background image

COOLING TROUBLESHOOTING CHART

SYMPTOM

CAUSE

REMEDY

Compressor and con-
denser fan will not
start.

Power failure

Call power company.

Fuse blown or circuit breaker tripped

Replace fuse or reset circuit breaker.

Defective thermostat, contactor, transformer,
or control relay

Replace component.

Insufficient line voltage

Determine cause and correct.

Incorrect or faulty wiring

Check wiring diagram and rewire correctly.

Thermostat setting too high

Lower thermostat setting below room temperature.

Compressor will not
start but condenser
fan runs.

Faulty wiring or loose connections in
compressor circuit

Check wiring and repair or replace.

Compressor motor burned out, seized, or
internal overload open

Determine cause. Replace compressor.

Defective run/start capacitor, overload, or
start relay

Determine cause and replace.

One leg of 3-phase power dead

Replace fuse or reset circuit breaker.
Determine cause.

Compressor cycles
(other than normally
satisfying thermostat).

Refrigerant overcharge or undercharge

Recover refrigerant, evacuate system, and recharge
to capacities shown on nameplate.

Defective compressor

Replace and determine cause.

Insufficient line voltage

Determine cause and correct.

Blocked condenser

Determine cause and correct.

Defective run/start capacitor, overload,
or start relay

Determine cause and replace.

Defective thermostat

Replace thermostat.

Faulty condenser-fan motor or capacitor

Replace.

Restriction in refrigerant system

Locate restriction and remove.

Compressor operates
continuously.

Dirty air filter

Replace filter.

Unit undersized for load

Decrease load or increase unit size.

Thermostat set too low

Reset thermostat.

Low refrigerant charge

Locate leak, repair, and recharge.

Leaking valves in compressor

Replace compressor.

Air in system

Recover refrigerant, evacuate system, and recharge.

Condenser coil dirty or restricted

Clean coil or remove restriction.

Excessive head
pressure.

Dirty air filter

Replace filter.

Dirty condenser coil

Clean coil.

Refrigerant overcharged

Recover excess refrigerant.

Air in system

Recover refrigerant, evacuate system, and recharge.

Condenser air restricted or air short-cycling

Determine cause and correct.

Head pressure too low.

Low refrigerant charge

Check for leaks, repair and recharge.

Compressor valves leaking

Replace compressor.

Restriction in liquid tube

Remove restriction.

Excessive suction
pressure.

High heat load

Check for source and eliminate.

Compressor valves leaking

Replace compressor.

Refrigerant overcharged

Recover excess refrigerant.

Suction pressure too
low.

Dirty air filter

Replace filter.

Low refrigerant charge

Check for leaks, repair, and recharge.

Metering device or low side restricted

Remove source of restriction.

Insufficient evaporator airflow

Increase air quantity. Check filter, and replace if
necessary.

Temperature too low in conditioned area

Reset thermostat.

Outdoor ambient below 40 F

Install low-ambient kit.

Field-installed filter-drier restricted

Replace.

—19—

Содержание 764A

Страница 1: ...al words DANGER WARNING and CAUTION These words are used with the safety alert symbol Danger identifies the most serious hazards which will result in severe personal injury or death Warning indi cates...

Страница 2: ...ts Power Entry Side 1066 8 42 00 Unit and Ungrounded Surfaces Power Entry Side 914 0 36 00 Unit and Block or Concrete Walls and Other Grounded Surfaces Power Entry Side 1066 8 42 00 REQUIRED CLEARANCE...

Страница 3: ...6 8 42 00 Unit and Ungrounded Surfaces Power Entry Side 914 0 36 00 Unit and Block or Concrete Walls and Other Grounded Surfaces Power Entry Side 1066 8 42 00 REQUIRED CLEARANCES FOR SERVICING mm in C...

Страница 4: ...rfaces Power Entry Side 914 0 36 00 Unit and Block or Concrete Walls and Other Grounded Surfaces Power Entry Side 1066 8 42 00 REQUIRED CLEARANCES FOR SERVICING mm in Condenser Coil Access Side 762 0...

Страница 5: ...rance of 36 in between the control box side of the unit and any electrically live parts Unit may be installed on wood flooring or on Class A B or C roof covering materials Although unit is weatherproo...

Страница 6: ...ditioning and Refrigeration Institute rated airflow at a velocity of 300 ft min for throwaway type or 450 ft min for high capacity type Recommended filters are 1 in thick If the installation requires...

Страница 7: ...rilling the duct system fastening holes into the side of the unit for duct flanges do not drill deeper than 3 4 in and use extreme care not to puncture the coil or coil tubes See Fig 11 2 Use flexible...

Страница 8: ...of improper voltage and or phase imbalance 4 Insulate low voltage wires for highest voltage con tained within conduit when low voltage control wires are run in same conduit as high voltage wires 5 Do...

Страница 9: ...y as described in Special Proce dures for 208 V Operation section on page 11 Accessory Electric Heat Wiring Refer to accessory electric heat installation instructions for information on installing acc...

Страница 10: ...9 32 11 3 15 0 31 3 36 1 44 3 50 4 45 60 41 46 15 0 20 0 41 7 48 1 57 4 65 4 60 70 53 60 060 230 1 60 207 254 26 9 128 0 1 4 6 2 41 2 50 40 141 5 0 20 8 41 2 50 40 10 0 41 7 59 8 60 55 15 0 62 5 85 9...

Страница 11: ...ed accessories should be installed on the unit Refer to separate accessory installation instructions PRE START UP WARNING Failure to observe the following warn ings could result in serious personal in...

Страница 12: ...or heat has been satisfied the evaporator fan will stop For units equipped with time delay relay evaporator fan will stop after a 30 second time delay To shut off unit set system selector switch at OF...

Страница 13: ...mended airflow is 350 to 450 cfm per each 12 000 Btuh of rated cooling capacity Table 3 shows dry coil air delivery for horizontal discharge units WARNING Disconnect electrical power to the unit be fo...

Страница 14: ...personal injury can result from sharp edges etc 3 Never place anything combustible either on or in con tact with the unit 4 Should overheating occur shut off all of the electri cal supply s I AIR FIL...

Страница 15: ...l volume of filter drier NOTE See Adjusting Refrigerant Charge on page 16 C Condenser Coil Evaporator Coil and Condensate Drain Pan WARNING Be careful Coil fins are sharp Protect hands with gloves whe...

Страница 16: ...rant system is factory charged When recharging is necessary weigh in total charge indicated on unit name plate Remove and recover any refrigerant remaining in system before recharging If system has lo...

Страница 17: ...Fig 19 Cooling Charging Chart 564A 764A024 Fig 20 Cooling Charging Chart 564A 764A030 Fig 21 Cooling Charging Chart 564A 764A036 Fig 22 Cooling Charging Chart 564A 764A042 17...

Страница 18: ...Fig 23 Cooling Charging Chart 564A 764A048 Fig 24 Cooling Charging Chart 564A 764A060 18...

Страница 19: ...er fan motor or capacitor Replace Restriction in refrigerant system Locate restriction and remove Compressor operates continuously Dirty air filter Replace filter Unit undersized for load Decrease loa...

Страница 20: ......

Страница 21: ......

Страница 22: ...n Overview Maintenance Operating Sequence A large selection of product theory and skills programs is available All programs include a video cassette and or slides and a companion booklet Use these for...

Страница 23: ......

Страница 24: ...NS AND TERMINALS FOR TIGHTNESS M VERIFY THAT UNIT INSTALLATION IS LEVEL M CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE L1...

Отзывы: