35
This oil is extremely hygroscopic, meaning it absorbs water
readily. POE oils can absorb 15 times as much water as other oils
designed for HCFC and CFC refrigerants. Take all necessary
precautions to avoid exposure of the oil to the atmosphere.
Servicing Systems on Roofs with Synthetic Materials
POE (polyolester) compressor lubricants are known to cause long
term damage to some synthetic roofing materials. Exposure, even if
immediately cleaned up, may cause embrittlement (leading to
cracking) to occur in one year or more. When performing any
service that may risk exposure of compressor oil to the roof, take
appropriate precautions to protect roofing. Procedures which risk
oil leakage include, but are not limited to, compressor replacement,
repairing refrigerant leaks, replacing refrigerant components such
as filter drier, pressure switch, metering device, coil, accumulator,
or reversing valve.
Synthetic Roof Precautionary Procedure
1. Cover extended roof working area with an impermeable
polyethylene (plastic) drip cloth or tarp. Cover an
approximate 10 x 10 ft (3 x 3 m) area.
2. Cover area in front of the unit service panel with a terry
cloth shop towel to absorb lubricant spills, prevent run--offs,
and protect drop cloth from tears caused by tools or
components.
3. Place terry cloth shop towel inside unit immediately under
component(s) to be serviced and prevent lubricant run--offs
through the louvered openings in the unit base.
4. Perform required service.
5. Remove and dispose of any oil contaminated material per
local codes.
Liquid Line Filter Drier
The filter drier is specifically designed to operate with Puron. Use
only factory--authorized components. Filter drier must be replaced
whenever the refrigerant system is opened. When removing a filter
drier, use a tubing cutter to cut the drier from the system. Do not
unsweat a filter drier from the system. Heat from unsweating will
release moisture and contaminants from drier into system.
Puron (R--410A) Refrigerant Charging
Refer to unit information plate and charging chart. Some R--410A
refrigerant cylinders contain a dip tube to allow liquid refrigerant to
flow from cylinder in upright position. For cylinders equipped
with a dip tube, charge Puron units with cylinder in upright
position and a commercial metering device in manifold hose.
Charge refrigerant into suction--line.
Step 5 — System Information
Loss of Charge Switch
The loss of charge switch is a protective device wired into control
circuit (low voltage). It shuts off the compressor if abnormally low
pressures are present in the refrigeration circuit.
NOTE
:
Because these switches are attached to refrigeration
system under pressure, it is not advisable to remove this device for
troubleshooting unless you are reasonably certain that a problem
exists. If switch must be removed, remove and recover all system
charge so that pressure gauges read 0 psig. Never open system
without breaking vacuum with dry nitrogen.
Check Defrost Thermostat
The defrost thermostat is usually located on the lowest liquid
leaving circuit of the left condenser coil (see Fig. 22). The
thermostat closes at 32
_
F (0
_
C) and opens at 65
_
F (18
_
C).
The defrost thermostat signals heat pump that conditions are right
for defrost or that conditions have changed to terminate defrost. It
is a thermally actuated switch clamped to outdoor coil to sense its
temperature. Normal temperature range is closed at 32
_
3
_
F (0
1.7
_
C) and open at 65
_
5
_
F (18
2.8
_
C).
NOTE
: The defrost thermostat must be located on the liquid side
of the outdoor coil on the bottom circuit and as close to the coil as
possible.
FEEDER TUBE
STUB TUBE
DEFROST
THERMOSTAT
C99029
Fig. 22 -- Defrost Thermostat
TROUBLESHOOTING
Refer to the Troubleshooting Chart (Table 12) for troubleshooting
information.
START--UP CHECKLIST
Use the Start--Up Checklist at the back of this manual.
607E
Содержание 607E Series
Страница 3: ...3 A180109 Fig 2 607E C24 30 Unit Dimensions 607E...
Страница 4: ...4 A13175 Fig 3 607E A36 60 Unit Dimensions 607E...
Страница 23: ...23 A13144 Fig 15 Connection Wiring Diagram without Advanced Dehumidification AD FIOP 208 230 1 60 607E...
Страница 24: ...24 A13145 Fig 15 Cont Ladder Wiring Diagram without Advanced Dehumidification AD FIOP 208 230 1 60 607E...
Страница 27: ...27 A13146 Fig 17 Connection Wiring Diagram 208 230 3 60 607E...
Страница 28: ...28 A13147 Fig 17 Cont Ladder Wiring Diagram 208 230 3 60 607E...
Страница 29: ...29 A13148 Fig 18 Connection Wiring Diagram 460 3 60 607E...
Страница 30: ...30 A13149 Fig 18 Cont Ladder Wiring Diagram 460 3 60 607E...
Страница 31: ...31 A170012 Fig 19 Cooling Charging Chart 607E...