SECTION 4.4
DIAGNOSTIC TESTS
INTRODUCTION
Perform these "Diagnostic Tests" in conjunction with
the "Troubleshooting Flow Charts" of Section 4.3.
The test procedures and methods presented in this
section are not exhaustive. We could not possibly
know of, evaluate and advise the service trade of all
conceivable ways in which testing and trouble
diagnosis might be performed. We have not
undertaken any such broad evaluation.
TEST 41 - CHECK POSITION OF AUTO-OFF-
MANUAL SWITCH
DISCUSSION:
If the standby system is to operate automatically, the
generator Auto-Off-Manual switch must be set to
AUTO. That is, the generator will not crank and start
on occurrence of a "Utility" power outage unless that
switch is at AUTO. In addition, the generator will not
exercise every seven (7) days as programmed unless
the switch is at AUTO.
PROCEDURE:
With the Auto-Off-Manual switch set to "Auto,” test
automatic operation. Testing of automatic operation
can be accomplished by turning OFF the Utility power
supply to the transfer switch. When the utility power is
turned OFF, the standby generator should crank and
start. Following startup, transfer to the standby source
should occur. Refer to Section 1.8 in this manual. An
"Automatic Operating Sequences Chart" is provided
in Section 1.7. Use the chart as a guide in evaluating
automatic operation.
Following generator startup and transfer to the
standby source, turn ON the utility power supply to
the transfer switch. Retransfer back to the "Utility"
source should occur. After an "engine cool down
timer" has timed out, generator shutdown should
occur.
RESULTS:
1. If normal automatic operation is obtained, discontinue
tests.
2. If engine does not crank when "Utility" power is turned
off, proceed to Test 42.
3. If engine cranks but won't start, go to Problem 10 in
Section 4.3.
4. If engine cranks and starts, but transfer to "Standby"
does not occur, go to Problem 5 in Section 3.3.
5. If transfer to "Standby" occurs, but retransfer back to
"Utility" does not occur when utility source voltage is
restored, go to Problem 6 in Section 3.3.
TEST 42 - TRY A MANUAL START
DISCUSSION:
The first step in troubleshooting for an "engine won't
crank" condition is to determine if the problem is
peculiar to automatic operations only or if the engine
won't crank manually either.
PROCEDURE:
1. On the generator panel, set the Auto-Off-Manual switch
to OFF.
2. Set the generator main line circuit breaker to its OFF or
open position.
3. Set the generator Auto-Off-Manual switch to MANUAL.
a. The engine should crank cyclically through it’s
"crank-rest" cycles until it starts.
b. Let the engine stabilize and warm up for a few
minutes after it starts.
RESULTS:
1. If the engine cranks manually but does not crank
automatically, go to Test 43.
2. If the engine does not crank manually, proceed to
Problem 9 in the "Troubleshooting Flow Charts".
TEST 43- TEST AUTO-OFF-MANUAL SWITCH
DISCUSSION:
When the Auto-Off-Manual switch is set to AUTO
position, battery voltage (12 volts DC) is delivered to
the circuit board via Wire 15A, the closed switch
terminal, Wire 15A, and Pin 10 of the circuit board
connector. This voltage is needed to operate the
circuit board.
Setting the switch to its "Manual" position delivers
battery voltage to the circuit board for its operation. In
addition, when the switch is set to "Manual", 12 volts
DC is supplied to the circuit board via Pin 11 of the
board, Wire 239, the closed switch contacts, Wire 17
and Pin 9 of the circuit board connector.
Figure 1. Schematic of Auto-Off-Manual Switch
239
A. Set to "Auto"
15
15A
15A
17
5
6
4
3
1
2
239
B. Set to "Manual"
15
15A
15A
17
5
6
4
3
1
2
DC CONTROL
PART 4
Page 97
Содержание ASPAS1BBA007
Страница 4: ...Page 4 SPECIFICATIONS MOUNTING DIMENSIONS...
Страница 5: ...Page 5 SPECIFICATIONS MOUNTING DIMENSIONS...
Страница 24: ...Page 24 NOTES PART 1 GENERAL INFORMATION...
Страница 32: ...Page 32 SECTION 2 3 TROUBLESHOOTING FLOWCHARTS PART 2 AC GENERATORS...
Страница 33: ...Page 33 SECTION 2 3 TROUBLESHOOTING FLOWCHARTS AC GENERATORS PART 2...
Страница 34: ...Page 34 SECTION 2 3 TROUBLESHOOTING FLOWCHARTS PART 2 AC GENERATORS...
Страница 60: ...Page 60 SECTION 3 3 TROUBLESHOOTING FLOW CHARTS PART 3 V TYPE PREPACKAGED TRANSFER SWITCHES...
Страница 70: ...Page 70 SECTION 3 4 DIAGNOSTIC TESTS PART 3 V TYPE PREPACKAGED TRANSFER SWITCHES...
Страница 90: ...Page 90 SECTION 4 3 TROUBLESHOOTING FLOW CHARTS PART 4 DC CONTROL...
Страница 91: ...Page 91 SECTION 4 3 TROUBLESHOOTING FLOW CHARTS DC CONTROL PART 4...
Страница 92: ...Page 92 SECTION 4 3 TROUBLESHOOTING FLOW CHARTS PART 4 DC CONTROL...
Страница 93: ...Page 93 SECTION 4 3 TROUBLESHOOTING FLOW CHARTS DC CONTROL PART 4...
Страница 94: ...Page 94 SECTION 4 3 TROUBLESHOOTING FLOW CHARTS PART 4 DC CONTROL...
Страница 95: ...Page 95 SECTION 4 3 TROUBLESHOOTING FLOW CHARTS DC CONTROL PART 4...
Страница 138: ...PART 7 ELECTRICAL DATA WIRING DIAGRAM 8 CIRCUIT LOAD CENTER Page 138 DRAWING 0E7687A...
Страница 140: ...Page 140 DRAWING 07687 PART 7 ELECTRICAL DATA WIRING DIAGRAM 10 12 CIRCUIT LOAD CENTER...
Страница 142: ...Page 142 PART 7 ELECTRICAL DATA NOTES...
Страница 144: ...Part No 0F4676 Revision 02 25 05 Printed in U S A Catalog No DMASPAS 07 1...