Bryant ASPAS1BBA Скачать руководство пользователя страница 20

18 Bryant

Section 5 — Troubleshooting 

Bryant Air-cooled 7 kW, 12 kW and 15 kW Generators

5.1 TROUBLESHOOTING 

GUIDE

PROBLEM

CAUSE

CORRECTION

The engine will not crank.

1. Fuse blown.

1. Replace 15A fuse in generator 

control panel.

2. Loose, corroded or defective

2. Tighten, clean or replace

battery cables.

as necessary.

3. Defective starter contactor. (7 kW)

3. *

4. Defective starter motor.

4. *

5. Dead Battery.

5. Charge or replace battery.

The engine cranks but 

1. Out of fuel.

1. Replenish fuel.

will not start.

2. Defective fuel solenoid (FS).

2. *

3. Open #14 wire from 

3. *

engine control board.

4. Defective spark plug(s).

4. Clean, re-gap or replace plug(s).

5. Valve lash out of adjustment.

5. *

The engine starts hard

1. Air cleaner plugged

1. Check, replace air cleaner.

and runs rough.

or damaged.

2. Defective spark plug(s).

2. Clean, re-gap or replace plug(s).

3. Fuel Regulator not set.

3. Set Fuel Regulator.

4. Fuel Pressure incorrect.

4. Confirm fuel pressure to regulator

is 11-14” water column (0.4-0.5 psi)

for LP, and 5-7” water colum (0.18-

0.25 psi) for natural gas.

The Auto/Off/Manual switch 

1. Defective switch.

1. *

is set to OFF, but the engine

2. Auto/Off/Manual switch

2. *

continues to run.

wired incorrectly.

3. Defective control board. 

3. *

There is no AC output from 

1. Main line circuit breaker open.

1. Reset circuit breaker 

the generator.

to ON (or closed).

2. Generator internal failure.

2. *

There is no transfer to 

1. Defective transfer switch coil.

1. *

standby after utility 

2. Defective transfer relay.

2. *

source failure.

3. Transfer relay circuit open.

3. *

4. Defective control logic board.

4. *

Unit consumes large

Break-in procedure

*

amounts of oil.

not followed (see Section 2.1).

*Contact the nearest Bryant Dealer for assistance.

Содержание ASPAS1BBA

Страница 1: ...ic Standby Generators Models ASPAS1BBA007 6 kW NG 7 kW LP ASPAS1BBA012 12 kW NG 12 kW LP ASPAS1BBA015 13 kW NG 15 kW LP DEADLY EXHAUST FUMES OUTDOOR INSTALLATION ONLY DANGER Not intended for use as Pr...

Страница 2: ...d or property of others This symbol points out potential explosion hazard This symbol points out potential fire hazard This symbol points out potential electrical shock hazard The operator is responsi...

Страница 3: ...ery Installation 8 1 11 The Battery 8 Section 2 Operation 9 2 1 Break in Procedure 9 2 2 Using the Auto Off Manual Switch 9 2 3 Automatic Transfer Operation 10 2 4 Sequence of Automatic Operation 10 2...

Страница 4: ...mpliance with applicable codes and standards Following installation do nothing that might render the system unsafe or in noncompliance with such codes and standards Keep hands feet clothing etc away f...

Страница 5: ...ed in accordance with the manufacturer s instructions and recommendations Following proper installation do nothing that might alter a safe installation and render the unit in noncompliance with the af...

Страница 6: ...the control panel to notify personnel that one of these faults has occurred There is also a System Set LED that is lit when all of the conditions describe in Section 1 3 are true 1 3 NEC REQUIREMENT F...

Страница 7: ...ck Data Decal Control Panel Fuel Regulator Fuel Inlet GFCI Outlet Oil Filter Battery Compartment Exhaust Enclosure Oil Filter Battery Compartment Fuel Inlet GFCI Outlet Control Panel Data Decal Oil Di...

Страница 8: ...as fuel Btu content ambient temperature altitude engine power and condition etc Maximum power decreases about 3 5 percent for each 1 000 feet above sea level and also will decrease about 1 percent for...

Страница 9: ...liquid propane LP gas are highly explosive Even the slightest spark can ignite such fuels and cause an explosion No leakage of fuel is permitted Natural gas which is lighter than air tends to collect...

Страница 10: ...hock and high short circuit current The following precautions are to be observed when working on batteries Remove the 7 5A and 15A fuses from the generator control panel Remove watches rings or other...

Страница 11: ...unit will continue to run for one minute and then shut down 9 Allow the unit to cool 10 Set the generator s main circuit breaker to its OFF or OPEN position 11 Set the generator s AUTO OFF MANUAL swi...

Страница 12: ...tor is not running This outlet is protected by a 15 amp circuit breaker located in the generator control panel Figure 3 1 2 4 SEQUENCE OF AUTOMATIC OPERATION The generator s control panel houses a con...

Страница 13: ...e should shut down 4 Check that utility power supply to the transfer switch is turned OFF Do not attempt to activate the transfer switch manually until all power voltage supplies to the switch have be...

Страница 14: ...light indicating an over crank failure The AUTO OFF MANUAL switch will need to be set to OFF and then back to AUTO to reset the generator control board NOTE If the fault is not repaired the over cran...

Страница 15: ...kW Figure 3 3 Oil Dipstick and Fill 12 kW and 15 kW 3 3 CHANGING THE ENGINE OIL 3 3 1 ENGINE OIL RECOMMENDATIONS Use oil of American Petroleum Institute API Service Class SG SH or SJ Use all season S...

Страница 16: ...side of the air box and around edges 4 Install the new air cleaner into the air box 5 Install the cover Turn the two cover screws clockwise to tighten See the Service Schedule Section 4 1 for air clea...

Страница 17: ...trolyte contacts the eyes flush thoroughly and immediately with water and seek medical attention and Spilled electrolyte is to be washed down with an acid neutralizing agent A common practice is to us...

Страница 18: ...completely Refill the crankcase with oil See Engine Oil Recommendations Section 3 3 1 7 Attach a tag to the engine indicating the viscosity and classification of the oil in the crankcase 8 Remove the...

Страница 19: ...Repair is Needed FUEL Fuel lines and connections X M LUBRICATION Oil level X M Oil X AFTER BREAK IN AND Y Oil filter X AFTER BREAK IN AND Y COOLING Enclosure louvers X X W BATTERY Remove corrosion X X...

Страница 20: ...and runs rough or damaged 2 Defective spark plug s 2 Clean re gap or replace plug s 3 Fuel Regulator not set 3 Set Fuel Regulator 4 Fuel Pressure incorrect 4 Confirm fuel pressure to regulator is 11...

Страница 21: ...misuse abuse negligence or improper installation As with all mechanical devices the Bryant engines need periodic part s service and replacement to perform well Failures caused by any external cause or...

Страница 22: ...ngine or a part component thereof has failed due to abuse neglect improper maintenance or unapproved modifications or the use of counterfeit and or grey market parts not made supplied or approved by G...

Страница 23: ...elow Any such emissions related part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period prior to the first scheduled replacement point for such...

Страница 24: ...PART NO 0F4108 13AS PA1 REV A 12 17 04 FORM OM18 1 PRINTED IN U S A...

Отзывы: