51
Connect to
computer’s
USB port
Connect to
the Local
Access port
USB Link Kit
RTU Open Controller
Access
Port
J12
P1
P1
P5
P5
LOCAL
ACCESS
PORT
GND
GND
*Therm
mA
*Therm
mA
UI-10
UI-11
SW3
on
COMM
OPTION
CR2032
+
-
SW1
SW2
MSB
LSB
TX
RX
+12 DVC
Rnet-
Rnet+
GND
RNET
J12
J13
J15
J20
C14131
Fig. 60 -- PC Running Field Assistant
Table 23 – LEDs
The LEDs on the RTU Open show the status of certain functions
If this LED is on...
Status is...
Power
The RTU Open controller has power
Rx
The RTU Open controller is receiving data from the network segment
Tx
The RTU Open controller is transmitting data over the network segment
BO#
The binary output is active
The
Run
and
Error
LEDs indicate control module and network status
If Run LED shows...
And Error LED shows...
Status is...
2 flashes per second
Off
Normal
2 flashes per second
2 flashes, alternating with
Run
LED
Five minute auto---restart delay after system error
2 flashes per second
3 flashes, then off
Control module has just been formatted
2 flashes per second
4 flashes, then pause
Two or more devices on this network have the
same MSTP network address
2 flashes per second
On
Exec halted after frequent system errors or
control programs halted
5 flashes per second
On
Exec start---up aborted, Boot is running
5 flashes per second
Off
Firmware transfer in progress, Boot is running
7 flashes per second
7 flashes per second, alternating
with
Run
LED
Ten second recovery period after brownout
14 flashes per second
14 flashes per second,
alternating with
Run
LED
Brownout
On
On
Failure. Try the following solutions:
S
Turn the RTU Open controller off, then on.
S
Format the RTU Open controller.
S
Download memory to the RTU Open controller.
S
Replace the RTU Open controller.
Outdoor Air Enthalpy Control
(P/N 33CSENTHSW)
The enthalpy control (33CSENTHSW) is available as a
field--installed
accessory
to
be
used
with
the
EconoMi$er
R
2 damper system. The outdoor air enthalpy
sensor is part of the enthalpy control. (The separate
field--installed accessory return air enthalpy sensor
(33CSENTSEN) is required for differential enthalpy
control. See Fig. 61.)
7
CTB ECON
(RTU Open: to J2-6)
LOW
GND
24V
Enthalpy
Switch
GRA
BLK
RED
Factory Wiring Harness
PL6-1 (24-V)
PL6-4 (COM)
C11169
Fig. 61 -- Enthalpy Switch (33CSENTHSW) Connections
Содержание 548J*17 D Series
Страница 4: ...4 a548J 015 Fig 2 Unit Dimensional Drawing Size 17 Units ...
Страница 5: ...5 a548J 016 Fig 2 Unit Dimensional Drawing Size 17 Units cont ...
Страница 6: ...6 a548J 017 Fig 2 Unit Dimensional Drawing Size 17 Units cont ...
Страница 7: ...7 a548J 018 Fig 3 Unit Dimensional Drawing Size 24 Units ...
Страница 8: ...8 a548J 019 Fig 3 Unit Dimensional Drawing Size 24 Units cont ...
Страница 9: ...9 a548J 020 Fig 3 Unit Dimensional Drawing Size 24 Units cont ...
Страница 13: ...13 C10139 Fig 7 Roof Curb Details Size 17 Units ...
Страница 14: ...14 C10140 Fig 8 Roof Curb Details Size 24 Units ...
Страница 19: ...19 a50 9696 Fig 20 548J 17 24 Control Wiring Diagram with VFD Option ...
Страница 20: ...20 a50 9697 Fig 21 Typical 548J 17 24 Power Wiring Diagram 208 230V 3 Phase 60Hz unit shown ...
Страница 44: ...44 a50 9699 Fig 44 RTU Open System Control Wiring Diagram ...