Accessory Description and Usage (Listed Alphabetically)

1. Compressor Start Assist -- Capacitor and Relay

Start capacitor and relay gives a ”hard” boost to compressor

motor at each start up.

Usage Guideline:
Required for reciprocating compressors in the

following applications:

Long line
Low ambient cooling
Hard shut off expansion valve on indoor coil
Liquid line solenoid on indoor coil

Required for single--phase scroll compressors in the
following applications:

Long line
Low ambient cooling

Suggested for all compressors in areas with a history of

low voltage problems.

2. Compressor Start Assist — PTC Type

Solid state electrical device which gives a ”soft” boost to the
compressor at each start--up.

Usage Guideline:

Suggested in installations with marginal power supply.

3. Crankcase Heater

An electric resistance heater which mounts to the base of the
compressor to keep the lubricant warm during off cycles.

Improves compressor lubrication on restart and minimizes the
chance of liquid slugging.

Usage Guideline:

Required in low ambient cooling applications.
Required in long line applications.
Suggested in all commercial applications.

4. Cycle Protector

The cycle protector is designed to prevent compressor short

cycling. This control provides an approximate 5--minute delay
after power to the compressor has been interrupted for any

reason, including power outage, protector control trip, thermostat
jiggling, or normal cycling.

5. Evaporator Freeze Thermostat

An SPST temperature--actuated switch that stops unit operation

when evaporator reaches freeze--up conditions.

Usage Guideline:

Required when low ambient kit has been added.

6. Low--Ambient Pressure Switch Kit

A long life pressure switch which is mounted to outdoor unit

service valve. It is designed to cycle the outdoor fan motor in
order to maintain head pressure within normal operating limits

(approximately 100 psig to 225 psig). The control will maintain
working head pressure at low--ambient temperatures down to 0

_

F

(--18

_

C) when properly installed.

Usage Guideline:

A Low--Ambient Pressure Switch or MotorMaster

r

Low--Ambient Controller must be used when cooling operation is
used at outdoor temperatures below 55

_

F (12.8

_

C).

7. Outdoor Air Temperature Sensor

Designed for use with Bryant Thermostats listed in this

publication. This device enables the thermostat to display the
outdoor temperature. This device also
is required to enable special thermostat features such as auxiliary

heat lock out.

Usage Guideline:

Suggested for all Bryant thermostats listed in this
publication.

8. Support Feet

Four stick--on plastic feet that raise the unit 4 in. (101.6 mm)
above the mounting pad. This allows sand, dirt, and other debris

to be flushed from the unit base, minimizing corrosion.

Usage Guideline:
Suggested in the following applications:
Coastal installations.
Windy areas or where debris is normally circulating.
Rooftop installations.
For improved sound ratings.

9. Thermostatic Expansion Valve (TXV)

A modulating flow--control valve which meters refrigerant liquid

flow rate into the evaporator in response to the superheat of the

refrigerant gas leaving the evaporator.
Kit includes valve, adapter tubes, and external equalizer tube.

Hard shut off types are available.

NOTE

: When using a hard shut off TXV with single phase

reciprocating compressors, a Compressor Start Assist Capacitor
and Relay is required.

Usage Guideline:

Required to achieve AHRI ratings in certain equipment

combinations. Refer to combination ratings.
Hard shut off TXV or LLS required in air conditioner

long line applications.
Required for use on all zoning systems.

10. Time--Delay Relay

An SPST delay relay which briefly continues operation of indoor
blower motor to provide additional cooling after the compressor

cycles off.

NOTE

: Most indoor unit controls include this feature. For those

that do not, use the guideline below.

Usage Guideline:

For improved efficiency ratings for certain
combinations of indoor and outdoor units. Refer to

AHRI Unitary Directory.

12. Winter Start Control

This control is designed to alleviate nuisance opening of the

low--pressure switch by bypassing it for the first 3 minutes of
operation.

186B

Содержание EVOLUTION 16 186B

Страница 1: ...e ratings information INDUSTRY LEADING FEATURES BENEFITS Efficiency S 14 16 SEER 11 0 13 5 EER S Microtube Technologyt refrigeration system S Indoor air quality accessories available Sound S Sound level as low as 68 dBA S Compressor sound blanket standard Comfort S System supports Evolution Control or standard thermostat controls Reliability S Puronr refrigerant environmentally sound won t deplete...

Страница 2: ... X X X X X Internal Thermal Overload X X X X X X X X Long Line capability X X X X X X X X Low Ambient capability with Kit X X X X X X X X High Pressure Switch X X X X X X X X Low Pressure Switch X X X X X X X X Compressor Sound Blanket X X X X X X X X Louvered Coil Guard X X X X X X X X Based on tested combinations X Standard PHYSICAL DATA UNIT SIZE SERIES 018 A 024 A 030 A 036 A 042 A 048 A 060 A...

