Table 10 – Dry Coil Air Delivery
*
- Horizontal and Downflow Discharge Sizes 24-60 208/230VAC - 1 Phase
Unit Size Heating Rise
°F (°C)
Motor Speed
Tap
Allowable
Functions
ESP (in. W.C.)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
24040
25 - 55
(14 - 31)
Low
†
Blue
Alternate Heating
CFM
654
552
454
338
x
x
x
x
x
x
BHP
0.09
0.10
0.10
0.11
x
x
x
x
x
x
Gas Heat Rise (
°
F)
45
54
NA
NA
NA
NA
NA
NA
NA
NA
Gas Heat Rise (
°
C)
25
30
NA
NA
NA
NA
NA
NA
NA
NA
Med-Low
‡
Pink
Heating
Alternate Cooling
CFM
840
759
677
600
505
411
293
x
x
x
BHP
0.14
0.15
0.16
0.16
0.17
0.17
0.18
x
x
x
Gas Heat Rise (
°
F)
35
39
44
50
NA
NA
NA
NA
NA
NA
Gas Heat Rise (
°
C)
20
22
24
28
NA
NA
NA
NA
NA
NA
Medium
Red
Cooling
Alternate Heating
CFM
888
818
750
679
606
511
425
320
238
x
BHP
0.18
0.18
0.19
0.19
0.20
0.20
0.21
0.21
0.22
x
Gas Heat Rise (
°
F)
34
36
40
44
49
NA
NA
NA
NA
NA
Gas Heat Rise (
°
C)
19
20
22
24
27
NA
NA
NA
NA
NA
Med-High
Orange
Alternate Cooling
Alternate Heating
CFM
1133
1069
995
930
854
784
701
628
549
464
BHP
0.26
0.27
0.28
0.29
0.30
0.30
0.31
0.31
0.32
0.33
Gas Heat Rise (
°
F)
26
28
30
32
35
38
42
47
54
NA
Gas Heat Rise (
°
C)
15
15
17
18
19
21
24
26
30
NA
High
Black
High Static Cooling Only
CFM
1291
1241
1190
1131
1081
1028
949
854
742
616
BHP
0.41
0.42
0.43
0.43
0.44
0.45
0.44
0.42
0.40
0.38
24060
25 - 55
(14 - 31)
Low
Blue
CFM
654
552
454
338
x
x
x
x
x
x
BHP
0.09
0.10
0.10
0.11
x
x
x
x
x
x
Gas Heat Rise (
°
F)
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
Gas Heat Rise (
°
C)
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
Med-Low
Pink
Alternate Cooling
Alternate Heating
CFM
840
759
677
600
505
411
293
x
x
x
BHP
0.14
0.15
0.16
0.16
0.17
0.17
0.18
x
x
x
Gas Heat Rise (
°
F)
53
NA
NA
NA
NA
NA
NA
NA
NA
NA
Gas Heat Rise (
°
C)
30
NA
NA
NA
NA
NA
NA
NA
NA
NA
Medium
Red
Cooling
Alternate Heating
CFM
888
818
750
679
606
511
425
320
238
x
BHP
0.18
0.18
0.19
0.19
0.20
0.20
0.21
0.21
0.22
x
Gas Heat Rise (
°
F)
50
55
NA
NA
NA
NA
NA
NA
NA
NA
Gas Heat Rise (
°
C)
28
30
NA
NA
NA
NA
NA
NA
NA
NA
Med-High
Orange
Heating
Alternate Cooling
CFM
1133
1069
995
930
854
784
701
628
549
464
BHP
0.26
0.27
0.28
0.29
0.30
0.30
0.31
0.31
0.32
0.33
Gas Heat Rise (
°
F)
40
42
45
48
53
NA
NA
NA
NA
NA
Gas Heat Rise (
°
C)
22
23
25
27
29
NA
NA
NA
NA
NA
High
Black
High Static Cooling Only
CFM
1291
1241
1190
1131
1081
1028
949
854
742
616
BHP
0.41
0.42
0.43
0.43
0.44
0.45
0.44
0.42
0.40
0.38
30040
25 - 55
(14 - 31)
Low
Blue
Alternate Heating
CFM
654
552
454
338
x
x
x
x
x
x
BHP
0.09
0.10
0.10
0.11
x
x
x
x
x
x
Gas Heat Rise (
°
F)
45
54
NA
NA
NA
NA
NA
NA
NA
NA
Gas Heat Rise (
°
C)
25
30
NA
NA
NA
NA
NA
NA
NA
NA
Med-Low
Pink
Heating
Alternate Cooling
CFM
840
759
677
600
505
411
293
x
x
x
BHP
0.14
0.15
0.16
0.16
0.17
0.17
0.18
x
x
x
Gas Heat Rise (
°
F)
35
39
44
50
NA
NA
NA
NA
NA
NA
Gas Heat Rise (
°
C)
20
22
24
28
NA
NA
NA
NA
NA
NA
Medium
Red
Cooling
Alternate Heating
CFM
1104
1038
979
915
844
782
712
639
532
452
BHP
0.26
0.27
0.28
0.28
0.29
0.30
0.30
0.31
0.31
0.32
Gas Heat Rise (
°
F)
27
29
30
33
35
38
42
47
NA
NA
Gas Heat Rise (
°
C)
15
16
17
18
20
21
23
26
NA
NA
Med-High
Orange
Alternate Cooling
Alternate Heating
CFM
1133
1069
995
930
854
784
701
628
549
464
BHP
0.26
0.27
0.28
0.29
0.30
0.30
0.31
0.31
0.32
0.33
Gas Heat Rise (
°
F)
26
28
30
32
35
38
42
47
54
NA
Gas Heat Rise (
°
C)
15
15
17
18
19
21
24
26
30
NA
High
Black
High Static Cooling Only
CFM
1291
1241
1190
1131
1081
1028
949
854
742
616
BHP
0.41
0.42
0.43
0.43
0.44
0.45
0.44
0.42
0.40
0.38