64
*With 2SP FAN DELAY (Advanced Set
u
p Men
u
) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for sec-
ond stage cooling by t
u
rning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
†With stage 3 delay (STG3 DLY) in Advanced set
u
p men
u
can t
u
rn on second stage of mechanical cooling Y2–O after the delay if the call for Y1–I and
Y2–I have not been satisfied.
*With 2SP FAN DELAY (Advanced Set
u
p Men
u
) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second
stage cooling by t
u
rning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
†With stage 3 delay (STG3 DLY) in Advanced set
u
p men
u
can t
u
rn on second stage of mechanical cooling Y2–O after the delay if the call for Y1–I and
Y2–I have not been satisfied.
Table 34 — Dry Bulb Operation with DCV (CO
2
Sensor) — 2 Speed Fan
DEMAND
CONTROLLED
VENTILATION (DCV)
OUTSIDE AIR
GOOD TO
ECONOMIZE
Y1-I
Y2-I
FAN
SPEED
Y1-O
Y2-O
OCCUPIED
UNOCCUPIED
Below CO
2
Set
No
OFF
OFF
LOW
0v/Off
0v/Off
VENTMIN
Closed
ON
OFF
LOW
24v/On
0v/Off
VENTMIN
Closed
ON
ON
HIGH
24v/On
24v/On
VENTMIN
Closed
Yes
OFF
OFF
LOW
0v/Off
0v/Off
VENTMIN
Closed
ON
OFF
LOW
0v/Off
0v/Off
VENTMIN to
F
u
ll-Open
Closed to F
u
ll-Open
ON
ON
HIGH
24v/On
0v/Off
VENTMIN to
F
u
ll-Open
Closed to F
u
ll-Open
Above CO
2
Set
No
OFF
OFF
LOW
0v/Off
0v/Off
VENTMIN to
VENTMAX
Closed
ON
OFF
LOW
24v/On
0v/Off
VENTMIN to
VENTMAX
Closed
ON
ON
HIGH
24v/On
24v/On
VENTMIN to
VENTMAX
Closed
Yes
OFF
OFF
LOW
0v/Off
0v/Off
VENTMIN to
VENTMAX
Closed
ON
OFF
LOW
0v/Off
0v/Off
VENTMIN to
F
u
ll-Open
Closed to F
u
ll-Open
ON
ON
HIGH
DELAY*
24v/On
0v/Off†
VENTMIN to
F
u
ll-Open
Closed to F
u
ll-Open
Table 35 — Enthalpy Operation without DCV (CO
2
Sensor) — 2 Speed Fan
DEMAND
CONTROLLED
VENTILATION (DCV)
OUTSIDE AIR
GOOD TO
ECONOMIZE
Y1-I
Y2-I
FAN
SPEED
Y1-O
Y2-O
OCCUPIED
UNOCCUPIED
NO CO
2
SENSOR
NO
OFF
OFF
LOW
0v/Off
0v/Off
MIN POS
Closed
ON
OFF
LOW
24v/On
0v/Off
MIN POS
Closed
ON
ON
HIGH
24v/On
24v/On
MIN POS
Closed
YES
OFF
OFF
LOW
0v/Off
0v/Off
MIN POS
Closed
ON
OFF
LOW
0v/Off
0v/Off
MIN POS to F
u
ll Open
Closed to F
u
ll-Open
ON
ON
HIGH
DELAY*
24v/On
0v/Off†
MIN POS to F
u
ll Open
Closed to F
u
ll-Open
Содержание 581J 17-28 Series
Страница 18: ...18 COOLING CHARGING CHARTS Fig 21 Cooling Charging Chart 15 Ton ...
Страница 19: ...19 Fig 22 Cooling Charging Chart 17 5 Ton ...
Страница 20: ...20 Fig 23 Cooling Charging Chart 20 Ton ...
Страница 21: ...21 Fig 24 Cooling Charging Chart 25 Ton ...
Страница 36: ...36 Fig 47 Unit Control Box IGC Location IGC Board IGC Board Side view Front view ...
Страница 39: ...39 Fig 50 Integrated Gas Control IGC Board RED LED STATUS ...
Страница 45: ...45 Fig 56 RTU Open Overlay for Economizer Wiring ...
Страница 46: ...46 Fig 57 VFD Overlay for W2770 Controller Wiring ...
Страница 84: ...84 Fig B 581J 17 28 Control Diagram 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 85: ...85 Fig C 581J 17 28 Power Diagram 208 230 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 86: ...86 Fig D 581J 17 28 Power Diagram 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 87: ...87 Fig E 581J 17 28 Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 88: ...88 Fig F 581J 17 28 Control Diagram with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...
Страница 89: ...89 Fig G 581J 17 28 Power Diagram 208 230 3 60 with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...
Страница 90: ...90 Fig H 581J 17 28 Power Diagram 460 3 60 with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...
Страница 91: ...91 Fig I 581J 17 28 Power Diagram 575 3 60 with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...
Страница 92: ...92 Fig J RTU OPEN Wiring Diagram APPENDIX D WIRING DIAGRAMS ...
Страница 93: ...93 Fig K RTU OPEN Wiring Diagram with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...