background image

11

WIRING

Recommended Connection Method for Power and
Communication Wiring (To minimize communication wiring
interference)
Power Wiring:

The main power is supplied to the outdoor unit. The field supplied
connecting cable from the outdoor unit to indoor unit consists of

three (3) wires and provides the power for the indoor unit. Two

wires are high voltage AC power and one is a ground wire.
Consult your local building codes and the NEC (National

Electrical Code) or CEC (Canadian Electrical Code) for special
requirements.
All wires must be sized per NEC or CEC and local codes. Use

Electrical Data table MCA (minimum circuit amps) and MOCP
(maximum over current protection) to correctly size the wires and

the disconnect fuse or breakers respectively.
Per caution note, only copper conductors with a minimum 300 volt

rating and 2/64- inch thick insulation must be used.

Communication Wiring:

A separate shielded copper conductor only, with a minimum 300

volt rating and 2/64- inch thick insulation, must be used as the
communication wire from the outdoor unit to the indoor unit.
To minimize voltage drop, the factory recommended wire size is
14/3 stranded with a ground. In special cases where there is high

electrical interference, please use a separate shielded 16GA

stranded control wire.

Alternate Connection Method for Power and Communication

Wiring (May not prevent communication wiring interference)

The main power is supplied to the outdoor unit. The field

supplied connecting cable from the outdoor unit to indoor unit

consists of four (4) wires and provides the power and
communication signals for the indoor unit. Two conductors are for

power wiring (L1/L2, or L/N), one is a ground wire, and one is a
DC communication wire.
Consult your local building codes and the NEC (National

Electrical Code) or CEC (Canadian Electrical Code) for special

requirements. All power wires must be sized per NEC or CEC and

local codes. Use Electrical Data table MCA (minimum circuit

amps) and MOCP (maximum over current protection) to correctly

size the wires and the disconnect fuse or breakers respectively.
Per caution note, only copper conductors with a minimum 300 volt

rating and 2/64- inch thick insulation must be used.

CAUTION

!

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.

S

Wires should be sized based on NEC and local codes.

S

Use copper conductors only with a minimum 300 volt

rating and 2/64 inch thick insulation.

CAUTION

!

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.

S

Be sure to comply with local codes while running wire
from indoor unit to outdoor unit.

S

Every wire must be connected firmly. Loose wiring
may cause terminal to overheat or result in unit

malfunction. A fire hazard may also exist. Therefore,
be sure all wiring is tightly connected.

S

No wire should be allowed to touch refrigerant tubing,

compressor or any moving parts.

S

Disconnecting means must be provided and shall be

located within sight and readily accessible from the air
conditioner.

S

Connecting cable with conduit shall be routed through

hole in the conduit panel.

The main power is supplied to the outdoor unit. The field supplied

connecting cable from the outdoor unit to indoor unit consists of

four wires and provides the power for the indoor unit as well as the

communication signal between the outdoor unit and indoor unit.

Two wires are high voltage AC power (L1 and L2), one is a

ground wire, and one is a DC communication wire.

CONTROL SYSTEM

The 619P unit is equipped with a microprocessor control to

perform two functions:

1. Provide safety for the system
2. Control the system and provide optimum levels of comfort

and efficiency

The main microprocessor is located on the control board of the

fan coil unit (outdoor units have a microprocessor too) with

thermistors located in the fan coil air inlet and on the indoor coil.

Heat pump units have a thermistor on the outdoor coil. These

thermistors monitor the system operation to maintain the unit

within acceptable parameters and control the operating mode.

WIRELESS REMOTE CONTROL

Fig. 7 – Wireless remote control

1. A wireless remote control is supplied for system operation

for system operation of all high- wall units.

2. Each battery operated wireless (infrared) remote control

may be used to control more than one unit.

WIRED REMOTE CONTROL (OPTIONAL)

P/N KSACN0101AAA

1. Optional wired remote controller used

for system operation of all high- wall

units.

2. Kit includes a wired remote controller

and a connecting cable.

3. Connect with wire terminal between

remote controller and indoor unit.

4. Display in

_

F or

_

C and temperature

increments every 1

_

F or every 1

_

C.

Fig. 8 – Wired Remote Control

Содержание 538PR

Страница 1: ...ily room addition S Special space requirements S When changes in the load cannot be handled by the existing system S When adding air conditioning to spaces that are heated by hydronic or electric heat and have no ductwork S Historical renovations or any application where preserving the look of the original structure is essential The ideal compliment to your ducted system when it is impractical or ...

Страница 2: ...ll indoor units service and maintenance expense is reduced due to easy to use cleanable filters In addition these high wall systems have extensive self diagnostics to assist in troubleshooting BUILT IN RELIABILITY Ductless split system indoor and outdoor units are designed to provide years of trouble free operation The high wall indoor units include protection against freeze up and high evaporator...

