82
NOTE: Do not adj
u
st p
u
lley f
u
rther than 5 t
u
rns open.
GENERAL FAN PERFORMANCE NOTES
1. Interpolation is permissible. Do not extrapolate.
2. External static pressure is the static pressure difference between the return duct and the supply duct plus the static pressure
caused by any FIOPs or accessories.
3. Tabular data accounts for pressure loss due to clean filters, unit casing, wet coils, and highest gas heat exchanger (when gas heat
unit).
4. Factory options and accessories may effect static pressure losses. Gas heat unit fan tables assume highest gas heat models; for
fan selections with low or medium heat models, the user must deduct low and medium heat static pressures. Selection software
is available, through your salesperson, to help you select the best motor/drive combination for your application.
5. The fan performance tables offer motor/drive recommendations. In cases when two motor/drive combinations would work,
Bryant recommends the lower horsepower option.
6. For information on the electrical properties of Bryant motors, please see the Electrical information section of this book.
7. For more information on the performance limits of Bryant motors, see the application data section of this book.
8. The EPACT (Energy Policy Act of 1992) regulates energy requirements for specific types of indoor fan motors. Motors regu-
lated by EPACT include any general purpose, T-frame (three-digit, 143 and larger), single-speed, foot mounted, polyphase,
squirrel cage induction motors of NEMA (National Electrical Manufacturers Association) design A and B, manufactured for use
in the United States. Ranging from 1 to 200 Hp, these continuous-duty motors operate on 230 and 460 volt, 60 Hz power. If a
motor does not fit into these specifications, the motor does not have to be replaced by an EPACT compliant energy-efficient
motor. Variable-speed motors are exempt from EPACT compliance requirements.
Table L — Pulley Adjustment (Horizontal) - Fan RPM at Motor Pulley Settings
MODEL SIZE
MOTOR/DRIVE
COMBO
MOTOR PULLEY TURNS OPEN
0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
17
3-phase
Standard Static
680
663
647
630
614
597
580
564
547
531
514
Medium Static
780
763
747
730
714
697
680
664
647
631
614
High Static
912
895
879
862
846
829
812
796
779
763
746
20
3-phase
Standard Static
822
802
782
762
742
722
702
682
662
642
622
Medium Static
879
862
846
829
813
796
779
763
746
730
713
High Static
1021
1002
984
965
947
928
909
891
872
854
835
24
3-phase
Standard Static
863
846
828
811
794
777
759
742
725
707
690
Medium Static
1021
1002
984
965
947
928
909
891
872
854
835
High Static
1176
1153
1129
1106
1082
1059
1035
1012
988
965
941
28
3-phase
Standard Static
791
777
762
748
733
719
705
690
676
661
647
Medium Static
923
906
889
873
856
839
822
805
789
772
755
High Static
1107
1087
1067
1047
1027
1007
986
966
946
926
906
Factory settings
APPENDIX C — FAN PERFORMANCE
Содержание 581J 17-28 Series
Страница 18: ...18 COOLING CHARGING CHARTS Fig 21 Cooling Charging Chart 15 Ton ...
Страница 19: ...19 Fig 22 Cooling Charging Chart 17 5 Ton ...
Страница 20: ...20 Fig 23 Cooling Charging Chart 20 Ton ...
Страница 21: ...21 Fig 24 Cooling Charging Chart 25 Ton ...
Страница 36: ...36 Fig 47 Unit Control Box IGC Location IGC Board IGC Board Side view Front view ...
Страница 39: ...39 Fig 50 Integrated Gas Control IGC Board RED LED STATUS ...
Страница 45: ...45 Fig 56 RTU Open Overlay for Economizer Wiring ...
Страница 46: ...46 Fig 57 VFD Overlay for W2770 Controller Wiring ...
Страница 84: ...84 Fig B 581J 17 28 Control Diagram 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 85: ...85 Fig C 581J 17 28 Power Diagram 208 230 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 86: ...86 Fig D 581J 17 28 Power Diagram 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 87: ...87 Fig E 581J 17 28 Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 88: ...88 Fig F 581J 17 28 Control Diagram with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...
Страница 89: ...89 Fig G 581J 17 28 Power Diagram 208 230 3 60 with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...
Страница 90: ...90 Fig H 581J 17 28 Power Diagram 460 3 60 with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...
Страница 91: ...91 Fig I 581J 17 28 Power Diagram 575 3 60 with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...
Страница 92: ...92 Fig J RTU OPEN Wiring Diagram APPENDIX D WIRING DIAGRAMS ...
Страница 93: ...93 Fig K RTU OPEN Wiring Diagram with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...