Страница 3: ...50 250 250 250 250 230 160 060 061 AC with Puron 3 8 3 8 250 250 250 225 190 150 110 Maximum actual length not to exceed 200 ft 61 m Total equivalent length accounts for losses due to elbows or fitting See the Long Line Guideline for details outside acceptable range Maximum Total Equivalent Length Outdoor Unit ABOVE Indoor Unit Size Liquid Line Connection Liquid Line Diam w TXV AC with Puron Refri...

Страница 4: ... 4 No accessories needed within allowed lengths No accessories needed within allowed lengths 175 53 3 5 16 120 36 6 50 15 2 vertical or 120 36 6 total 120 36 6 3 8 80 24 4 35 10 7 vertical or 80 24 4 total 80 24 4 Note See Long Line Guideline for details VAPOR LINE SIZING AND COOLING CAPACITY LOSS Acceptable vapor line diameters provide adequate oil return to the compressor while avoiding excessiv...

Страница 5: ...Optional wall control used to monitor temperature and or fan control in an individual zone SYSTXBBRRS01 Evolution Remote Room Sensor Monitors temperature in an individual zone SYSTXBBRWF01 Evolution System Access Module Hardware for wireless access and control via phone or internet SYSTXBBNIM01 Evolution Network Interface Module Connects Heat Recovery and Energy Recovery Ventilators on non zoning ...

Страница 6: ...to 0_F 18_C when properly installed Usage Guideline A Low Ambient Pressure Switch or MotorMasterr Low Ambient Controller must be used when cooling operation is used at outdoor temperatures below 55_F 12 8_C 7 Outdoor Air Temperature Sensor Designed for use with Bryant Thermostats listed in this publication This device enables the thermostat to display the outdoor temperature This device also is re...

Страница 7: ... consult applicable tables of the NEC NFPA 70 Length shown is as measured one way along wire path between unit and service panel for voltage drop not to exceed 2 Time Delay fuse FLA Full Load Amps LRA Locked Rotor Amps MCA Minimum Circuit Amps RLA Rated Load Amps NOTE Control circuit is 24 V on all units and requires external power source Copper wire must be used from service disconnect to unit Al...

Страница 8: ...15 16 5 8 17 16 3 4 14 200 243 186B042 A X O O O 35 40 1 4 3 7 8 7 8 6 9 16 28 7 16 9 1 8 2 15 16 5 8 17 16 18 1 2 253 297 186B048 A X O 0 0 35 40 1 4 3 7 8 7 8 6 9 16 28 7 16 9 1 8 2 15 16 5 8 17 1 2 16 1 4 18 295 340 186B060 A X O 0 0 35 47 1 16 3 7 8 7 8 6 9 16 28 7 16 9 1 8 2 15 16 5 8 17 1 2 17 1 4 21 327 373 5 186B061 A X O O O 35 47 1 16 3 7 8 7 8 6 9 16 28 7 16 9 1 8 2 15 16 5 8 17 1 4 17 ...

Страница 9: ... 913 2 186B036 A X O 0 0 889 0 763 9 97 9 22 2 166 1 722 8 231 3 74 5 16 3 431 8 425 5 355 6 90 7 110 2 917 7 X 997 7 X 913 2 186B042 A X O O O 889 0 1022 9 97 9 22 2 166 1 722 8 231 3 74 5 16 3 431 8 406 4 469 9 114 8 134 7 917 7 X 997 7 X 1172 2 186B048 A X O 0 0 889 0 1022 9 97 9 22 2 166 1 722 8 231 3 74 5 16 3 444 5 412 8 457 2 133 8 154 2 917 7 X 997 7 X 1172 2 186B060 A X O 0 0 889 0 1195 7...

Страница 10: ...6 Service 24 609 6 Service 24 609 6 Service 24 609 6 24 609 6 24 609 6 12 304 8 12 304 8 12 304 8 12 304 8 6 152 4 Note Numbers in mm IMPORTANT When installing multiple units in an alcove roof well or partially enclosed area ensure there is adequate ventilation to prevent re circulation of discharge air 186B ...

Страница 11: ...5 186BNA061 A CNPV 6124A TDR 59 500 12 0 14 5 AHRI Air Conditioning Heating Refrigeration Institute EER Energy Efficiency Ratio SEER Seasonal Energy Efficiency Ratio TDR Time Delay Relay In most cases only 1 method should be used to achieve TDR function Using more than 1 method in a system may cause degradation in performance Use either the accessory Time Delay Relay KAATD0101TDR or a furnace equi...

