5
C
B
A
F
D
E
LARGE CURB
C
B
A
F
D
E
SMALL CURB
ROOF CURB DETAIL
Wood nailer*
Roofcurb*
Insulation
(field supplied)
*Provided with roofcurb
Cant strip
field supplied
Roofing material
field supplied
Flashing field
supplied
HVAC unit
base rails
Roofcurb
Sealing
Gasket
HVAC unit
basepan
Anchor screw
A09090
A09095
A09110
A09111
UNIT SIZE
CATALOG
NUMBER
A
IN. (mm)
B
IN. (mm)*
C
IN. (mm)
D
IN. (mm)
E
IN. (mm)
F
IN. (mm)
Small
CPRFCURB010A00
11 (279)
10 (254)
16 (406)
47.8 (1214)
32.4 (822)
2.7 (69)
CPRFCURB011A00
14 (356)
Large
CPRFCURB012A00
11 (279)
14 (356)
43.9 (1116)
CPRFCURB013A00
14 (356)
NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Roof curb is made of 16--gauge steel.
4. Attach ductwork to curb (flanges of duct rest on curb).
5. Insulated panels: 1--in. (25.4 mm) thick fiberglass 1 lb. density.
IMPORTANT
: Do not install large base pan HYBRID HEAT
units onto the small base pan (common curb). The center of gravity
on a large base pan HYBRID HEAT unit could overhang the curb
causing an unsafe condition. Before installing any large base pan
unit onto the common curb, check the “Y” distance in the product
literature dimensional drawing to ensure that “Y” is greater than 14
in. (356 mm). Do not install any large base pan unit onto the
common curb with a “Y” dimension (center of gravity) less than 14
in. (356 mm).
Fig. 4 -- Roof Curb Dimensions
677C
--
--
A
Содержание 677C--A
Страница 3: ...3 A09146 Fig 2 677C A24 30 Unit Dimensions 677C A ...
Страница 4: ...4 A09147 Fig 3 677C A36 60 Unit Dimensions 677C A ...
Страница 24: ...24 A09068 Fig 15 208 230 1 60 Wiring Diagram Unit 677C A 677C A ...
Страница 25: ...25 A09209 Fig 16 208 230 3 60 Wiring Diagram Unit 677C A 677C A ...
Страница 26: ...26 50VT500173 REV 4 0 A09099 Fig 17 Cooling Charging Table Subcooling 677C A ...