III.

INSTALL THERMOSTAT

WARNING:

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal
injury or death.
Before installing thermostat, turn off all power to unit.
There may be more than 1 power disconnect.

1. Turn OFF all power to unit.

2. If an existing thermostat is being replaced:

a. Remove existing thermostat from wall.

b. Disconnect wires from existing thermostat, 1 at a time.

Be careful not to allow wires to fall back into the wall.

c. As each wire is disconnected, record wire color and

terminal marking.

d. Discard or recycle old thermostat.

NOTE:

Mercury is a hazardous waste and MUST be disposed of

properly.

3. Open thermostat (mounting base) to expose mounting

holes. The base can be removed to simplify mounting. Snap
apart carefully to separate mounting base from remainder of
thermostat.

NOTE:

If thermostat will not separate, insert a small screwdriver

into top slots for ease of opening.

4. Route thermostat wires through large hole in mounting

base. Level mounting base against wall (for aesthetic value
only—thermostat need not be leveled for proper operation)
and mark wall through 2 mounting holes.

5. Drill two 3/16-in. mounting holes in wall where marked.

6. Secure mounting base to wall with 2 anchors and screws

provided, (additional anchoring holes available for more
secure mounting if needed) making sure all wires extend
through hole in mounting base.

7. Adjust length and routing of each wire to reach proper

terminal and connector block on mounting base with 1/4 in.
extra wire. Strip only 1/4 in. insulation from each wire to
prevent adjacent wires from shorting together when con-
nected.

8. Match and connect equipment wires to proper terminals of

the connector blocks. (See Table 1.)

CAUTION:

ELECTRICAL OPERATION HAZARD

Failure to follow this caution may result in equipment
damage or improper operation.
Improper wiring or installation may damage the thermo-
stat. Check to make sure wiring is correct before proceed-
ing with installation or turning on unit.

9. Push any excess wire into wall and against mounting base.

Seal hole in wall to prevent air leaks. Leaks can affect
operation.

10. Snap case back together.

11. Close thermostat assembly making sure pins on back of

circuit board align with sockets in connector.

12. Turn ON power to unit.

NOTE:

If a common wire has not been connected, two AA

batteries must be used to power the thermostat.
On power up, LCD readout will display AC, HP, A2, or H2
depending on the thermostat model status. See "Power On Check"
under "Operational Information" on page 11 for explanation.

IV.

SET THERMOSTAT CONFIGURATION

Configuration options are intended to be selected at installation
and are normally not modified by the home owner. These options
are not discussed in the Homeowner’s Guide and therefore must be
made as part of the installation. A special procedure allows entry
into the configuration mode. The thermostat will automatically exit
this mode if no button is pressed for 3 minutes. While in the
configuration mode, up to 14 option choices can be made:
Option 01: Anticipator setting
Option 02: Clean filter setting
Option 03: Fahrenheit or Celsius selection
Option 04: Enable fan (G) on with W/W1 output
Option 05: HP / AC
Option 06: Cooling Lockout (available only if an outdoor air
temperature sensor is present)
Option 07: Enable zoning
Option 08: Auxiliary heat lockout temperature adjustment (avail-
able only on heat pump systems and if an outdoor air temperature
sensor is present)
Option 10: O (reversing valve) ON with Heat or Cool (present on
Heat Pump models only)
Option 13: Room temperature offset adjustment
Option 15: Enable AUTO mode
Option 18: Backlight configuration
Option 19: Equipment Present
Option 21: Keypad Lockout
An explanation for each of these and how to enter the configura-
tion mode follows.

TO ENTER THE CONFIGURATION MODE:

To enter Configuration Mode, hold the FAN button down for
approximately 15 seconds. After the 15 second period, Option

01

will appear in the display and the SERVICE icon will be

turned on.

NOTE:

If the FAN button is pressed again or if no button is

pressed for 3 min, the thermostat will exit the configuration mode
and return to normal operation. To reenter the configuration mode,
the FAN button must be pressed and held for 15 seconds again.

WHILE IN CONFIGURATION MODE:

The display is used to show both the option number and the
selection choice within that option.

A.

