background image

: Advanced Installation and Configuration Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

17

A200484

If Manual staging is selected instead of Automatic, then 5 additional staging options for the Auxiliary heat need to be configured.   Unlike straight

cooling projects where Manual Staging is recommended be enabled so Reverse Staging could be utilized, the same recommendation is not made for

heat pumps. The Auxiliary Staging adds an extra layer of complexity into the mix, especially if there are 2 compression stages plus 2 auxiliary stages,

so Automatic Staging should be selected on heat pump applications.

Installation Settings > Thresholds > Thermal Protect

A200485

The Thermal Protect range tells the thermostat the maximum difference allowed between the thermostat and hottest or coldest rooms in the home. If a

sensor measures a temperature that is significantly outside of this range, it probably means the reading is inaccurate. The thermostat will ignore this

inaccurate reading to prevent the heating or cooling from running excessively. This setting is adjustable from 10 to 25 degrees.

Installation Settings > Thresholds > Installer Code 

A200486

It  is  recommended  that  professionally  installed  thermostats  be  locked  out  by  enabling  the  Installer  Code.  This  prevents  the  homeowner  from

accidentally changing any of the settings in the Equipment, Thresholds, or Test Equipment settings. This lockout feature is separate from the Access

Control lockout and password that the homeowner can set for the homeowner settings.
Write this code down as it is not well documented or easy to find online. The code cannot be changed, as is the same for all thermostats.

Photo credit: ecobee

3262

Содержание EB-STATE3LTBB-01

Страница 1: ...or ERV Also the thermostats can be installed with the PEK if a C wire isn t present Additionally the thermostats can control boilers with or without an AC When connected to a boiler the thermostats s...

Страница 2: ...ntify the final assembly number model name country of origin and device serial number A210086 The following final assembly numbers and corresponding model name are as follows c Table 1 Final Assembly...

Страница 3: ...mostat can control the equipment it is preferred to allow the Bryant equipment to determine the staging by not connecting W2 See furnace installation instructions for heat staging setup Power Extender...

Страница 4: ...dd a Wire Kit works similar to the PEK Normally this would not be needed because the PEK comes with the ecobee However the PEK is limited to one extra wire and only one PEK can be used per system Seve...

Страница 5: ...g valve During the startup process the O B should be configured to act as an O terminal with Bryant equipment since the equipment defaults to heating and needs the reversing valve to be energized on a...

Страница 6: ...ion and Configuration Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 6 Air Conditioner with Boiler A200461 Boiler...

Страница 7: ...bee PEK Venstar Add a Wire or Fast Stat Wiring Extender accessories mentioned above cannot be used The W call gets piggy backed on the common wire with the small black sender module installed at the t...

Страница 8: ...ct variable speed furnaces The ACC terminal will wire to the DH or DHUM terminal on the equipment in these applications On the FV fan coils remove jumper J1 from the Easy Select board to enable this f...

Страница 9: ...mer and so only Rc is connected It is important to note that in these applications Rc must be used instead of Rh like some Bryant thermostats If the heating and cooling equipment have separate transfo...

Страница 10: ...made here Start Up Dehum for Fan Coil or Furnace Initial Start Up Wiring Standard A200469 During installation the thermostat will automatically detect which terminals have wires connected If something...

Страница 11: ...entilator Initial Start Up Wiring Accessory Dehumidifier for Fancoil or Furnace A200471 When selecting dehumidifier for using the equipment s DHUM or DH terminal select the appropriate relay action A...

Страница 12: ...e auxiliary heat is electric resistance then shut off the compressor when either a The manufacturer has a published lowest operating temperature for example our 5 stage inverters can only run down to...

Страница 13: ...y the fan on a W1 allowing the heat exchanger to warm up before engaging airflow so the occupants do not get a blast of cold air This setting only affects the gas heat startup sequence it will not del...

Страница 14: ...latent capacity of the evaporator coil while reducing sensible capacity Installation Settings Thresholds Cool Dissipation A200478 Cool Dissipation Time is default on but the feature should only be us...

Страница 15: ...to 76 degrees the 2nd stage will come on Then both will run together until the room temperature is satisfied at 74 Reverse staging works example If there is a 74 degree cooling setpoint the 1st stage...

Страница 16: ...200482 The Auxiliary Heat Maximum Outdoor Temperature specifies when the heat pump should be able to handle the heating load solo without the need for auxiliary electric heat to assist Aux heat will b...

Страница 17: ...the thermostat the maximum difference allowed between the thermostat and hottest or coldest rooms in the home If a sensor measures a temperature that is significantly outside of this range it probabl...

Страница 18: ...and the sensor stops detecting occupancy the thermostat s temperature data is gradually and not immediately removed from the calculation A200488 Each sensor can be used with a Comfort Setting Home Aw...

Страница 19: ...nd without obligations 19 Training My Learning Center is your central location for professional residential HVAC training resources that help strengthen careers and businesses We believe in providing...

Страница 20: ...pany Edition Date 04 21 Catalog No II EBSTATE 02 Replaces II EBSTATE 01 Advanced Installation and Configuration Instructions Manufacturer reserves the right to change at any time specifications and de...

Отзывы: