31
Table 10 – 574D----A Wet Coil Pressure Drop (IN. W.C.)
UNIT
SIZE
STANDARD CFM (S.C.F.M)
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
24
0.030
0.037
0.044
0.053
0.063
---
---
---
---
---
---
---
---
---
---
30
---
0.037
0.044
0.053
0.063
0.072
0.081
0.105
---
---
---
---
---
---
---
36
---
---
---
0.055
0.060
0.090
0.100
0.110
0.140
---
---
---
---
---
---
42
---
---
---
---
0.045
0.050
0.060
0.065
0.075
0.080
0.090
0.094
0.110
---
---
48
---
---
---
---
---
---
0.041
0.063
0.085
0.100
0.104
0.110
0.120
0.130
---
60
---
---
---
---
---
---
---
---
---
0.060
0.065
0.072
0.077
0.085
0.100
Table 11 – Wet Coil Air Delivery (CFM) -- Downflow -- High Speed with 1--in. (25 mm) Filter and Economizer
UNIT SIZE
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
36
1333
1289
1256
1214
1152
1118
1076
1035
997
950
42
1612
1569
1527
1481
1451
1393
1351
1317
1278
1242
48
2166
2085
2002
1919
1798
1709
1582
1467
1270
988
60
2298
2239
2180
2110
2044
1951
1862
1777
1697
1591
MAINTENANCE
To ensure continuing high performance and to minimize the
possibility of premature equipment failure, periodic maintenance
must be performed on this equipment. This
unit should be
inspected at least once each year by a qualified service person. To
troubleshoot unit, refer to Table 12--14, Troubleshooting Chart.
NOTE TO EQUIPMENT OWNER: Consult your local dealer
about the availability of a maintenance contract.
PERSONAL
INJURY
AND
UNIT
DAMAGE
HAZARD
Failure to follow this warning could result in personal
injury or death and unit component damage.
The ability to properly perform maintenance on this
equipment requires certain expertise, mechanical skills,
tools and equipment. If you do not possess these, do not
attempt to perform any maintenance on this equipment,
other than those procedures recommended in the Owner’s
Manual.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow these warnings could result in personal
injury or death:
1. Turn off electrical power to the unit and install lock out
tag before performing any maintenance or service on this
unit.
2. Use extreme caution when removing panels and parts.
3. Never place anything combustible either on or in contact
with the unit.
!
WARNING
UNIT OPERATION HAZARD
Failure to follow this caution may result in improper
operation.
Errors made when reconnecting wires may cause improper
and dangerous operation. Label all wires prior to
disconnecting when servicing.
CAUTION
!
ENVIRONMENTAL HAZARD
Failure to follow this caution may result in environmental
pollution.
Remove and re--cycle all components or materials (i.e. oil,
refrigerant, etc) before unit final disposal.
!
CAUTION
The minimum maintenance requirements for this equipment are as
follows:
1. Inspect air filter(s) each month. Clean or replace when
necessary.
2. Inspect indoor coil, drain pan, and condensate drain each
cooling season for cleanliness. Clean when necessary.
3. Inspect blower motor and wheel for cleanliness at the
beginning of each heating and cooling season. Clean when
necessary. For first heating and cooling season, inspect
blower wheel bi--monthly to determine proper cleaning
frequency.
4. Check electrical connections for tightness and controls for
proper operation each heating and cooling season. Service
when necessary.
5. Ensure electric wires are not in contact with refrigerant
tubing or sharp metal edges.
6. Check and inspect heating section before each heating
season. Clean and adjust when necessary.
7. Check flue hood and remove any obstructions, if necessary.
Air Filter
IMPORTANT
: Never operate the unit without a suitable air filter
in the return--air duct system. Always replace the filter with the
same dimensional size and type as originally installed. See Table 1
for recommended filter sizes.
Inspect air filter(s) at least once each month and replace
(throwaway--type) or clean (cleanable--type) at least twice during
each cooling season and twice during the heating season, or
whenever the filter becomes clogged with dust and lint.
Indoor Blower and Motor
NOTE
: All motors are pre--lubricated. Do not attempt to lubricate
these motors.
For longer life, operating economy, and continuing efficiency,
clean accumulated dirt and grease from the blower wheel and
motor annually.
574D
--
--
A
Содержание 574D----A
Страница 3: ...3 A09469 Fig 2 574D A24 36 Unit Dimensions 574D A ...
Страница 4: ...4 A09470 Fig 3 574D A42 60 Unit Dimensions 574D A ...
Страница 16: ...16 A09282 Fig 14 208 230 1 60 Connection Wiring Diagram 574D A ...
Страница 17: ...17 A09282 Fig 14 Cont 208 230 1 60 Ladder Wiring Diagram 574D A ...
Страница 18: ...18 A09264 Fig 15 208 230 3 60 Connection Wiring Diagram 574D A ...
Страница 19: ...19 A09264 Fig 15 Cont 208 230 3 60 Ladder Wiring Diagram 574D A ...
Страница 20: ...20 A09265 Fig 16 460 3 60 Connection Wiring Diagram 574D A ...
Страница 21: ...21 A09265 Fig 16 Cont 460 3 60 Ladder Wiring Diagram 574D A ...
Страница 25: ...25 Table 7 Cooling Charging Chart A08490 574D A ...
Страница 50: ...50 A10098 Fig 45 Economizer Wiring Diagram 574D A ...
Страница 51: ...51 A10075 Fig 46 Connection Wiring Diagram 230 3 574D A ...
Страница 52: ...52 A10075 Fig 46 Cont Ladder Wiring Diagram 230 3 574D A ...
Страница 53: ...53 A10087 Fig 47 Connection Wiring Diagram 460 3 574D A ...
Страница 54: ...54 A10087 Fig 48 Ladder Wiring Diagram 460 3 574D A ...
Страница 58: ...58 A10064 Fig 49 574D A 30 36 3 Phase with Economizer 574D A ...
Страница 59: ...59 A10065 Fig 50 574D A 42 60 3 Phase with Economizer 574D A ...