providing electrical potential to second heater sequencer (if used).
If outdoor temperature falls below setting of outdoor thermostat
(field-installed option), contacts close to complete circuit and bring
on second bank of supplemental electric heat.

When thermostat is satisfied, its contacts open, de-energizing
contactor and sequencer. All heaters and motors should stop.

DEFROST

The defrost control is a time/temperature control which includes a
field-selectable (quick-connects located at board edge) time period
between defrost cycles (30, 50, or 90 minutes), factory set at 90
minutes.

The electronic timer and defrost cycle start only when contactor is
energized and defrost thermostat is closed.

Defrost mode is identical to cooling mode except that outdoor fan
motor stops and second-stage heat is turned on to continue
warming conditioned space.

To initiate defrost, the defrost thermostat must be closed. This can
be accomplished as follows:

1. Turn off power to outdoor unit.

2. Disconnect outdoor fan motor lead from OF2 on control

board. (See Fig. 15.) Tape lead to prevent grounding.

3. Restart unit in heating mode, allowing frost to accumulate

on outdoor coil.

4. After a few minutes in heating mode, liquid line tempera-

ture should drop below closing point of defrost thermostat
(approximately 30˚F).

5. Short between speed-up terminals with a flat-bladed screw-

driver. (See Fig. 15.) This reduces the timing sequence to
1/256th of original time. (See Table 3.)

6. When you hear reversing valve change position, remove

screwdriver immediately; otherwise, control will terminate
normal 10-minute defrost cycle in approximately 2 sec.

NOTE:

Length of defrost cycle is dependent on the length of time

it takes to remove screwdriver from test pins after reversing valve
has shifted.

7. Unit will remain in defrost for remainder of defrost cycle

time or until defrost thermostat reopens at approximately
80˚F coil temperature of liquid line.

8. Turn off power to outdoor unit and reconnect fan motor lead

to OF2 on control board. (See Fig. 15.)

A97413

LEGEND

24 VOLT FACTORY WIRING

24 VOLT FIELD WIRING

FIELD SPLICE CONNECTION

OUTDOOR THERMOSTAT

EMERGENCY HEAT RELAY

SUPPLEMENTAL HEAT RELAY

  

SHR

  

EHR

  

ODT

WIRING DIAGRAM NOTES:

1. BRYANT THERMOSTAT WIRING DIAGRAMS ARE ONLY ACCURATE FOR MODEL NUMBERS BEGINNING

WITH TSTAT _ _ _ _ _ _ _.

2. WIRING MUST CONFORM TO NEC OR LOCAL CODES.

3. SOME UNITS ARE EQUIPPED WITH PRESSURE SWITCH(ES), TEMPERATURE SWITCH, OR 5-MINUTE COM-

PRESSOR CYCLE PROTECTION. CONNECT 24-V FIELD WIRING TO FACTORY-PROVIDED STRIPPED LEADS.

4. A LIQUID-LINE SOLENOID VALVE IS REQUIRED ON SOME UNITS.

5. THERMOSTATS ARE FACTORY CONFIGURED WITH 5-MINUTE COMPRESSOR CYCLE PROTECTION AND 4

CYCLES PER HR LIMIT. SEE THERMOSTAT INSTALLATION INSTRUCTIONS FOR DETAILS.

6. TO STAGE ELECTRIC RESISTANCE HEAT, CONSULT OUTDOOR THERMOSTAT INSTALLATION INSTRUC-

TIONS.

7. FOR DUAL FUEL THERMOSTATS, UNDERLINED LETTER ON DUAL TERMINAL INDICATES ITS USAGE.

FOR EXAMPLE: O/W2 MEANS O

O/W2 MEANS W2

OUTDOOR TEMPERATURE SENSOR MUST BE ATTACHED IN ALL DUAL FUEL INSTALLATIONS.

JUMPER WIRE BETWEEN O/W2 AND L THERMOSTAT TERMINALS MUST BE PRESENT.

8. Y1 AND O CONNECTIONS TO 2-STAGE FURNACES MAY NOT EXIST OR MAY ONLY BE A WIRE RATHER

THAN A SCREW TERMINAL.

—11—

Содержание 663C

Страница 1: ...r installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sounds may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate to capacity...

Страница 2: ...ing mode is 66 F V ELEVATE UNIT CAUTION Accumulation of water and ice in base pan may cause equipment damage In areas where prolonged freezing temperatures are encountered elevate unit per local clima...

Страница 3: ...1 for field tubing equivalent line length Refer to Table 2 for accessory requirements For buried line applications greater than 36 in refer to Table 2 and Residential Split System Buried Line Applicat...

Страница 4: ...AND RECOMMENDED LIQUID AND VAPOR TUBE DIAMETERS IN UNIT SIZE LIQUID VAPOR VAPOR LONG LINE Connection Diameter Tube Diameter Connection Diameter Tube Diameter Connection Diameter Tube Diameter 018 3 8...

Страница 5: ...afety glasses protective clothing and gloves when handling refrigerant and observe the following Back seating service valves are not equipped with Schrader valves Fully back seat counter clockwise val...

Страница 6: ...P FA FB FC FD FF FH FAN COIL HEAT PUMP G Y1 W2 L R O INDOOR FAN HEAT STAGE 2 COOL HEAT STAGE 1 NOT USED 24 VAC COM NOT USED TROUBLE OPTIONAL OUTDOOR SENSOR CONNECTION Y C C IF AVAILABLE A97372 24 VAC...

Страница 7: ...R C W2 Y G R C RVS COOLING C W2 OTHER HP THERMOSTAT FA FB FC FD FF FH FAN COIL HEAT PUMP G O E W2 E W3 R Y 24 VAC COM HEAT STAGE 2 COOL HEAT STAGE 1 INDOOR FAN EMERGENCY HEAT O IF AVAILABLE A97373 24...

Страница 8: ...xiliary heat for even heating comfort via W W1 and Y1 W2 Refer to FK4 Installation Instructions Fig 11 Typical 24 v Circuit Connections using Bryant Model DF Thermostat with Single or 2 Stage Furnace...

Страница 9: ...ONNECTION CUT JW1 SHR SHR ODT A97407 24 VAC HOT R G W W1 Y Y2 O W2 RVS COOLING C B S1 S2 BRYANT PROGRAMMABLE THERMOSTAT MODEL HP FA FB FC FH FAN COIL WITH SMART HEAT HEAT PUMP Y1 W2 L R C Y G O W2T W3...

Страница 10: ...VAC COM HEAT STAGE 2 CUT JW1 SHR SHR FA FB FC FH FAN COIL SMART HEAT ODT A97410 24 VAC HOT R C Y G O RVS COOLING W2 OTHER HP THERMOSTAT FA FB FC FH FAN COIL SMART HEAT HEAT PUMP E R C Y G O W2T W3 W2D...

Страница 11: ...rewdriver immediately otherwise control will terminate normal 10 minute defrost cycle in approximately 2 sec NOTE Length of defrost cycle is dependent on the length of time it takes to remove screwdri...

Страница 12: ...rging is necessary during heating season charge must be weighed in accordance with unit rating plate 0 6 oz ft of 3 8 in liquid line above or below 15 ft respectively EXAMPLE To calculate additional c...

Отзывы: