: Advanced Installation and Configuration Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
11
Initial Start-Up –> Wiring -> Accessory
A200470
Select which accessory is installed if any; No accessory, Humidifier, Dehumidifier, or Ventilator
Initial Start-Up –> Wiring -> Accessory -> Dehumidifier for Fancoil or Furnace
A200471
When selecting dehumidifier for using the equipment’s DHUM or DH terminal, select the appropriate relay action. A fan coil or furnace will
dehumidify when the Dehum input is
Open
.
Initial Start-Up –> Heat Pump
A200472
Bryant heat pumps need the reversing valve (O terminal) to be energized on a cooling call, so
On cool
should be selected. Some other equipment
manufacturers could energize the reversing valve on a heat call.