58
STATUS
(cont)
RA TEMP
_ _ . _ °F
(or _ _ . _ °C)
0°F to 140°F
(–18°C to 60°C)
RETURN AIR TEMPERATURE
Displays measured value of return air temperature from RAT
Sylk Bus sensor.
Displays _ _ . _ F if sensor sends invalid value, if not connected,
short or out of range
RA HUM
_ _ %
0 to 100%
RETURN AIR RELATIVE HUMIDITY
Displays measured value of return air humidity from RA Sylk Bus
sensor.
Displays _ _% if sensor sends invalid value, if not connected,
short or out of range
IN CO2
_ _ _ ppm
0 to 2000 ppm
SPACE/RETURN AIR CO
2
Displays value of measured CO
2
from CO
2
sensor. Invalid if not
connected, short or out of range. May be adjusted in Advanced
menu by Zero offset and Span.
DCV STATUS
N/A
ON/OFF
DEMAND CONTROLLED VENTILATION STATUS
Displays ON if above set point and OFF if below set point, and
ONLY if a CO
2
sensor is connected.
DAMPER OUT
2.0v
2.0 to 10.0v
Displays voltage output to the damper actuator.***
ACT POS
N/A
0 to 100%
Displays actual position of actuator
ACT COUNT
N/A
1 to 65,535
Displays number of times actuator has cycled.
1 cycle equals 180 degrees of actuator movement in any
direction.
ACTUATOR
N/A
OK/Alarm (on
Alarm menu)
Displays ERROR if voltage or torque is below actuator range.
EXH1 OUT
OFF
ON/OFF
EXHAUST STAGE 1 RELAY OUTPUT
Displays ON when damper position reaches programmed
percentage set point.
Output of EXH1 terminal:
ON = relay closed
OFF = relay open
EXH2 OUT
OFF
ON/OFF
EXHAUST STAGE 2 RELAY OUTPUT
Output of AUX1 O terminal
Displays ON when damper position reaches programmed
percentage set point.
ON = 24 vac output
OFF = No output
Displays only if AUX1 O = EXH2
ERV
OFF
ON/OFF
ENERGY RECOVERY VENTILATOR
Output of AUX1 O terminal; displays only if AUX1 O = ERV
ON = 24 vac output
OFF = No Output
MECH COOL ON
or
HEAT STAGES ON
0
0, 1, or 2
Displays stage of mechanical cooling that is active.
Displays the stage of heat pump heating that is active.
FAN SPEED
N/A
LOW or HIGH
SUPPLY FAN SPEED
Displays speed setting of fan on a 2-speed fan unit.
W (HEAT IN)
N/A
ON/OFF
HEAT DEMAND STATUS
Displays status of heat demand on a 2-speed fan unit.
SETPOINTS
MAT SET
53°F (12°C)
38°F to 70°F
(3°C to 21°C);
increment by 1°F
SUPPLY AIR SETPOINT
The economizer will modulate the OA damper to maintain the
mixed air temperature at the set point
LOW T LOCK
32°F (0°C)
–45°F to 80°F
(–43°C to 27°C);
increment by 1°F
COMPRESSOR LOW TEMPERATURE LOCKOUT
Set point determines outdoor temperature when the mechanical
cooling cannot be turned on. Commonly referred to as the
Compressor lockout. At or below the set point, the Y1-O and Y2-
O will not be energized on the controller.
DRYBLB SET
63°F (17°C)
48°F to 80°F
(9°C to 27°C);
increment by 1°F
OA DRY BULB TEMPERATURE CHANGEOVER SETPOINT
Dry bulb set point will only appear if using dry bulb changeover.
Set point determines where the economizer will assume outdoor
air temperature is good for free cooling; e.g.; at 63°F unit will
economize at 62°F and below and not economize at 64°F and
above. There is a 2°F deadband.
ENTH CURVE
ES3
ES1,ES2,ES3,ES4,
or ES5
ENTHALPY CHANGEOVER CURVE
ES curve will only appear if using enthalpy changeover.
Enthalpy boundary “curves” for economizing using single
enthalpy. See page 65 for description of enthalpy curves.
DCV SET
1100ppm
500 to 2000 ppm;
increment by 100
DEMAND CONTROLLED VENTILATION
Displays only if CO
2
sensor is connected. Set point for Demand
Controlled Ventilation of space. Above the set point, the OA
dampers will modulate open to bring in additional OA to maintain
a space ppm level below the set point.
MIN POS
2.8 V
2 to 10 vdc
VENTILATION MINIMUM POSITION
Displays ONLY if a CO
2
sensor is NOT connected.
With 2-speed fan units, MIN POS L (low speed fan) and MIN
POS H (high speed fan) settings are required. Default for MIN
POS L is 3.2V and MIN POS H is 2.8V.
Table 27 — W7220 Menu Structure* (cont)
MENU
PARAMETER
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND
INCREMENT
†
EXPANDED PARAMETER NAME
Notes
Содержание 581J 17-28 Series
Страница 18: ...18 COOLING CHARGING CHARTS Fig 21 Cooling Charging Chart 15 Ton ...
Страница 19: ...19 Fig 22 Cooling Charging Chart 17 5 Ton ...
Страница 20: ...20 Fig 23 Cooling Charging Chart 20 Ton ...
Страница 21: ...21 Fig 24 Cooling Charging Chart 25 Ton ...
Страница 36: ...36 Fig 47 Unit Control Box IGC Location IGC Board IGC Board Side view Front view ...
Страница 39: ...39 Fig 50 Integrated Gas Control IGC Board RED LED STATUS ...
Страница 45: ...45 Fig 56 RTU Open Overlay for Economizer Wiring ...
Страница 46: ...46 Fig 57 VFD Overlay for W2770 Controller Wiring ...
Страница 84: ...84 Fig B 581J 17 28 Control Diagram 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 85: ...85 Fig C 581J 17 28 Power Diagram 208 230 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 86: ...86 Fig D 581J 17 28 Power Diagram 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 87: ...87 Fig E 581J 17 28 Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 88: ...88 Fig F 581J 17 28 Control Diagram with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...
Страница 89: ...89 Fig G 581J 17 28 Power Diagram 208 230 3 60 with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...
Страница 90: ...90 Fig H 581J 17 28 Power Diagram 460 3 60 with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...
Страница 91: ...91 Fig I 581J 17 28 Power Diagram 575 3 60 with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...
Страница 92: ...92 Fig J RTU OPEN Wiring Diagram APPENDIX D WIRING DIAGRAMS ...
Страница 93: ...93 Fig K RTU OPEN Wiring Diagram with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...