Bryant ASPAS1BBA Скачать руководство пользователя страница 12

10 Bryant

2.3

AUTOMATIC TRANSFER 
OPERATION

To select automatic operation, do the following:
1. Make sure the transfer switch main contacts are set

to their UTILITY position, i.e., loads connected to the

utility power source (Figure 2.2).

2. Be sure that normal UTILITY power source voltage is

available to transfer switch terminal lugs N1 and N2.

3. Set the generator’s AUTO/OFF/MANUAL switch to

AUTO.

4. Set the generator’s main circuit breaker to its ON (or

closed) position.

With the preceding steps complete, the generator will

start automatically when utility source voltage drops

below a preset level. After the unit starts, loads are

transferred to the standby power source. Refer to Section

2.4, “Sequence of Automatic Operation.”

2.3.1 12 VDC ACCESSORY OUTLET

Your generator is equipped with a 12 VDC accessory

outlet in the Generator Control Panel. (Figure 2.1) With

the generator running or in standby mode, this outlet may

be used to temporarily power low power accessories

such as a work light, cell phone, radio or any other

automotive style accessory. This outlet is capable of

delivering a MAXIMUM of 7.5 Amps. If the accessory to

be used through this circuit demands too much power,

the fuse that protects this circuit will melt open and the

circuit will not be functional.  

This 12 VDC outlet draws power from the
generator's starting battery and extended use
of this outlet may drain the battery and the
engine may not start. This outlet should NOT
be used for battery charging.

2.3.2 120 VAC GFCI OUTLET

Your generator is equipped with an external, 15 amp, 120

volt, GFCI convenience outlet that is located in the right

rear of the generator enclosure. (Figures 1.1 and 1.2,

page 5) When the generator is running, in the absence of

utility power, this outlet may be used to power items

outside your home such as lights or power tools. This

outlet may also be used when utility power is present by

running the generator in manual mode. This oultlet does

not provide power if the generator is not running. This

outlet is protected by a 15-amp circuit breaker located in

the generator control panel. (Figure 3.1).

2.4

SEQUENCE OF AUTOMATIC 
OPERATION

The generator’s control panel houses a control logic

circuit board. This board constantly monitors utility power

source voltage. Should that voltage drop below a preset

level, circuit board action will signal the engine to crank

and start. After the engine starts, the circuit board signals

the transfer switch to activate and connect load circuits to

the standby power supply (load terminal lugs T1/T2

connect to terminal lugs E1/E2).
Upon restoration of utility power supply, generator circuit

board action signals the transfer switch to transfer loads

back to the utility power supply. After retransfer, the

engine is signalled to shut down.
The actual sequence of operation is controlled by 

sensors and timers on a control logic circuit board, as

follows:
A. Utility Voltage Dropout Sensor

• This sensor monitors utility source voltage.
• If utility source voltage drops below about 70 percent

of the nominal supply voltage, the sensor energizes

a 15-second timer.

• Once the timer has expired, the engine will crank and

start.

B. Engine Warm-up Time Delay

• This mechanism lets the engine warm up for about

10 seconds before the load is transferred to the

standby source.

C.Standby Voltage Sensor 

• This sensor monitors generator AC output voltage.

When the voltage has reached 50 percent of the

nominal rated voltage, transfer to standby can occur.

D.Utility Voltage Pickup Sensor 

• This sensor monitors utility power supply voltage.

When that voltage is restored above 70 percent of

the nominal source voltage, a retransfer time delay

starts timing.

E. Retransfer Time Delay 

• This timer runs for about 15 seconds.
• At end of a 15-second delay, circuit board action de-

energizes transfer relay in the transfer switch.

• Retransfer to utility power source then occurs.

F. Engine Cool-down Timer

• When the load is transferred back to utility power

source, the engine cool-down timer starts timing.

• The timer will run for about one minute, and the

generator will then shut down.

‹

!

‹

Section 2 — Operation

Bryant Air-cooled 7 kW, 12 kW and 15 kW Generators

Содержание ASPAS1BBA

Страница 1: ...ic Standby Generators Models ASPAS1BBA007 6 kW NG 7 kW LP ASPAS1BBA012 12 kW NG 12 kW LP ASPAS1BBA015 13 kW NG 15 kW LP DEADLY EXHAUST FUMES OUTDOOR INSTALLATION ONLY DANGER Not intended for use as Pr...

Страница 2: ...d or property of others This symbol points out potential explosion hazard This symbol points out potential fire hazard This symbol points out potential electrical shock hazard The operator is responsi...

