IMPORTANT — READ BEFORE INSTALLING

1. Read and become familiar with these installation in-

structions before installing this unit (Fig. 1). Retain these
instructions for future maintenance and repair.

2. Be sure the installation conforms to all applicable local

and national codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire
extinguisher available for all brazing operations.

CONTENTS

Page

SAFETY CONSIDERATIONS

. . . . . . . . . . . . . . . . . . . . . . . 1

INSTALLATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11

I. Locate the Unit

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

II. Rig and Place Unit

. . . . . . . . . . . . . . . . . . . . . . . . . . 5

III. Unit Duct and Field Connections

. . . . . . . . . . . . . . 5

PRE-START-UP

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11,12

START-UP

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12,13

I. Heating Section Start-Up and Adjustments

. . . . 12

II. Cooling Section Start-Up and Adjustments

. . . . 12

III. Indoor Airflow and Airflow Adjustments

. . . . . . . 13

CARE AND MAINTENANCE

. . . . . . . . . . . . . . . . . . . . . . . 14

I. Air Filter

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

II. Evaporator Fan and Motor

. . . . . . . . . . . . . . . . . . 14

SERVICE

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-18

I. Cleaning

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

II. Evaporator Fan and Motor

. . . . . . . . . . . . . . . . . . 15

III. Condenser Fan

. . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

IV. Electrical Controls and Wiring

. . . . . . . . . . . . . . . 16

V. Indoor Airflow

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

VI. Metering Device Servicing

. . . . . . . . . . . . . . . . . . 16

VII. Liquid Line Strainer

. . . . . . . . . . . . . . . . . . . . . . . . 16

VIII. Refrigerant Charge

. . . . . . . . . . . . . . . . . . . . . . . . . 16

IX. Replacement Parts

. . . . . . . . . . . . . . . . . . . . . . . . . 16

COOLING TROUBLESHOOTING CHART

. . . . . . . . . . . . 19

START-UP CHECKLIST

. . . . . . . . . . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

WARNING:

Improper installation, adjustment, alter-

ation, service, maintenance, or use can cause explo-
sion, fire, electric shock, or other occurrences which may
injure you or damage your property. Consult a quali-
fied installer or service agency for information or assis-
tance. The qualified installer or agency must use only
factory-authorized kits or accessories when modifying
this product.

Recognize safety information. This is the safety-alert symbol
(

). When you see this symbol on the unit and in instruc-

tions or manuals, be alert to the potential for personal
injury.

Understand the signal words — DANGER, WARNING, and
CAUTION. These words are used with the safety-alert

symbol

. Danger identifies the most serious hazards which

will result in severe personal injury or death. Warning indi-
cates a condition that could result in personal injury.
Caution is used to identify unsafe practices which would
result in minor personal injury or product and property
damage.

WARNING:

Before performing service or main-

tenance operations on system, turn off main power
switches to unit. Turn off accessory heater power switch
if applicable. Electric shock can cause personal injury.

1. The power supply (volts, phase, and hertz) must corre-

spond to that specified on unit rating plate.

2. The electrical supply provided by the utility must be suf-

ficient to handle load imposed by this unit.

3. Refer to Installation, Locate the Unit section (page 5)

and Fig. 2-4 for locations of electrical inlets, condensate
drain, duct connections, and required clearances before
setting unit in place.

4. This installation must conform with local building codes

and with NEC (National Electrical Code) or NFPA
(National Fire Protection Association) 54 TIA-54-84-1.
Refer to provincial and local plumbing or wastewater codes
and other applicable local codes.

5. Approved for outdoor installation on wood flooring or on

class A, B, or C roof covering materials.

INSTALLATION

All units can be connected into existing duct systems that are
sized properly and designed to handle the airflow shown in
the Air Delivery table and Indoor Airflow and Airflow Adjust-
ments section.

NOTE:

When installing any accessory item, see the manu-

facturer’s installation instructions packaged with the acces-
sory. Use factory-authorized kits or accessories when
modifying this unit.

Fig. 1 — Unit 564A and 764A (Size 036 Shown)

installation, start-up and
service instructions

PACKAGED AIR
CONDITIONERS

564A

Sizes 024-060

764A

Sizes 024-060

Cancels: II 564A-24-1

II 564A-24-2

6/1/96

Содержание 764A

Страница 1: ...al words DANGER WARNING and CAUTION These words are used with the safety alert symbol Danger identifies the most serious hazards which will result in severe personal injury or death Warning indi cates...

