23
Table 10 -- Dry Coil Air Delivery* -- Horizontal and Downflow Discharge -- Unit 677C----A24--60 Cont
UNIT
HEATING
RISE
RANGE
MOTOR
SPEED
WIRE
COLOR
EXTERNAL STATIC PRESSURE (in. W.C.)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
677C--- ---A60115
30 - 60
o
F
(17 - 33
o
C)
Low
Blue
CFM
1448
1362
1296
1226
1168
1108
1071
998
905
Heating
Rise (
o
F)
60
NA
NA
NA
NA
NA
NA
NA
NA
Heating
Rise (
o
C)
33
NA
NA
NA
NA
NA
NA
NA
NA
Med-Low
Pink
CFM
1722
1675
1614
1543
1499
1442
1408
1356
1308
Heating
Rise (
o
F)
50
52
54
56
58
60
NA
NA
NA
Heating
Rise (
o
C)
28
29
30
31
32
33
NA
NA
NA
Medium
2
Red
CFM
1887
1847
1783
1726
1677
1625
1578
1527
1432
Heating
Rise (
o
F)
46
47
49
50
52
53
55
57
NA
Heating
Rise (
o
C)
26
26
27
28
29
30
31
32
NA
Med-High
1
Orange
CFM
2055
2008
1958
1927
1900
1768
1685
1581
1458
Heating
Rise (
o
F)
42
43
44
45
46
49
52
55
60
Heating
Rise (
o
C)
23
24
25
25
25
27
29
31
33
High
Black
CFM
2292
2238
2158
2049
1935
1840
1732
1635
1513
Heating
Rise (
o
F)
38
39
40
42
45
47
50
53
57
Heating
Rise (
o
C)
21
22
22
24
25
26
28
30
32
677C--- ---A60130
35 - 65
o
F
(19 - 36
o
C)
Low
Blue
CFM
1448
1321
1282
1235
1192
1145
1101
1057
1011
Heating
Rise (
o
F)
NA
NA
NA
NA
NA
NA
NA
NA
NA
Heating
Rise (
o
C)
NA
NA
NA
NA
NA
NA
NA
NA
NA
Med-Low
Pink
CFM
1722
1675
1614
1543
1499
1442
1408
1356
1308
Heating
Rise (
o
F)
56
57
60
62
64
NA
NA
NA
NA
Heating
Rise (
o
C)
31
32
33
35
36
NA
NA
NA
NA
Medium
2
Red
CFM
1887
1847
1783
1726
1677
1625
1578
1527
1432
Heating
Rise (
o
F)
51
52
54
56
57
59
61
63
NA
Heating
Rise (
o
C)
28
29
30
31
32
33
34
35
NA
Med-High
1
Orange
CFM
2055
2008
1958
1927
1900
1768
1685
1581
1458
Heating
Rise (
o
F)
47
48
49
50
51
54
57
61
NA
Heating
Rise (
o
C)
26
27
27
28
28
30
32
34
NA
High
Black
CFM
2292
2238
2158
2049
1935
1840
1732
1635
1513
Heating
Rise (
o
F)
42
43
45
47
50
52
56
59
64
Heating
Rise (
o
C)
23
24
25
26
28
29
31
33
35
* Air delivery values are without air filter and are for dry coil (See 677C--- ---A Wet Coil Pressure Drop table).
1
Factory---shipped gas heating speed
2
Factory---shipped heat pump speed
NA --- Not allowed for heating speed
Note: Deduct field---supplied air filter pressure drop and wet coil pressure drop to obtain external static pressure available for ducting.
Shaded areas indicate speed/static combinations that are not permitted for dehumidification speed.
677C
--
--
A
Содержание 677C--A
Страница 3: ...3 A09146 Fig 2 677C A24 30 Unit Dimensions 677C A ...
Страница 4: ...4 A09147 Fig 3 677C A36 60 Unit Dimensions 677C A ...
Страница 24: ...24 A09068 Fig 15 208 230 1 60 Wiring Diagram Unit 677C A 677C A ...
Страница 25: ...25 A09209 Fig 16 208 230 3 60 Wiring Diagram Unit 677C A 677C A ...
Страница 26: ...26 50VT500173 REV 4 0 A09099 Fig 17 Cooling Charging Table Subcooling 677C A ...