Страница 3: ...ery Installation 8 1 11 The Battery 8 Section 2 Operation 9 2 1 Break in Procedure 9 2 2 Using the Auto Off Manual Switch 9 2 3 Automatic Transfer Operation 10 2 4 Sequence of Automatic Operation 10 2...

Страница 4: ...mpliance with applicable codes and standards Following installation do nothing that might render the system unsafe or in noncompliance with such codes and standards Keep hands feet clothing etc away f...

Страница 5: ...ed in accordance with the manufacturer s instructions and recommendations Following proper installation do nothing that might alter a safe installation and render the unit in noncompliance with the af...

Страница 6: ...the control panel to notify personnel that one of these faults has occurred There is also a System Set LED that is lit when all of the conditions describe in Section 1 3 are true 1 3 NEC REQUIREMENT F...

Страница 7: ...ck Data Decal Control Panel Fuel Regulator Fuel Inlet GFCI Outlet Oil Filter Battery Compartment Exhaust Enclosure Oil Filter Battery Compartment Fuel Inlet GFCI Outlet Control Panel Data Decal Oil Di...

Страница 8: ...as fuel Btu content ambient temperature altitude engine power and condition etc Maximum power decreases about 3 5 percent for each 1 000 feet above sea level and also will decrease about 1 percent for...

Страница 9: ...liquid propane LP gas are highly explosive Even the slightest spark can ignite such fuels and cause an explosion No leakage of fuel is permitted Natural gas which is lighter than air tends to collect...

Страница 10: ...hock and high short circuit current The following precautions are to be observed when working on batteries Remove the 7 5A and 15A fuses from the generator control panel Remove watches rings or other...

Страница 11: ...unit will continue to run for one minute and then shut down 9 Allow the unit to cool 10 Set the generator s main circuit breaker to its OFF or OPEN position 11 Set the generator s AUTO OFF MANUAL swi...

Страница 12: ...tor is not running This outlet is protected by a 15 amp circuit breaker located in the generator control panel Figure 3 1 2 4 SEQUENCE OF AUTOMATIC OPERATION The generator s control panel houses a con...

Страница 13: ...e should shut down 4 Check that utility power supply to the transfer switch is turned OFF Do not attempt to activate the transfer switch manually until all power voltage supplies to the switch have be...

Страница 14: ...light indicating an over crank failure The AUTO OFF MANUAL switch will need to be set to OFF and then back to AUTO to reset the generator control board NOTE If the fault is not repaired the over cran...

Страница 15: ...kW Figure 3 3 Oil Dipstick and Fill 12 kW and 15 kW 3 3 CHANGING THE ENGINE OIL 3 3 1 ENGINE OIL RECOMMENDATIONS Use oil of American Petroleum Institute API Service Class SG SH or SJ Use all season S...

Страница 16: ...side of the air box and around edges 4 Install the new air cleaner into the air box 5 Install the cover Turn the two cover screws clockwise to tighten See the Service Schedule Section 4 1 for air clea...

Страница 17: ...trolyte contacts the eyes flush thoroughly and immediately with water and seek medical attention and Spilled electrolyte is to be washed down with an acid neutralizing agent A common practice is to us...

Страница 18: ...completely Refill the crankcase with oil See Engine Oil Recommendations Section 3 3 1 7 Attach a tag to the engine indicating the viscosity and classification of the oil in the crankcase 8 Remove the...

Страница 19: ...Repair is Needed FUEL Fuel lines and connections X M LUBRICATION Oil level X M Oil X AFTER BREAK IN AND Y Oil filter X AFTER BREAK IN AND Y COOLING Enclosure louvers X X W BATTERY Remove corrosion X X...

Страница 20: ...and runs rough or damaged 2 Defective spark plug s 2 Clean re gap or replace plug s 3 Fuel Regulator not set 3 Set Fuel Regulator 4 Fuel Pressure incorrect 4 Confirm fuel pressure to regulator is 11...

Страница 21: ...misuse abuse negligence or improper installation As with all mechanical devices the Bryant engines need periodic part s service and replacement to perform well Failures caused by any external cause or...

Страница 22: ...ngine or a part component thereof has failed due to abuse neglect improper maintenance or unapproved modifications or the use of counterfeit and or grey market parts not made supplied or approved by G...

Страница 23: ...elow Any such emissions related part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period prior to the first scheduled replacement point for such...

Страница 24: ...PART NO 0F4108 13AS PA1 REV A 12 17 04 FORM OM18 1 PRINTED IN U S A...

Отзывы: