Page 28
SECTION 2.1
DESCRIPTION & COMPONENTS
PART 2
AC GENERATORS
Figure 5. Excitation Circuit Breaker
VOLTAGE REGULATOR:
A typical voltage regulator is shown in Figure 6.
Unregulated AC output from the stator excitation
winding is delivered to the regulator's DPE terminals,
via Wire 2, the excitation circuit breaker, Wire 162,
and Wire 6. The voltage regulator rectifies that current
and, based on stator AC power winding sensing,
regulates it. The rectified and regulated excitation
current is then delivered to the rotor windings from the
positive (+) and negative (-) regulator terminals, via
Wire 4 and Wire 1. Stator AC power winding
“sensing” is delivered to the regulator "SEN" terminals
via Wires 11 and 22.
The regulator provides "over-voltage" protection, but
does not protect against "under-voltage". On
occurrence of an "over-voltage' condition, the
regulator will "shut down" and complete loss Of
excitation current to the rotor will occur. Without
excitation current, the generator AC output voltage
will drop to approximately one-half (or lower) of the
unit's rated voltage.
Figure 6. Typical Voltage Regulator
A single red lamp (LED) glows during normal
operation. The lamp will become dim if excitation
winding AC output diminishes. It will go out on
occurrence of an open condition in the sensing AC
output circuit.
An adjustment potentiometer permits the stator AC
power winding voltage to be adjusted. Perform this
adjustment with the generator running at no-load, and
with a 62 Hz AC frequency (62 Hz equals 3720 rpm).
At the stated no-load frequency, adjust to obtain a
line-to-line AC voltage of about 252 volts.
MAIN LINE CIRCUIT BREAKER:
The main line circuit breaker protects the generator
against electrical overload. See “Specifications” on
inside front cover of this manual for amp ratings.
Содержание ASPAS1BBA007
Страница 4: ...Page 4 SPECIFICATIONS MOUNTING DIMENSIONS...
Страница 5: ...Page 5 SPECIFICATIONS MOUNTING DIMENSIONS...
Страница 24: ...Page 24 NOTES PART 1 GENERAL INFORMATION...
Страница 32: ...Page 32 SECTION 2 3 TROUBLESHOOTING FLOWCHARTS PART 2 AC GENERATORS...
Страница 33: ...Page 33 SECTION 2 3 TROUBLESHOOTING FLOWCHARTS AC GENERATORS PART 2...
Страница 34: ...Page 34 SECTION 2 3 TROUBLESHOOTING FLOWCHARTS PART 2 AC GENERATORS...
Страница 60: ...Page 60 SECTION 3 3 TROUBLESHOOTING FLOW CHARTS PART 3 V TYPE PREPACKAGED TRANSFER SWITCHES...
Страница 70: ...Page 70 SECTION 3 4 DIAGNOSTIC TESTS PART 3 V TYPE PREPACKAGED TRANSFER SWITCHES...
Страница 90: ...Page 90 SECTION 4 3 TROUBLESHOOTING FLOW CHARTS PART 4 DC CONTROL...
Страница 91: ...Page 91 SECTION 4 3 TROUBLESHOOTING FLOW CHARTS DC CONTROL PART 4...
Страница 92: ...Page 92 SECTION 4 3 TROUBLESHOOTING FLOW CHARTS PART 4 DC CONTROL...
Страница 93: ...Page 93 SECTION 4 3 TROUBLESHOOTING FLOW CHARTS DC CONTROL PART 4...
Страница 94: ...Page 94 SECTION 4 3 TROUBLESHOOTING FLOW CHARTS PART 4 DC CONTROL...
Страница 95: ...Page 95 SECTION 4 3 TROUBLESHOOTING FLOW CHARTS DC CONTROL PART 4...
Страница 138: ...PART 7 ELECTRICAL DATA WIRING DIAGRAM 8 CIRCUIT LOAD CENTER Page 138 DRAWING 0E7687A...
Страница 140: ...Page 140 DRAWING 07687 PART 7 ELECTRICAL DATA WIRING DIAGRAM 10 12 CIRCUIT LOAD CENTER...
Страница 142: ...Page 142 PART 7 ELECTRICAL DATA NOTES...
Страница 144: ...Part No 0F4676 Revision 02 25 05 Printed in U S A Catalog No DMASPAS 07 1...