36
PURON
R
(R--410A) QUICK REFERENCE GUIDE
S
Puron refrigerant operates at 50--70 percent higher pressures than R--22. Be sure that servicing equipment and replacement
components are designed to operate with Puron
S
Puron refrigerant cylinders are rose colored.
S
Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
S
Puron systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when
charging into suction line with compressor operating
S
Manifold sets should be minimum 700 psig high side and 180 psig low side with 550 psig low--side retard.
S
Use hoses with minimum 700 psig service pressure rating.
S
Leak detectors should be designed to detect HFC refrigerant.
S
Puron, as with other HFCs, is only compatible with POE oils.
S
Vacuum pumps will not remove moisture from oil.
S
Do not use liquid--line filter driers with rated working pressures less than 600 psig.
S
Do not leave Puron suction line filter driers in line longer than 72 hrs.
S
Do not install a suction--line filter drier in liquid line.
S
POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
S
POE oils may cause damage to certain plastics and roofing materials.
S
Wrap all filter driers and service valves with wet cloth when brazing.
S
A factory approved liquid--line filter drier is required on every unit.
S
Do NOT use an R--22 TXV.
S
Never open system to atmosphere while it is under a vacuum.
S
When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter
driers. Evacuate to 500 microns prior to recharging.
S
Do not vent Puron into the atmosphere.
S
Observe all
warnings
,
cautions
, and
bold
text.
S
All indoor coils must be installed with a hard shutoff Puron TXV metering device.
574D
--
--
A
Содержание 574D----A
Страница 3: ...3 A09469 Fig 2 574D A24 36 Unit Dimensions 574D A ...
Страница 4: ...4 A09470 Fig 3 574D A42 60 Unit Dimensions 574D A ...
Страница 16: ...16 A09282 Fig 14 208 230 1 60 Connection Wiring Diagram 574D A ...
Страница 17: ...17 A09282 Fig 14 Cont 208 230 1 60 Ladder Wiring Diagram 574D A ...
Страница 18: ...18 A09264 Fig 15 208 230 3 60 Connection Wiring Diagram 574D A ...
Страница 19: ...19 A09264 Fig 15 Cont 208 230 3 60 Ladder Wiring Diagram 574D A ...
Страница 20: ...20 A09265 Fig 16 460 3 60 Connection Wiring Diagram 574D A ...
Страница 21: ...21 A09265 Fig 16 Cont 460 3 60 Ladder Wiring Diagram 574D A ...
Страница 25: ...25 Table 7 Cooling Charging Chart A08490 574D A ...
Страница 50: ...50 A10098 Fig 45 Economizer Wiring Diagram 574D A ...
Страница 51: ...51 A10075 Fig 46 Connection Wiring Diagram 230 3 574D A ...
Страница 52: ...52 A10075 Fig 46 Cont Ladder Wiring Diagram 230 3 574D A ...
Страница 53: ...53 A10087 Fig 47 Connection Wiring Diagram 460 3 574D A ...
Страница 54: ...54 A10087 Fig 48 Ladder Wiring Diagram 460 3 574D A ...
Страница 58: ...58 A10064 Fig 49 574D A 30 36 3 Phase with Economizer 574D A ...
Страница 59: ...59 A10065 Fig 50 574D A 42 60 3 Phase with Economizer 574D A ...