool 2 stage heat for either HP or AC with 2 stage heat 2S 2 stage cool 2 stage heat for 2 speed AC systems or 2 stage c...

Страница 2: ...on page 11 for explanation IV SET THERMOSTAT CONFIGURATION Configuration options are intended to be selected at installation and are normally not modified by the home owner These options are not disc...

Страница 3: ...D Option 04 G Fan On With W W1 Output This selection determines whether the G fan output is to be ON or OFF when any W furnace or strip heat output is ON Most furnaces and fan coils manage their own b...

Страница 4: ...ween 5 and 5 Factory default is 0 This adjusted value will be used as actual temperature for both display and control action For example if 2 is selected 72 F actual will read 74 F If setpoint is 72 t...

Страница 5: ...ler test will be initiated by pressing the fan button for 20 seconds 15 seconds will enter installer setup InS will appear on the screen and the SERVICE icon will be illuminated In installer test mode...

Страница 6: ...R CONDITIONER See notes 6 10 and 11 Y G W2 E W3 HEAT STAGE 1 FAN A98453 Fig 2 Single Speed Air Conditioner with Single Stage Furnace A04006 24 VAC HOT 24 VAC COMM HEAT STAGE 1 COOL STAGE 1 FAN R C G W...

Страница 7: ...ED AIR CONDITIONER See notes 2 4 6 10 and 11 Y G O W2 B W2 E W3 A98455 Fig 9 Two Speed Air Conditioner with 2 Stage or Variable Speed Furnace A04010 24 VAC HOT 24 VAC COMM HEAT STAGE 1 COOL STAGE 2 FA...

Страница 8: ...2 4 5 6 8 10 and 11 Y G O W2 B W2 R Y2 E W3 A98459 Fig 13 Single Speed Air Conditioner with Variable Speed FK4D FV 40FK Fan Coil A98464 24 VAC HOT HEAT STAGE 1 24 VAC COMM COOL STAGE 1 FAN R G W W1 Y...

Страница 9: ...n Coil A98466 24 VAC HOT 24 VAC COMM FAN COOL HEAT STAGE 1 HEAT STAGE 2 R Y Y2 R C C C R MODEL HP THERMOSTAT EASY SELECT TERMINAL BOARD SINGLE SPEED HEAT PUMP J1 JUMPER J2 JUMPER See notes 7 8 and 11...

Страница 10: ...eat Refer to indoor equipment Installation Instructions for proper setup 5 Refer to outdoor equipment Installation Instructions for latent kit requirements if any 6 Terminals marked with may not be pr...

Страница 11: ...s the model configuration via the following 2 digit code AC 1 speed air conditioner HP 1 speed heat pump A2 2 speed air conditioner H2 2 speed heat pump ERROR CODES If the thermostat cannot properly r...

Страница 12: ...AC Configuration 6 Cooling Lockout Off or On factory default Off 7 Zoning Selection Off or On factory default Off 8 Auxiliary Heat Lockout Off or 5 55 F factory default Off 9 N A 10 O Reversing Valve...

Отзывы: