704C CORNER WEIGHTS (IN POUNDS)

A06124

Corner Weights (Lbs.)

Corner Weights (Small Cabinet)

Corner Weights (Large Cabinet)

M

ode

l

704C

Unit

024

030

036

M

ode

l

704C

Unit

042

048

060

Total Weight

349

349

373

Total Weight

438

463

499

Corner Weight 1

70

70

75

Corner Weight 1

88

98

107

Corner Weight 2

54

54

58

Corner Weight 2

68

61

70

Corner Weight 3

84

84

90

Corner Weight 3

106

127

136

Corner Weight 4

141

141

150

Corner Weight 4

177

177

186

SELECTION PROCEDURE

Determine cooling and heating requirements at design
conditions:

Given:
REQUIRED COOLING CAPACITY (TC)

34,500 BTUH

. . . . .

SENSIBLE HEAT CAPACITY (SHC)

26,000 BTUH

. . . . . . . .

REQUIRED HEATING CAPACITY (SHC)

15,000 BTUH

. . . .

CONDENSER ENTERING AIR TEMPERATURE

95

°

F

. . . . .

INDOOR--AIR TEMPERATURE

80

°

F EDB, 67

°

F EWB

. . . . .

EVAPORATOR AIR QUANTITY

1200 CFM

. . . . . . . . . . . . . .

ELECTRICAL CHARACTERISTICS

230--1--60

. . . . . . . . . . . .

Select unit based on required cooling capacity

Enter Net Cooling Capacities table at condenser entering

temperature of 95

°

F. The 036 unit at 1200 cfm and 67

°

F ewb

(entering wet bulb) will provide a total capacity of 36,000 Btuh

and a SHC of 27,200 Btuh. Calculate SHC correction, if required,
using Note 4 under Cooling Capacities tables.

Select electric heat

The required heating capacity is 15,000 Btuh.
Determine additional electric heat capacity in kW.

15,000 Btuh

3414 Btuh/kW

= 4.4kW of heat required

Enter the Electric Heater table on page 5 for 208/230v,

single--phase unit. The 5--kW heater at 240v most closely satisfies
the heating required. To calculate kW at 230v, multiply the heater

kW by multiplication factor 0.92 found in the Multiplication
Factors table on page 14.
5 kW x 0.92 = 4.6 kW
4.6 kW x 3414 Btuh/kW = 15,704 Btuh
Total unit heating capacity is 35,904 Btuh
(20,200 + 15,704).

Select unit that corresponds to power source available

The Electrical Data table shows that the unit is designed to

operate at 208/230--1--60.

704C

Содержание 704C EVOLUTION

Страница 1: ...iency Each compressor is hermetically sealed against contamination to help promote longer life and dependable operation Vibration isolation provides quiet operation Compressors have internal high pres...

Страница 2: ...ch keeps the conditioned air from being affected by the outdoor ambient temperature and provides improved indoor air quality Conforms to American Society of Heating Refrigeration and Air Conditioning...

Страница 3: ...A SEER Sound Ratings dBA 024 2 800 24 000 11 13 0 72 030 2 1 2 1000 28 800 11 13 0 72 036 3 1200 36 000 11 13 0 74 042 3 1 2 1400 41 000 11 13 0 74 048 4 1600 45 000 11 13 0 78 060 5 1750 57 000 11 1...

Страница 4: ...fficiency 700 875 1050 1225 1400 1750 Max 800 1000 1200 1400 1600 2000 Size in 10x10 10x10 11x10 11x10 11x10 11x10 Motor HP RPM 1 2 1 2 3 4 3 4 3 4 1 HIGH PRESSURE SWITCH psig 650 15 420 25 Cutout Res...

Страница 5: ...m s variable speed indoor blower delivers Bryant s patented PerfectHumidity technology that allows for even greater humidity control Along with more precisely controlling temperature and humidity the...

Страница 6: ...FILTER RACK EVAPORATOR COIL TOP FILTER RACK BEND FLANGE AT 90 SCREW TO DIVIDER WITH 1 IN SCREW BOTTOM FILTER RACK MANUAL OUTSIDE AIR DAMPER DAMPER BLADE MANUAL OUTSIDE AIR HOOD REPLACEMENT PANEL 704C...

Страница 7: ...7 A06120 704C024 036 Unit Dimensions 704C...

Страница 8: ...8 A06121 704C042 060 Unit Dimensions 704C...

Страница 9: ...G E F G D E A05308 UNIT SIZE ODS CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM E IN MM F IN MM G IN MM 704C024 036 CPRFCURB006A00 8 203 11 279 16 1 2 419 28 3 4 730 30 3 8 771 44 5 16 1126 45 15 16 1...

Страница 10: ...ased on required cooling capacity Enter Net Cooling Capacities table at condenser entering temperature of 95 F The 036 unit at 1200 cfm and 67 F ewb entering wet bulb will provide a total capacity of...

Страница 11: ...21 1 17 8 18 0 19 4 21 4 SHC 17 8 17 0 14 5 11 7 18 5 18 1 15 5 12 3 kW 2 8 2 8 3 0 3 0 2 9 2 9 3 0 3 0 Cooling Extended Performance Table 704C030 Temp F Outdoor Air Entering Condenser Evaporator Air...

Страница 12: ...8 5 31 5 28 1 27 2 29 3 32 3 SHC 26 2 20 9 21 9 17 1 27 8 23 5 24 7 18 9 kW 4 2 4 3 4 3 4 3 4 4 4 4 4 4 4 4 Cooling Extended Performance Table 704C042 Temp F Outdoor Air Entering Condenser Evaporator...

Страница 13: ...5 3 38 8 34 6 33 3 35 9 39 5 SHC 32 4 27 0 28 4 21 9 34 1 28 9 30 6 23 3 kW 5 5 5 4 5 5 5 5 5 5 5 5 5 5 5 5 Cooling Extended Performance Table 704C060 Temp F Outdoor Air Entering Condenser Evaporator...

Страница 14: ...ES 1 Ratings are net they account for the effects of the evaporator fan motor power and heat 2 Direct interpolation is permissible Do not extrapolate 3 The following formulas may be used Sensible capa...

Страница 15: ...IR FLEXIBLE DUCT CEILING CONCENTRIC DIFFUSER BOX FIELD SUPPLIED SUPPLY AIR FLEXIBLE DUCT ROOF MOUNTING CURB C00023 USER INTERFACE DISCONNECT PER NEC FROM POWER SOURCE RETURN AIR TOP COVER FROM GAS LIN...

Страница 16: ...nflow openings Remove theinsertssimilar toremoving anelectrical knockout Leave onduct covers to seal the horizontal discharge openings in the unit Units installed in horizontal discharge orientation d...

Страница 17: ...6 60 6 60 70 11 3 15 0 54 2 62 5 76 2 86 6 80 90 15 0 20 0 72 2 83 3 98 8 112 7 100 125 208 230 3 60 187 253 15 4 88 0 0 8 6 8 26 9 26 9 35 35 3 8 5 0 10 4 12 0 26 9 26 9 30 35 7 5 10 0 20 8 24 1 34...

Страница 18: ...a phase imbalance in supply volt age is greater than 2 Use the following formula to determine the percentage of voltage imbalance Voltage imbalance max voltage deviation from average voltage 100 x av...

Страница 19: ...19 TYPICAL WIRING SCHEMATIC 230 1 60 7 0 A06126 704C...

Страница 20: ...20 TYPICAL WIRING SCHEMATIC 230 3 60 5 0 A06127 704C...

Страница 21: ...capacity as defined by unit size Actual airflow request will be adjusted from nominal using indoor and outdoor temperature and indoor humidity data to optimize the system operation for occupant comfo...

Страница 22: ...ation capableof beingwiped clean Aluminum foil faced fiberglass insulation shall be used in the entire indoor air cavity seciton 5 Unit shall have a field supplied condensate trap C Fans 1 The indoor...

Страница 23: ...tion whichshallallow unitto operatedown to0 F outdoorambi ent temperature in cooling 6 Filter Rack Kit Shall provide filter mounting for downflow and horizontal applications 7 Square To Round Duct Tra...

Страница 24: ...e or change at any time specifications or designs without notice and without incurring obligations E2006 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in U S A Edition...

Отзывы: