SELECTION PROCEDURE (with example)

I DETERMINE COOLING AND HEATING REQUIRE-

MENTS AT DESIGN CONDITIONS:

Given:

Required Cooling Capacity (TC) . . . . . . . . . 172,000 Btuh
Sensible Heat Capacity (SHC) . . . . . . . . . . 133,000 Btuh
Required Heating Capacity . . . . . . . . . . . . . 170,000 Btuh
Outdoor Entering-Air Temperature . . . . . . . . . . . . . . 95 F
Indoor Entering-Air Temperature

(Cooling) . . . . . . . . . . . . . 80 F entering dry bulb (edb)

67 F entering wet bulb (ewb)

Outdoor Coil Entering Air Temperature (Heating) . . . 0° F
Indoor-Air Winter Design Temperature . . . . . . . . . . . 70 F
Evaporator Air Quantity . . . . . . . . . . . . . . . . . . . 6000 cfm
External Static Pressure (ESP) . . . . . . . . . . . 0.75 in. wg
Electrical Characteristics (V-Ph-Hz) . . . . . . . . . . 230-3-60

II SELECT UNIT BASED ON REQUIRED COOLING

CAPACITY:

Enter Gross Cooling Capacities table on page 9 at outdoor
entering-air temperature of 95 F, indoor air entering at
6000 cfm and 67 F ewb. The 542F unit will provide a total
cooling capacity of 185,400 Btuh and a sensible heat ca-
pacity of 146,700 Btuh.

For indoor-air temperature other than 80 F edb, calculate
sensible heat capacity correction, as required, using the
formula found in Note 3 following the cooling capacities
table.

NOTE: Unit ratings are gross capacities and do not include
the effect of indoor-fan motor heat. To calculate net capaci-
ties, see Step V.

III SELECT ELECTRIC HEAT:

Enter the Integrated Heating Capacities table on page 9 at
6000 cfm. At 70 F return air and 0° F air entering outdoor
coil, the integrated heating capacity is 67,000 Btuh. (De-
ductions for outdoor-coil frost and defrosting have already
been made. No correction is required.)

The required heating capacity is 170,000 Btuh. Therefore,
103,000 Btuh (170,000 – 67,000 Btuh) additional electric
heat is required.

Determine additional electric heat capacity in kW.

103,000 Btuh

= 30.2 kW of heat required.

3413 Btuh/kW

Enter the Electric Resistance Heater Data table on page 11
for 542F at 230-3-60. The 31.0-kW heater at 230 v most
closely satisfies the heating required.

31.0 kW x 3413 Btuh/kW = 105,800 Btuh

Total unit heating capacity at 0° F is 172,800 Btuh
(105,800 + 67,000).

IV DETERMINE FAN SPEED AND POWER REQUIRE-

MENTS AT DESIGN CONDITIONS:

Before entering the Air Delivery table calculate the total
static pressure required based on unit components. From
the given and the Pressure Drop tables, find:

External static pressure

0.75 in. wg

Economizer

0.07 in. wg

Electric heat

0.09 in. wg

Total static pressure

0.91 in. wg

Enter the Air Delivery table on page 10. At 6000 cfm, the
standard motor with alternate drive will deliver up to
1.40 in. wg static pressure and 3.82 brake horsepower
(bhp). This will adequately handle job requirements.

V DETERMINE NET CAPACITIES:

Capacities are gross and do not include the effect of
indoor-fan motor (IFM) heat.

Determine net cooling capacity as follows:

Convert bhp to Watts using the formula found in the note
following the Air Delivery table on page 10.

For example:

746 x Bhp

Watts =

Motor Efficiency

746 x 3.82

Watts =

.81

Watts = 3518

Net capacity = Gross capacity – IFM heat

= 185,400 Btuh – (3518 Watts

x 3.413 Btuh/Watts)

= 185,400 Btuh – 12,007 Btuh
= 173,393 Btuh

Net sensible capacity = 146,700 Btuh – 12,007 Btuh

= 134,693 Btuh

Determine net heating capacity as follows:

Net capacity = Gross ca IFM heat

+ Electric heat capacity

= 67,000 Btuh + 12,007 Btuh

+ 105,800 Btuh

= 184,807 Btuh

8

Содержание 542F

Страница 1: ... on finish is corrosion and fade resistant VERTICAL CONDENSER AIR DISCHARGE prevents recircu lation of hot condenser air and reduces the operating sound level MANUAL OUTDOOR AIR DAMPER standard equipment on units without optional economizer provides up to 25 outdoor air for ventilation SUPPLEMENTAL ELECTRIC HEATERS are available as ac cessory equipment for operation on 208 230 and 460 v and are mo...

Страница 2: ... the ability to relieve internal building pressure and pressure losses through the return air ductwork are greater than 0 20 in wg When the job requires the ability to move large quantities of air to relieve pressure in the conditioned space Head Pressure Control Kit consists of an outdoor air ther mostat that permits adequate head pressure control during cooling operation at low outdoor ambient t...

Страница 3: ...Bulb Air Conditioning and Refrigeration Institute NOTE 542F180 units are rated in accordance with ARI Standard 340 Cooling ratings are net values reflecting the effects of circulating fan heat Ratings are based on ESP 35 in wg Cooling Standard 80 F db 67 F wb indoor coil entering air tempera ture and 95 F outdoor coil entering air temperature High Temp Heating Standard 70 F db indoor coil entering...

Страница 4: ...DIMENSIONAL DRAWING BASE UNIT NOTE Space required for service clearance and airflow Allow 68 09 above the unit 78 09 on filter access panel end and 48 09 on remaining sides of unit 4 ...

Страница 5: ...18 69 457 389210 201 18 119 584 Pre Assembled High Static Horizontal Adapter 68 29 1880 08 61 49 159 18 25 89 371 LEGEND COMP SECT Compressor Section NOTES 1 Roof curb accessory is shipped unassembled 2 Insulated panels 1 2 in thick neoprene coated 2 lb density 3 Dimensions in are in millimeters 4 Direction of airflow 5 Roof curb 18 gage steel 6 Attach all ductwork to roof curb NOTE To prevent the...

Страница 6: ...ING HORIZONTAL ADAPTER INSTALLATION NOTE 389210 201 is a fully factory preassembled horizontal adapter which includes an insulated high static regain transition duct and substantially improves fan static performance 6 ...

Страница 7: ...nge Std 916 1186 Alt 1158 1428 Max Allowable Rpm 1550 Fan Pulley Pitch Diameter in 6 4 Motor Pulley Pitch Diameter in Std 3 4 4 4 Alt 4 3 5 3 Motor Frame Size Std 56 Alt Belt Quantity Type Std 1 A44 Alt 1 B45 Speed Change per Full Turn of 54 Moveable Pulley Flange Rpm Moveable Pulley Maximum Full 5 Turns from Closed Position Factory Setting Full Turns Open 5 Factory Speed Setting Rpm Std 916 Alt 1...

Страница 8: ...d heating capacity is 170 000 Btuh Therefore 103 000 Btuh 170 000 67 000 Btuh additional electric heat is required Determine additional electric heat capacity in kW 103 000 Btuh 30 2 kW of heat required 3413 Btuh kW Enter the Electric Resistance Heater Data table on page 11 for 542F at 230 3 60 The 31 0 kW heater at 230 v most closely satisfies the heating required 31 0 kW x 3413 Btuh kW 105 800 B...

Страница 9: ...8 77 76 75 Under 75 Over 85 81 82 83 84 85 Correction Factor 03 1 06 2 11 3 17 4 33 5 28 use formula shown below 10 98 1 96 2 94 3 92 4 91 15 93 1 85 2 78 3 71 4 63 20 87 1 74 2 62 3 49 4 36 Interpolation is permissible Do not extrapolate Correction Factor 1 10 x 1 BF x edb 80 INTEGRATED HEATING CAPACITIES OUTDOOR AIR TEMP F db at 70 RH INTEGRATED CAPACITY MBtuh TOTAL POWER INPUT kW INTEGRATED CAP...

Страница 10: ...ance is based on wet coil and clean 2 in filters Casing losses have been deducted 5 Electric heater pressure drop must be accounted for in fan rpm and bhp section see Static Pressure Losses table on page 11 6 Minimum cfm for units with electric resistance heat 5650 cfm Converting Bhp to Watts Bhp x 746 Watts input Motor Efficiency Approximate Motor Efficiency 81 AIR DELIVERY USING ACCESSORY POWER ...

Страница 11: ...32 04 05 06 07 08 09 11 12 55 05 06 07 08 10 12 14 16 80 06 07 08 10 12 15 17 20 Economizer All 02 03 04 05 06 07 08 09 FIOP Factory Installed Option Static pressure losses must be added to external static pressure before entering Air Delivery table ELECTRICAL DATA V PH HZ VOLTAGE RANGE COMPRESSOR each OUTDOOR FAN MOTOR INDOOR FAN MOTOR ELECTRIC HEAT POWER SUPPLY Min Max RLA LRA Qty FLA Hp FLA kW ...

Страница 12: ...ses time delay relay energizes closing compressor contactor no 2 Both compressors now operate from W1 and W2 controls electric heat Cooling Units With Economizer Outdoor Air Enthalpy Above Set Point Indoor and outdoor fans and compressors energize when there is a call for cooling The economizer damper moves to VENT position Outdoor Air Enthalpy Below Set Point Indoor fan starts and economizer damp...

Страница 13: ... designed to operate at outdoor temperatures down to 40 F At temperatures below 40 F accessory head pressure control device will permit operation at outdoor temperatures as low as 20 F 8 All roof curb and adapter installations must be counter flashed to prevent water leakage 9 Select unit based on cooling only Do not select heat pumps on heating capacity Add auxiliary resistance heat if required 1...

Страница 14: ...TYPICAL FIELD WIRING 14 ...

Страница 15: ...tactor HPS High Pressure Switch HR Heater Relay IFC Indoor Fan Contactor IP Internal Protector L Light LOR Lockout Relay LPS Low Pressure Switch MAT Mixed Air Thermostat PL Plug Assembly PRI Primary RVR Reversing Valve Relay SW Switch TB Terminal Block TC Thermostat Cooling TH Thermostat Heating TRAN Transformer Terminal Marked Terminal Unmarked Terminal Block Splice Splice Marked Factory Wiring F...

Страница 16: ...required by NEC and be supplied with rainshields INDOOR SECTION Indoor coil shall be constructed of alumi num plate fins mechanically bonded to seamless copper tubes Indoor blower shall be of centrifugal type forward curved The blower shall be belt driven by means of an adjustable pitch pul ley permitting a variation of airflow by means of blower speed adjustment Blower motor shall be electrically...