Страница 2: ...ts Power Entry Side 1066 8 42 00 Unit and Ungrounded Surfaces Power Entry Side 914 0 36 00 Unit and Block or Concrete Walls and Other Grounded Surfaces Power Entry Side 1066 8 42 00 REQUIRED CLEARANCE...

Страница 3: ...6 8 42 00 Unit and Ungrounded Surfaces Power Entry Side 914 0 36 00 Unit and Block or Concrete Walls and Other Grounded Surfaces Power Entry Side 1066 8 42 00 REQUIRED CLEARANCES FOR SERVICING mm in C...

Страница 4: ...rfaces Power Entry Side 914 0 36 00 Unit and Block or Concrete Walls and Other Grounded Surfaces Power Entry Side 1066 8 42 00 REQUIRED CLEARANCES FOR SERVICING mm in Condenser Coil Access Side 762 0...

Страница 5: ...rance of 36 in between the control box side of the unit and any electrically live parts Unit may be installed on wood flooring or on Class A B or C roof covering materials Although unit is weatherproo...

Страница 6: ...ditioning and Refrigeration Institute rated airflow at a velocity of 300 ft min for throwaway type or 450 ft min for high capacity type Recommended filters are 1 in thick If the installation requires...

Страница 7: ...rilling the duct system fastening holes into the side of the unit for duct flanges do not drill deeper than 3 4 in and use extreme care not to puncture the coil or coil tubes See Fig 11 2 Use flexible...

Страница 8: ...of improper voltage and or phase imbalance 4 Insulate low voltage wires for highest voltage con tained within conduit when low voltage control wires are run in same conduit as high voltage wires 5 Do...

Страница 9: ...y as described in Special Proce dures for 208 V Operation section on page 11 Accessory Electric Heat Wiring Refer to accessory electric heat installation instructions for information on installing acc...

Страница 10: ...9 32 11 3 15 0 31 3 36 1 44 3 50 4 45 60 41 46 15 0 20 0 41 7 48 1 57 4 65 4 60 70 53 60 060 230 1 60 207 254 26 9 128 0 1 4 6 2 41 2 50 40 141 5 0 20 8 41 2 50 40 10 0 41 7 59 8 60 55 15 0 62 5 85 9...

Страница 11: ...ed accessories should be installed on the unit Refer to separate accessory installation instructions PRE START UP WARNING Failure to observe the following warn ings could result in serious personal in...

Страница 12: ...or heat has been satisfied the evaporator fan will stop For units equipped with time delay relay evaporator fan will stop after a 30 second time delay To shut off unit set system selector switch at OF...

Страница 13: ...mended airflow is 350 to 450 cfm per each 12 000 Btuh of rated cooling capacity Table 3 shows dry coil air delivery for horizontal discharge units WARNING Disconnect electrical power to the unit be fo...

Страница 14: ...personal injury can result from sharp edges etc 3 Never place anything combustible either on or in con tact with the unit 4 Should overheating occur shut off all of the electri cal supply s I AIR FIL...

Страница 15: ...l volume of filter drier NOTE See Adjusting Refrigerant Charge on page 16 C Condenser Coil Evaporator Coil and Condensate Drain Pan WARNING Be careful Coil fins are sharp Protect hands with gloves whe...

Страница 16: ...rant system is factory charged When recharging is necessary weigh in total charge indicated on unit name plate Remove and recover any refrigerant remaining in system before recharging If system has lo...

Страница 17: ...Fig 19 Cooling Charging Chart 564A 764A024 Fig 20 Cooling Charging Chart 564A 764A030 Fig 21 Cooling Charging Chart 564A 764A036 Fig 22 Cooling Charging Chart 564A 764A042 17...

Страница 18: ...Fig 23 Cooling Charging Chart 564A 764A048 Fig 24 Cooling Charging Chart 564A 764A060 18...

Страница 19: ...er fan motor or capacitor Replace Restriction in refrigerant system Locate restriction and remove Compressor operates continuously Dirty air filter Replace filter Unit undersized for load Decrease loa...

Страница 20: ......

Страница 21: ......

Страница 22: ...n Overview Maintenance Operating Sequence A large selection of product theory and skills programs is available All programs include a video cassette and or slides and a companion booklet Use these for...

Страница 23: ......

Страница 24: ...NS AND TERMINALS FOR TIGHTNESS M VERIFY THAT UNIT INSTALLATION IS LEVEL M CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE L1...

Отзывы: