41
OAT Sensor
Hood Top
Panel
A09689
Fig. 23 -- Economizer Hood Top Panel Removal
OAT Sensor
A09690
Fig. 24 -- Oat Sensor Installed
6. Replace horizontal return duct cover panel. Screw in place
ensuring all seams are air and watertight.
7. Install the 2 angle filter brackets to the right and left hood
side panels respectively with the #10 screws provided. See
Fig. 26.
8. Assemble hood according to Fig. 27 screwing together with
provided #10 sheet metal screws.
9. Install assembled hood over the economizer opening in the
replacement return chamber panel. See Fig. 28. Screw in
place through pre-punched holes. Make sure all seams are
air watertight.
NOTE
: The two wires that connect to the outside air temperature
sensor (OAT) should remain accessible.
10. Connect the outside air temperature sensor (OAT) to the
economizer per wiring diagram.
11. Open the filter clips on the inside of the hood top. Insert the
aluminum filter into the hood and close the clips to hold in
place. See Fig. 29.
12. To replace 12 x 20 x 1 (304.8mm x 508mm x 25.4mm) air
filters, open the filter access door (horizontal return duct
cover panel), remove old filters and install new disposable
filters in filter rack. See Table 18 for filter part number.
Table 18 – Filter Part Number
DESCRIPTION
PART NUMBER
Indoor Coil Air Filter
12 x 20 x 1
(304.8 x 508 x 25.4 mm)
KH01AA312
NOTE
:
The economizer control settings and the filters are
accessible through the filter access door.
13. Economizer controls are set to a standard factory setting.
Nevertheless, you can adjust these settings through the filter
access door. Review the settings in the Operation section:
(1.) The standard economizer controller has a factory
setting of “C” for the outdoor air temperature
changeover and 63
_
F (17
_
C) for the supply air
(mixed air) temperature sensor. The outdoor air
temperature changeover setting is adjusted on the
sensor by setting the dip switches on the sensor.
The ABCD potentiometer on the economizer
controller should be set to the “D” position.
(2.) The low ambient compressor lockout switch setting
is fixed at 42
_
F (5.6
_
C).
(3.) The minimum position for the outdoor air damper
can be configured at the controller. When not using
a CO
2
sensor, the DCV Max potentiometer must be
completely closed (CCW) for the Minimum Posi-
tion potentiometer to function correctly.
(4.) Settings for the optional outdoor enthalpy sensor,
indoor enthalpy sensor, and CO
2
sensor can also be
configured at the controller.
14. Replace the filter access panel. Screw in place ensuring all
seams are air and watertight.
15. Install all economizer accessories then power HVAC unit
and test cycle economizer.
574D
--
--
A
Содержание 574D----A
Страница 3: ...3 A09469 Fig 2 574D A24 36 Unit Dimensions 574D A ...
Страница 4: ...4 A09470 Fig 3 574D A42 60 Unit Dimensions 574D A ...
Страница 16: ...16 A09282 Fig 14 208 230 1 60 Connection Wiring Diagram 574D A ...
Страница 17: ...17 A09282 Fig 14 Cont 208 230 1 60 Ladder Wiring Diagram 574D A ...
Страница 18: ...18 A09264 Fig 15 208 230 3 60 Connection Wiring Diagram 574D A ...
Страница 19: ...19 A09264 Fig 15 Cont 208 230 3 60 Ladder Wiring Diagram 574D A ...
Страница 20: ...20 A09265 Fig 16 460 3 60 Connection Wiring Diagram 574D A ...
Страница 21: ...21 A09265 Fig 16 Cont 460 3 60 Ladder Wiring Diagram 574D A ...
Страница 25: ...25 Table 7 Cooling Charging Chart A08490 574D A ...
Страница 50: ...50 A10098 Fig 45 Economizer Wiring Diagram 574D A ...
Страница 51: ...51 A10075 Fig 46 Connection Wiring Diagram 230 3 574D A ...
Страница 52: ...52 A10075 Fig 46 Cont Ladder Wiring Diagram 230 3 574D A ...
Страница 53: ...53 A10087 Fig 47 Connection Wiring Diagram 460 3 574D A ...
Страница 54: ...54 A10087 Fig 48 Ladder Wiring Diagram 460 3 574D A ...
Страница 58: ...58 A10064 Fig 49 574D A 30 36 3 Phase with Economizer 574D A ...
Страница 59: ...59 A10065 Fig 50 574D A 42 60 3 Phase with Economizer 574D A ...