Option 01—Anticipator Adjustment

This adjustment controls the sensitivity and cycle rate of the
thermostat. Higher numbers decrease the sensitivity and slow the
cycle rate. Lower numbers increase sensitivity and increase cycle

TABLE 1—MODEL SELECTION AND WIRING DIAGRAM CHART

OUTDOOR UNIT

AIR CONDITIONER

HEAT PUMP

1 Speed

2 Speed

1 Speed

2 Speed

1-Stage

Furnace

Model AC

See Fig. 2

Model 2S

See Fig. 8

Requires

Dual Fuel Thermostat

Requires

Dual Fuel Thermostat

2-Stage

Furnace

Model AC

See Fig. 3

Model HP

See Fig. 5

Model 2S

See Fig. 9

Requires

Dual Fuel Thermostat

Requires

Dual Fuel Thermostat

Typical Fan Coil

Model AC

See Fig. 4

Model HP

See Fig. 6

Model 2S

See Fig. 10

Model HP

See Fig. 7

Model 2S

See Fig. 11

Variable-Speed

Fan Coil

(FK4D, FV4, 40FK)

Model AC

See Fig. 12

Model HP

See Fig. 13

Model 2S

See Fig. 14

Model HP

See Fig. 15

Model 2S

See Fig. 16

—2—

Содержание TSTATBBN2S01-C

Страница 1: ...lication Models are AC 1 stage cool 1 stage heat for AC systems only HP 1 stage cool 2 stage heat for either HP or AC with 2 stage heat 2S 2 stage cool 2 stage heat for 2 speed AC systems or 2 stage c...

Страница 2: ...on page 11 for explanation IV SET THERMOSTAT CONFIGURATION Configuration options are intended to be selected at installation and are normally not modified by the home owner These options are not disc...

Страница 3: ...D Option 04 G Fan On With W W1 Output This selection determines whether the G fan output is to be ON or OFF when any W furnace or strip heat output is ON Most furnaces and fan coils manage their own b...

Страница 4: ...ween 5 and 5 Factory default is 0 This adjusted value will be used as actual temperature for both display and control action For example if 2 is selected 72 F actual will read 74 F If setpoint is 72 t...

Страница 5: ...ler test will be initiated by pressing the fan button for 20 seconds 15 seconds will enter installer setup InS will appear on the screen and the SERVICE icon will be illuminated In installer test mode...

Страница 6: ...R CONDITIONER See notes 6 10 and 11 Y G W2 E W3 HEAT STAGE 1 FAN A98453 Fig 2 Single Speed Air Conditioner with Single Stage Furnace A04006 24 VAC HOT 24 VAC COMM HEAT STAGE 1 COOL STAGE 1 FAN R C G W...

Страница 7: ...ED AIR CONDITIONER See notes 2 4 6 10 and 11 Y G O W2 B W2 E W3 A98455 Fig 9 Two Speed Air Conditioner with 2 Stage or Variable Speed Furnace A04010 24 VAC HOT 24 VAC COMM HEAT STAGE 1 COOL STAGE 2 FA...

Страница 8: ...2 4 5 6 8 10 and 11 Y G O W2 B W2 R Y2 E W3 A98459 Fig 13 Single Speed Air Conditioner with Variable Speed FK4D FV 40FK Fan Coil A98464 24 VAC HOT HEAT STAGE 1 24 VAC COMM COOL STAGE 1 FAN R G W W1 Y...

Страница 9: ...n Coil A98466 24 VAC HOT 24 VAC COMM FAN COOL HEAT STAGE 1 HEAT STAGE 2 R Y Y2 R C C C R MODEL HP THERMOSTAT EASY SELECT TERMINAL BOARD SINGLE SPEED HEAT PUMP J1 JUMPER J2 JUMPER See notes 7 8 and 11...

Страница 10: ...eat Refer to indoor equipment Installation Instructions for proper setup 5 Refer to outdoor equipment Installation Instructions for latent kit requirements if any 6 Terminals marked with may not be pr...

Страница 11: ...s the model configuration via the following 2 digit code AC 1 speed air conditioner HP 1 speed heat pump A2 2 speed air conditioner H2 2 speed heat pump ERROR CODES If the thermostat cannot properly r...

Страница 12: ...AC Configuration 6 Cooling Lockout Off or On factory default Off 7 Zoning Selection Off or On factory default Off 8 Auxiliary Heat Lockout Off or 5 55 F factory default Off 9 N A 10 O Reversing Valve...

Отзывы: