Table 2 — Electrical Data
UNIT
542J
VOLTAGE
(3 Ph,
60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OUTDOOR
FAN
MOTOR
INDOOR FAN
MOTOR
POWER
EXHAUST
ELECTRIC HEAT*
POWER SUPPLY
DISCONNECT
SIZING
No. 1
No. 2
Min
Max
RLA
LRA
RLA
LRA
Qty
FLA
(ea)
Hp
FLA
FLA
LRA
FLA
kW
MCA
MOCP†
RLA
LRA
150
208/230
187
253
39.7
228
—
—
3
1.7
3.7
10.5/10.5
—
—
−/−
39/ 45
72/ 82
117/135
−/−
14/19
26/34
42/56
65/ 65
114/122
155/168
211/200
100/100
125/150
175/175
225/225
64/ 64
64/ 64
94/107
147/167
387/387
4.6
18.8
−/−
39/ 45
72/ 82
117/135
−/−
14/19
26/34
42/56
70/ 70
119/126
159/173
216/205
100/100
125/150
175/175
225/225
69/ 69
69/ 69
100/112
152/173
406/406
460
414
508
19.9
114
—
—
3
0.8
3.7
4.8
—
—
—
18
39
66
—
15
32
55
32
54
81
98
50
60
90
110
31
31
50
82
189
2.3
6.0
—
18
39
66
—
15
32
55
34
57
83
100
50
70
90
110
34
34
53
84
195
180
208/230
187
253
28.2
160
28.2
160
3
1.7
5
15.8/15.8
—
—
—/—
72/ 82
117/135
—/—
26/34
42/56
84/ 84
174/187
231/219
110/110
175/200
250/225
89/ 89
101/112
153/173
499/485
4.6
18.8
—/—
72/ 82
117/135
—/—
26/34
42/56
89/ 89
179/191
235/224
110/110
200/200
250/225
94/ 94
106/118
158/179
518/504
460
414
508
14.1
80
14.1
80
3
0.8
5
7.9
—
—
—
39
66
—
32
55
42
91
108
50
100
110
44
54
85
238
2.3
6.0
—
39
66
—
32
55
44
93
110
50
100
125
47
57
88
244
LEGEND
FLA
— Full Load Amps
HACR
— Heating, Air Conditioning and Refrigeration
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC
— National Electrical Code
RLA
— Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v and 480 v. If
power distribution voltage to unit varies from rated heater voltage, heater kW will
vary accordingly.
†Fuse or HACR circuit breaker. This is the maximum size permissible; smaller
fuse size may be used where conditions permit.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equip-
ment (refer to NEC Articles 430 and 440), the overcurrent protective device for
the unit shall be fuse or HACR breaker. The Canadian units may be fuse or
circuit breaker.
2. MCA calculation for units with electric heaters over 50 kW
= (1.25 x IFM amps) + (1.00 x heater FLA).
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater
than 2%. Use the following formula to determine the percent of voltage
imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
= 457
Determine maximum deviation from average voltage.
(AB) 457 − 452 = 5 v
(BC) 464 − 457 = 7 v
(AC) 457 − 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
7
% Voltage Imbalance = 100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
—10—
Содержание 542J Series
Страница 28: ...Fig 33 Typical Label Diagram Schematic 542J180 208 230 V 60 Hz Unit Shown cont 28...
Страница 29: ...TROUBLESHOOTING CHART HEATING CYCLE ODT Outdoor Temperature 29...
Страница 30: ...TROUBLESHOOTING CHART COOLING CYCLE Copyright 1997 Carrier Corporation CATALOG NO BDP 3354 237...
Страница 31: ......