GUIDE SPECIFICATIONS

SINGLE--PACKAGED ELECTRIC COOLING UNITS

CONSTANT VOLUME APPLICATION

HVAC GUIDE SPECIFICATIONS
SIZE RANGE:

2 TO 5 TONS, NOMINAL COOLING

MODEL NUMBER: 704C

PART I -- GENERAL

SYSTEM DESCRIPTION

Outdoor rooftop or ground mounted electric cooling unit utiliz-

ing a hermetic compressor for cooling duty and optional electric

heating. Unit shall discharge supply air vertically or horizontal-
ly as shown on contract drawings. Outdoor fan/coil section shall

have a draw--thru design with vertical discharge for minimum
sound levels.

QUALITY ASSURANCE

A. Unit shall be rated in accordance with ARI Standards

210/240, and 270.

B. Unit shall be designed in accordance with UL Standard 1995.
C. Unit shall be manufactured in a facility registered to ISO

9001 manufacturing quality standard

D. Unit shall be UL listed and c--UL certified as a total package

for safety requirements.

E. Roof curb shall be designed to conform to NRCA Standards.
F. Insulation and adhesives shall meet NFPA 90A requirements

for flame spread and smoke generation.

G. Cabinet insulation shall meet ASHRAE Standard 62P.

DELIVERY, STORAGE, AND HANDLING

Unit shall be stored and handled per manufacturer’s recommen-
dations.

PART 2-- PRODUCTS

EQUIPMENT

A. General:

Factory--assembled, single--piece, cooling unit. Contained

within the unit enclosure shall be all factory wiring, piping,
controls, refrigerant charge (R--410A), and special features re-

quired prior to field start--up.

B. Unit Cabinet:

1. Unit cabinet shall be constructed of phosphated,

zinc--coated, prepainted steel capable of withstanding 500
hrs of salt spray.

2. Normal service shall be through a single removable cabinet

panel.

3. The unit shall be constructed on a rust proof unit base that has

an externally trapped, integrated sloped drain pan.

4. Indoor fan compartment top surface shall be insulated with

a minimum 1/2--in. thick, flexible fiberglass insulation,
coated on the air side and retained by adhesive and
mechanical means. The indoor wall sections will be

insulated with a foil--faced insulation capable of being wiped
clean. Aluminum foil--faced fiberglass insulation shall be

used in the entire indoor air cavity seciton.

5. Unit shall have a field--supplied condensate trap.

C. Fans:

1. The indoor fan shall be variable--speed motor and control, as

shown on equipment drawings.

2. Fan wheel shall be made from steel, be double--inlet type.

It

shall

have

forward--curved

blades

with

a

corrosion--resistant finish and shall be dynamically
balanced.

3. Outdoor fan shall be of the direct--driven propeller type with

aluminum blades, riveted to corrosion--resistant steel
spiders. It shall be dynamically balanced and discharge air

vertically.

D. Compressor:

1. Fully hermetic compressors with factory--installed

vibration isolation.

2. Scroll compressors shall be standard on all units.

E. Coils:

1. Indoor and outdoor coils shall have aluminum plate fins

mechanically bonded to seamless copper tubes with all joints

brazed.

2. Tube sheet openings shall be bellied to prevent tube wear.

F. Refrigerant Metering Device:

Refrigerant metering device shall be of the TXV type.

G. Filters:

Filter section shall consist of field--installed, throw--away,
1--in. thick fiberglass filters of commercially available sizes.

H. Controls and Safeties:

1. Unit controls shall be complete with self--contained low

voltage control circuit.

2. Units shall incorporate an internal compressor protector that

provides reset capability.

3. Unit shall provide high and low/loss--of--charge pressure

safety protection.

I. Operating Characteristics:

1. Unit shall be capable of starting and running at 125

°

F

ambient outdoor temperature, exceeding maximum load
criteria of ARI Standard 240.

2. Compressor with standard controls shall be capable of

operation down to 55

°

F ambient outdoor temperature.

J. Electrical Requirements:

All unit power wiring shall enter unit cabinet at a single loca-

tion.

K. Motors:

1. Compressor motors shall be of the refrigerant--cooled type

with line--break thermal and current overload protection.

2. All fan motors shall have permanently lubricated bearings

and inherent automatic reset thermal overload protection.

3. Outdoor fan motor shall be totally enclosed.

L. Grille

1. Louvered Grille:

Louvered grille shall be standard on all units.

704C

Содержание 704C EVOLUTION

Страница 1: ...iency Each compressor is hermetically sealed against contamination to help promote longer life and dependable operation Vibration isolation provides quiet operation Compressors have internal high pres...

Страница 2: ...ch keeps the conditioned air from being affected by the outdoor ambient temperature and provides improved indoor air quality Conforms to American Society of Heating Refrigeration and Air Conditioning...

Страница 3: ...A SEER Sound Ratings dBA 024 2 800 24 000 11 13 0 72 030 2 1 2 1000 28 800 11 13 0 72 036 3 1200 36 000 11 13 0 74 042 3 1 2 1400 41 000 11 13 0 74 048 4 1600 45 000 11 13 0 78 060 5 1750 57 000 11 1...

Страница 4: ...fficiency 700 875 1050 1225 1400 1750 Max 800 1000 1200 1400 1600 2000 Size in 10x10 10x10 11x10 11x10 11x10 11x10 Motor HP RPM 1 2 1 2 3 4 3 4 3 4 1 HIGH PRESSURE SWITCH psig 650 15 420 25 Cutout Res...

Страница 5: ...m s variable speed indoor blower delivers Bryant s patented PerfectHumidity technology that allows for even greater humidity control Along with more precisely controlling temperature and humidity the...

Страница 6: ...FILTER RACK EVAPORATOR COIL TOP FILTER RACK BEND FLANGE AT 90 SCREW TO DIVIDER WITH 1 IN SCREW BOTTOM FILTER RACK MANUAL OUTSIDE AIR DAMPER DAMPER BLADE MANUAL OUTSIDE AIR HOOD REPLACEMENT PANEL 704C...

Страница 7: ...7 A06120 704C024 036 Unit Dimensions 704C...

Страница 8: ...8 A06121 704C042 060 Unit Dimensions 704C...

Страница 9: ...G E F G D E A05308 UNIT SIZE ODS CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM E IN MM F IN MM G IN MM 704C024 036 CPRFCURB006A00 8 203 11 279 16 1 2 419 28 3 4 730 30 3 8 771 44 5 16 1126 45 15 16 1...

Страница 10: ...ased on required cooling capacity Enter Net Cooling Capacities table at condenser entering temperature of 95 F The 036 unit at 1200 cfm and 67 F ewb entering wet bulb will provide a total capacity of...

Страница 11: ...21 1 17 8 18 0 19 4 21 4 SHC 17 8 17 0 14 5 11 7 18 5 18 1 15 5 12 3 kW 2 8 2 8 3 0 3 0 2 9 2 9 3 0 3 0 Cooling Extended Performance Table 704C030 Temp F Outdoor Air Entering Condenser Evaporator Air...

Страница 12: ...8 5 31 5 28 1 27 2 29 3 32 3 SHC 26 2 20 9 21 9 17 1 27 8 23 5 24 7 18 9 kW 4 2 4 3 4 3 4 3 4 4 4 4 4 4 4 4 Cooling Extended Performance Table 704C042 Temp F Outdoor Air Entering Condenser Evaporator...

Страница 13: ...5 3 38 8 34 6 33 3 35 9 39 5 SHC 32 4 27 0 28 4 21 9 34 1 28 9 30 6 23 3 kW 5 5 5 4 5 5 5 5 5 5 5 5 5 5 5 5 Cooling Extended Performance Table 704C060 Temp F Outdoor Air Entering Condenser Evaporator...

Страница 14: ...ES 1 Ratings are net they account for the effects of the evaporator fan motor power and heat 2 Direct interpolation is permissible Do not extrapolate 3 The following formulas may be used Sensible capa...

Страница 15: ...IR FLEXIBLE DUCT CEILING CONCENTRIC DIFFUSER BOX FIELD SUPPLIED SUPPLY AIR FLEXIBLE DUCT ROOF MOUNTING CURB C00023 USER INTERFACE DISCONNECT PER NEC FROM POWER SOURCE RETURN AIR TOP COVER FROM GAS LIN...

Страница 16: ...nflow openings Remove theinsertssimilar toremoving anelectrical knockout Leave onduct covers to seal the horizontal discharge openings in the unit Units installed in horizontal discharge orientation d...

Страница 17: ...6 60 6 60 70 11 3 15 0 54 2 62 5 76 2 86 6 80 90 15 0 20 0 72 2 83 3 98 8 112 7 100 125 208 230 3 60 187 253 15 4 88 0 0 8 6 8 26 9 26 9 35 35 3 8 5 0 10 4 12 0 26 9 26 9 30 35 7 5 10 0 20 8 24 1 34...

Страница 18: ...a phase imbalance in supply volt age is greater than 2 Use the following formula to determine the percentage of voltage imbalance Voltage imbalance max voltage deviation from average voltage 100 x av...

Страница 19: ...19 TYPICAL WIRING SCHEMATIC 230 1 60 7 0 A06126 704C...

Страница 20: ...20 TYPICAL WIRING SCHEMATIC 230 3 60 5 0 A06127 704C...

Страница 21: ...capacity as defined by unit size Actual airflow request will be adjusted from nominal using indoor and outdoor temperature and indoor humidity data to optimize the system operation for occupant comfo...

Страница 22: ...ation capableof beingwiped clean Aluminum foil faced fiberglass insulation shall be used in the entire indoor air cavity seciton 5 Unit shall have a field supplied condensate trap C Fans 1 The indoor...

Страница 23: ...tion whichshallallow unitto operatedown to0 F outdoorambi ent temperature in cooling 6 Filter Rack Kit Shall provide filter mounting for downflow and horizontal applications 7 Square To Round Duct Tra...

Страница 24: ...e or change at any time specifications or designs without notice and without incurring obligations E2006 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in U S A Edition...