Table 1 – Physical Data
UNIT SIZE
24
30
36
42
48
60
NOMINAL CAPACITY (ton)
2
2---1/2
3
3---1/2
4
5
SHIPPING WEIGHT lb.
SHIPPING WEIGHT (kg)
347
157
393
178
420
191
466
212
462
210
511
232
COMPRESSORS
Quantity
Scroll
1
REFRIGERANT (R---410A)
Quantity lb
Quantity (kg)
8.2
3.7
11.2
5.1
11.0
5.0
14.6
6.6
12.0
5.4
14.8
6.7
REFRIGERANT METERING DEVICE
TXV, Indoor TXV
ORIFICE
OD (in.)
OD (mm)
.032 (2)
0.81 (2)
.035 (1)
.038 (1)
.89 (1)
.97 (1)
.042 (2)
1.07 (2)
.042 (2)
1.07 (2)
.042 (2)
1.07 (2)
.052 (2)
1.32 (2)
OUTDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
1...21
18.8
2...21
18.8
2...21
13.6
2...21
19.4
2...21
17.5
2...21
23.3
OUTDOOR FAN
Nominal Cfm
Diameter in.
Diameter (mm)
Motor Hp (Rpm)
2100
24
609.6
1/12 (800)
2500
24
609.6
1/8 (810)
3000
26
660.4
1/5 (810)
3000
26
660.4
1/5 (810)
3300
26
660.4
1/5 (810)
3600
26
660.4
1/5 (810)
INDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
3...17
3.7
3...17
3.7
3...17
4.7
3...17
4.7
3...17
5.7
4...17
5.7
INDOOR BLOWER
Nominal Low Stage Cooling Airflow (Cfm)
Nominal High Stage Cooling Airflow (Cfm)
Size in.
Size (mm.)
Motor HP (RPM)
675
775
900
1050
1200
1400
675
855
10x10
254x254
1/2 (1050)
775
1000
10x10
254x254
1/2 (1050)
900
1200
11x10
279.4x254
3/4 (1000)
1050
1400
11x10
279.4x254
3/4 (1075)
1200
1600
11x10
279.4x254
1.0 (1075)
1400
1750
11x10
279.4x254
1.0 (1075)
HIGH---PRESSURE SWITCH
(psig) Cut---out Reset (Auto)
650 +/--- 15
420 +/--- 25
LOW---PRESSURE SWITCH
(psig) cut---out Reset (auto)
20 +/--- 5
45 +/--- 5
RETURN---AIR FILTERS
†
}
Throwaway Size in.
Throwaway Size (mm)
20x20x1
508x508x25
20x24x1
508x610x25
24x30x1
610x762x25
24x36x1
610x914x25
{
Required filter sizes shown are based on the larger of the AHRI (Air Conditioning Heating and Refrigeration Institute) rated cooling airflow or the heating air-
flow velocity of 300 ft/minute for throwaway type or 450 ft/minute for high---capacity type. Air filter pressure drop for non---standard filters must not exceed 0.08
in. W.C.
}
If using accessory filter rack refer to the filter rack installation instructions for correct filter sizes and quantity.
Table 2 – Minimum Airflow for Safe Electric Heater Operation (CFM)
SIZE
24
30
36
42
48
60
Cfm
850
1000
1200
1400
1600
1750
607E
Содержание 607E Series
Страница 3: ...3 A180109 Fig 2 607E C24 30 Unit Dimensions 607E...
Страница 4: ...4 A13175 Fig 3 607E A36 60 Unit Dimensions 607E...
Страница 23: ...23 A13144 Fig 15 Connection Wiring Diagram without Advanced Dehumidification AD FIOP 208 230 1 60 607E...
Страница 24: ...24 A13145 Fig 15 Cont Ladder Wiring Diagram without Advanced Dehumidification AD FIOP 208 230 1 60 607E...
Страница 27: ...27 A13146 Fig 17 Connection Wiring Diagram 208 230 3 60 607E...
Страница 28: ...28 A13147 Fig 17 Cont Ladder Wiring Diagram 208 230 3 60 607E...
Страница 29: ...29 A13148 Fig 18 Connection Wiring Diagram 460 3 60 607E...
Страница 30: ...30 A13149 Fig 18 Cont Ladder Wiring Diagram 460 3 60 607E...
Страница 31: ...31 A170012 Fig 19 Cooling Charging Chart 607E...