Страница 12: ...18 57 18 57 1 17 17 82 17 82 1 31 17 03 17 03 1 46 16 18 16 18 1 62 15 27 15 27 1 80 14 30 14 30 2 01 EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES F C 75 23 9 85 29 4 95 35 105 40 6 115 46 1 125 51 7 CFM EWB F C Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Total Sens Tot...

Страница 13: ... 96 3 49 72 22 2 29 80 29 80 1 94 28 59 28 59 2 17 27 34 27 34 2 43 25 99 25 99 2 73 24 53 24 53 3 08 22 93 22 93 3 49 EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES F C 75 23 9 85 29 4 95 35 105 40 6 115 46 1 125 51 7 CFM EWB F C Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys ...

Страница 14: ...72 22 2 43 29 43 29 2 77 41 94 41 94 3 11 40 42 40 42 3 52 38 73 38 73 3 98 36 87 36 87 4 50 34 82 34 82 5 09 EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES F C 75 23 9 85 29 4 95 35 105 40 6 115 46 1 125 51 7 CFM EWB F C Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Total ...

Страница 15: ...door Section With CNPV 6124A TDR Indoor Section 1750 72 22 2 68 26 35 40 3 65 65 62 34 24 4 19 62 70 33 02 4 80 59 44 31 72 5 50 55 84 30 35 6 31 51 84 28 89 7 25 67 19 4 62 16 43 65 3 59 59 80 42 52 4 12 57 18 41 32 4 72 54 27 40 05 5 42 51 03 38 69 6 24 47 43 37 23 7 18 63 17 2 57 75 41 99 3 55 55 60 40 87 4 07 53 20 39 69 4 67 50 52 38 42 5 37 47 55 37 07 6 18 44 22 35 62 7 13 62 16 7 56 92 51 ...

Страница 16: ...2 42 40 4 44 TCG 24 60 23 70 22 70 21 60 20 40 19 10 17 80 16 30 SDT 68 40 77 90 87 30 96 70 106 10 115 50 124 80 134 10 KW 0 95 1 12 1 29 1 46 1 66 1 88 2 13 2 42 45 7 22 TCG 27 10 26 00 24 90 23 70 22 40 21 10 19 60 18 00 SDT 69 60 79 00 88 30 97 60 107 00 116 30 125 60 134 90 KW 0 94 1 11 1 29 1 47 1 67 1 89 2 14 2 43 50 10 0 TCG 29 70 28 60 27 30 26 00 24 60 23 10 21 50 19 80 SDT 70 80 80 10 8...

Страница 17: ...1 3 83 4 42 40 4 44 TCG 39 90 39 00 37 90 36 60 35 00 33 20 31 10 28 90 SDT 72 70 81 90 91 20 100 40 109 60 118 70 127 80 136 90 KW 1 63 1 87 2 15 2 49 2 88 3 33 3 85 4 45 45 7 22 TCG 43 90 42 90 41 60 40 10 38 40 36 40 34 20 31 80 SDT 74 20 83 30 92 50 101 60 110 80 119 90 128 90 137 90 KW 1 64 1 88 2 17 2 51 2 91 3 36 3 88 4 48 50 10 0 TCG 48 10 46 90 45 50 43 90 42 00 39 80 37 40 34 80 SDT 75 8...

Страница 18: ...0 129 90 138 60 KW 2 18 2 54 2 90 3 28 3 69 4 15 4 66 5 25 186BNA061000BAAA 30 1 11 TCG 47 40 46 30 45 00 43 40 41 50 39 30 36 80 33 80 SDT 70 70 80 00 89 20 98 50 107 70 116 90 126 00 135 10 KW 1 95 2 35 2 79 3 30 3 90 4 61 5 45 6 46 35 1 67 TCG 52 30 51 10 49 60 47 90 45 90 43 40 40 70 37 40 SDT 72 20 81 40 90 60 99 70 108 90 118 00 127 00 136 00 KW 1 98 2 38 2 82 3 34 3 94 4 65 5 49 6 49 40 4 4...

Страница 19: ... 1 2 TO 5 NOMINAL TONS Condenser fan motors will be totally enclosed 1 phase type with class B insulation and permanently lubricated bearings Shafts will be corrosion resistant Fan blades will be statically and dynamically balanced Condenser fan openings will be equipped with coated steel wire safety guards Compressor Compressor will be hermetically sealed Compressor will be mounted on rubber spli...

Страница 20: ...nt distributor 6 If any refrigerant tubing is buried provide a 6 in 152 4 mm vertical rise to the valve connections at the unit Refrigerant tubing lengths up to 36 in 914 4 mm may be buried without further consideration Do not bury refrigerant lines longer than 36 in 914 4 mm 7 Use only copper wire for electric connection at unit Aluminum and clad aluminum are not acceptable for the type of connec...

Отзывы: