Bryant ASPAS1BBA Скачать руководство пользователя страница 6

Only qualified electricians or contractors should
attempt such installations, which must comply
strictly with applicable codes, standards and
regulations.

1.1

UNPACKING/INSPECTION

After unpacking, carefully inspect the contents 

for damage.
• This standby generator set has been factory supplied

with a weather protective enclosure that is intended for

outdoor installation only.

• This UL listed standby generator set is packaged with

an automatic transfer switch with built in load center.

The combination transfer switch and load center is

pre-wired with a two foot and 30 foot conduit. Circuit

breakers for emergency circuit connections are

included.

• This UL listed, 2-pole switch is rated at 100 AC

amperes at 250 volts maximum. 

This transfer switch

is for indoor use only.

If this generator is used to power electrical load
circuits normally powered by a utility power
source, it is required by code to install a
transfer switch. The transfer switch must
effectively isolate the electrical system from the
utility distribution system when the generator
is operating (NEC 700, 701 & 702). Failure to
isolate an electrical system by such means will
result in damage to the generator and also may
result in injury or death to utility power
workers due to backfeed of electrical energy.

If any loss or damage is noted at time of delivery, have

the person(s) making the delivery note all damage on the

freight bill or affix their signature under the consignor's

memo of loss or damage.
If a loss or damage is noted after delivery, separate the

damaged materials and contact the Bryant for claim

procedures.
“Concealed damage” is understood to mean damage to

the contents of a package that is not in evidence at the

time of delivery, but is discovered later.

1.2

PROTECTION SYSTEMS

Unlike an automobile engine, the generator may have to

run for long periods of time with no operator present to

monitor engine conditions. For that reason, the engine is

equipped with the following systems that protect it

against potentially damaging conditions:
1. Low Oil Pressure Sensor

3. Overcrank

2. High Temperature Sensor

4. Overspeed

There are LED readouts on the control panel to notify

personnel that one of these faults has occurred. There is

also a “System Set” LED that is lit when all of the

conditions describe in Section 1.3 are true.

1.3

NEC REQUIREMENT FOR ARC
FAULT CIRCUIT INTERRUPTION
BREAKER FOR BEDROOMS

In 2001, the National Electric Code (NEC) introduced a

requirement for new construction. This new requirement

indicates the need for Arc Fault Circuit Interrupters to be

used to protect the complete branch circuit that feeds a

dwelling bedroom. The actual NEC requirement is

indicated below.

1.3.1 SECTION 210.12 ARC FAULT CIRCUIT

INTERRUPTER PROTECTION

1. Definition:  An arc fault circuit interrupter is a device

intended to provide protection from the effects of arc

faults by recognizing characteristics unique to arcing

and by functioning to de-energize the circuit when an

arc fault is detected.

2. Dwelling Unit Bedrooms:  All branch circuits that

supply 125 volt, single-phase, 15 and 20 ampere

outlets installed in dwelling unit bedrooms shall be

protected by an arc fault circuit interrupter listed to

provide protection of the entire branch circuit.

Section 210.12 requires that AFCI protection be provided

on branch circuits that supply outlets (receptacle,

lighting, etc.) in dwelling bedrooms. The requirement is

limited to 15 and 20 ampere, 125 volt circuits. There is no

prohibition against providing AFCI protection on other

circuits or in locations other than bedrooms. Because

circuits are often shared between a bedroom and other

areas such as closets and hallways, providing AFCI

protection on the complete circuit would comply with

210.12.
If during the installation of the Bryant Home Standby

system the decision is made to provide back up power to

a bedroom branch circuit, then the circuit breaker in the

Bryant Transfer Switch should be replaced with an Arc

Fault Circuit Interrupter.
It is most important that breakers only be switched like for

like. For instance, if replacing a 15A breaker, it MUST be

replaced with a 15A AFCI breaker. Likewise, a 20A

breaker MUST be replaced with a 20A AFCI.
These AFCI breakers are available at the nearest

electrical wholesaler or hardware store.
Siemens Item #

Description

Q115AF

15A Single Pole AFCI

Q120AF

20A Single Pole AFCI

‹

!

DANGER

Section 1 — General Information

Bryant Air-cooled 7 kW, 12 kW and 15 kW Generators

4

Bryant

Содержание ASPAS1BBA

Страница 1: ...ic Standby Generators Models ASPAS1BBA007 6 kW NG 7 kW LP ASPAS1BBA012 12 kW NG 12 kW LP ASPAS1BBA015 13 kW NG 15 kW LP DEADLY EXHAUST FUMES OUTDOOR INSTALLATION ONLY DANGER Not intended for use as Pr...

Страница 2: ...d or property of others This symbol points out potential explosion hazard This symbol points out potential fire hazard This symbol points out potential electrical shock hazard The operator is responsi...

Страница 3: ...ery Installation 8 1 11 The Battery 8 Section 2 Operation 9 2 1 Break in Procedure 9 2 2 Using the Auto Off Manual Switch 9 2 3 Automatic Transfer Operation 10 2 4 Sequence of Automatic Operation 10 2...

Страница 4: ...mpliance with applicable codes and standards Following installation do nothing that might render the system unsafe or in noncompliance with such codes and standards Keep hands feet clothing etc away f...

Страница 5: ...ed in accordance with the manufacturer s instructions and recommendations Following proper installation do nothing that might alter a safe installation and render the unit in noncompliance with the af...

Страница 6: ...the control panel to notify personnel that one of these faults has occurred There is also a System Set LED that is lit when all of the conditions describe in Section 1 3 are true 1 3 NEC REQUIREMENT F...

Страница 7: ...ck Data Decal Control Panel Fuel Regulator Fuel Inlet GFCI Outlet Oil Filter Battery Compartment Exhaust Enclosure Oil Filter Battery Compartment Fuel Inlet GFCI Outlet Control Panel Data Decal Oil Di...

Страница 8: ...as fuel Btu content ambient temperature altitude engine power and condition etc Maximum power decreases about 3 5 percent for each 1 000 feet above sea level and also will decrease about 1 percent for...

Страница 9: ...liquid propane LP gas are highly explosive Even the slightest spark can ignite such fuels and cause an explosion No leakage of fuel is permitted Natural gas which is lighter than air tends to collect...

Страница 10: ...hock and high short circuit current The following precautions are to be observed when working on batteries Remove the 7 5A and 15A fuses from the generator control panel Remove watches rings or other...

Страница 11: ...unit will continue to run for one minute and then shut down 9 Allow the unit to cool 10 Set the generator s main circuit breaker to its OFF or OPEN position 11 Set the generator s AUTO OFF MANUAL swi...

Страница 12: ...tor is not running This outlet is protected by a 15 amp circuit breaker located in the generator control panel Figure 3 1 2 4 SEQUENCE OF AUTOMATIC OPERATION The generator s control panel houses a con...

Страница 13: ...e should shut down 4 Check that utility power supply to the transfer switch is turned OFF Do not attempt to activate the transfer switch manually until all power voltage supplies to the switch have be...

Страница 14: ...light indicating an over crank failure The AUTO OFF MANUAL switch will need to be set to OFF and then back to AUTO to reset the generator control board NOTE If the fault is not repaired the over cran...

Страница 15: ...kW Figure 3 3 Oil Dipstick and Fill 12 kW and 15 kW 3 3 CHANGING THE ENGINE OIL 3 3 1 ENGINE OIL RECOMMENDATIONS Use oil of American Petroleum Institute API Service Class SG SH or SJ Use all season S...

Страница 16: ...side of the air box and around edges 4 Install the new air cleaner into the air box 5 Install the cover Turn the two cover screws clockwise to tighten See the Service Schedule Section 4 1 for air clea...

Страница 17: ...trolyte contacts the eyes flush thoroughly and immediately with water and seek medical attention and Spilled electrolyte is to be washed down with an acid neutralizing agent A common practice is to us...

Страница 18: ...completely Refill the crankcase with oil See Engine Oil Recommendations Section 3 3 1 7 Attach a tag to the engine indicating the viscosity and classification of the oil in the crankcase 8 Remove the...

Страница 19: ...Repair is Needed FUEL Fuel lines and connections X M LUBRICATION Oil level X M Oil X AFTER BREAK IN AND Y Oil filter X AFTER BREAK IN AND Y COOLING Enclosure louvers X X W BATTERY Remove corrosion X X...

Страница 20: ...and runs rough or damaged 2 Defective spark plug s 2 Clean re gap or replace plug s 3 Fuel Regulator not set 3 Set Fuel Regulator 4 Fuel Pressure incorrect 4 Confirm fuel pressure to regulator is 11...

Страница 21: ...misuse abuse negligence or improper installation As with all mechanical devices the Bryant engines need periodic part s service and replacement to perform well Failures caused by any external cause or...

Страница 22: ...ngine or a part component thereof has failed due to abuse neglect improper maintenance or unapproved modifications or the use of counterfeit and or grey market parts not made supplied or approved by G...

Страница 23: ...elow Any such emissions related part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period prior to the first scheduled replacement point for such...

Страница 24: ...PART NO 0F4108 13AS PA1 REV A 12 17 04 FORM OM18 1 PRINTED IN U S A...

Отзывы: