54
2. Set the tension gauge to the desired tension (see Table 1
in Fig. 67). Place the large O--ring at that point.
3. Press the tension checker downward on the belt until
the large O--ring is at the bottom of the straightedge.
4. Adjust the belt tension as needed.
Adjust belt tension by loosing the motor mounting plate
front bolts and rear bolt (see Fig. 68) and slide the plate
towards the fan (to reduce tension) or away from the fan
(to increase tension). Ensure the blower shaft and motor
shaft are parallel to each other (pulleys aligned). Tighten
all bolts securely when finished.
C160146
Fig. 67 -- V--Belt Force Label
BLOWER PULLEY
V-BELT
MOTOR
PULLEY
MOTOR
MOTOR MOUNTING
PLATE
MOUNTING
BOLTS (4)
C11504
Fig. 68 -- Belt Drive Motor Mounting
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
E
2018 Bryant Heating & Cooling Systems
Edition Date: 01/18
Printed in U.S.A.
Replaces: II548J--- 17--- 24--- 01
Catalog No. II548J---17---24---02
Содержание 548J*17 D Series
Страница 4: ...4 a548J 015 Fig 2 Unit Dimensional Drawing Size 17 Units ...
Страница 5: ...5 a548J 016 Fig 2 Unit Dimensional Drawing Size 17 Units cont ...
Страница 6: ...6 a548J 017 Fig 2 Unit Dimensional Drawing Size 17 Units cont ...
Страница 7: ...7 a548J 018 Fig 3 Unit Dimensional Drawing Size 24 Units ...
Страница 8: ...8 a548J 019 Fig 3 Unit Dimensional Drawing Size 24 Units cont ...
Страница 9: ...9 a548J 020 Fig 3 Unit Dimensional Drawing Size 24 Units cont ...
Страница 13: ...13 C10139 Fig 7 Roof Curb Details Size 17 Units ...
Страница 14: ...14 C10140 Fig 8 Roof Curb Details Size 24 Units ...
Страница 19: ...19 a50 9696 Fig 20 548J 17 24 Control Wiring Diagram with VFD Option ...
Страница 20: ...20 a50 9697 Fig 21 Typical 548J 17 24 Power Wiring Diagram 208 230V 3 Phase 60Hz unit shown ...
Страница 44: ...44 a50 9699 Fig 44 RTU Open System Control Wiring Diagram ...