Страница 3: ...TO THE OUTDOOR UNIT B 1 1 Q A R SYSTEM TYPE Q HEAT PUMP VOLTAGE A 115 1 60 E 208 230 1 60 OUTDOOR UNIT 538 P MA 009 538 OUTDOOR UNIT P MODEL MA ALL MODELS NOMINAL CAPACITY 009 3 4TON 012 1TON 018 1 1 2TONS 024 2TONS 030 2 1 2TONS UNIT TYPE R OUTDOOR UNIT B MAXIMUM NUMBER OF FAN COIL UNITS THAT CAN BE CONNECTED TO THE OUTDOOR UNIT B 1 1 Use of the AHRI Certified TM Mark indicates a manufacturer s p...

Страница 4: ... Indoor Coil High Temp Protection in Heating Mode S Condenser High Temp Protection in Cooling Mode S Ease Of Service And Maintenance Cleanable Filters S Diagnostics S Liquid Line Pressure Taps S Application Flexibility Condensate Pumps A Crankcase Heater S Legend S Standard A Accessory INDOOR UNITS Fig 1 Condensate Pump Accessory On high wall fan coils the condensate pump has a lift capability of ...

Страница 5: ...6 7 1186 10 2 258 13 4 343 40 8 18 5 DIMENSIONS OUTDOOR Fig 3 Outdoor unit Model W in mm D in mm H in mm L1 in mm L2 in mm Operating Weight lb kg 9K 12K 32 0 810 12 2 310 22 0 558 20 9 530 11 4 290 82 5 37 4 18K 32 3 845 12 6 320 27 6 700 22 1 560 13 2 335 102 5 46 5 24K 37 2 945 15 6 395 31 9 810 25 1 640 15 9 405 137 6 62 4 30K 37 2 945 15 6 395 31 9 810 25 1 640 15 9 405 157 6 71 5 ...

Страница 6: ... 15m min 5 0 13m min 6 5 0 13m min 1 8m CEILING FLOOR Fig 4 Indoor Unit Clearance CLEARANCES OUTDOOR A D B Air outlet Air inlet C E Fig 5 Clearances Outdoor UNIT Minimum Value in mm A 24 609 B 24 609 C 24 609 D 4 101 E 4 101 ...

Страница 7: ... 550 Metering Device Electronic Expansion Valve Capillary Tube Charge Lb 2 76 2 76 2 76 2 76 4 19 5 18 6 62 Outdoor Coil Face Area Sq Ft 9 2 9 2 9 2 9 2 16 0 21 1 17 2 No Rows 2 2 2 2 2 3 3 Fins per inch 21 21 21 21 18 18 17 Circuits 4 4 4 4 6 8 6 Indoor Coil Face Area sq ft Sq Ft 2 2 2 2 2 2 2 2 2 6 3 7 3 7 No Rows 2 2 2 2 2 3 3 Fins per inch 20 20 20 20 20 18 18 Circuits 3 3 3 3 4 7 7 Compressor...

Страница 8: ... 8 69 8 66 7 62 6 53 5 81 Input 0 57 0 94 1 25 1 27 0 98 0 94 80 6F 27C 66 2F 19C TC 8 81 11 95 12 23 9 69 8 87 7 95 SC 7 49 8 32 8 63 7 85 6 64 6 04 Input 0 39 0 75 1 06 0 89 0 85 0 82 89 6F 32C 73 4F 23C TC 9 01 12 15 12 43 9 89 9 07 8 15 SC 7 7 8 53 8 84 8 06 6 85 6 25 Input 0 4 0 97 1 3 1 34 0 92 0 85 18 208 230V 69 8F 21C 59F 15C TC 12 58 15 24 16 25 11 04 8 32 6 78 SC 8 34 10 3 10 6 7 93 6 1...

Страница 9: ... 0 83 64 4F 18C TH 12 1 12 7 12 32 11 34 10 32 9 32 8 81 6 14 Input 0 83 1 37 1 4 1 26 1 22 1 27 1 01 0 91 69F 20 5C TH 12 3 12 6 12 12 11 32 10 21 9 12 8 43 6 49 Input 0 83 1 1 1 12 1 19 1 19 1 25 1 03 0 98 71 6F 22C TH 11 1 12 4 12 01 11 21 10 01 9 02 8 21 6 01 Input 0 85 1 15 1 16 1 21 1 23 1 31 1 05 1 18 208 230V 59F 15C TH 23 2 20 5 19 42 17 56 16 52 14 28 12 08 9 39 Input 1 58 1 49 1 48 1 58...

Страница 10: ...he base unit dimensional drawings for the location of mounting brackets SYSTEM OPERATING CONDITIONS Operating Range Min Max F C Cooling Heating Outdoor DB 4 122 20 50 4 86 20 30 Indoor DB 63 90 17 32 32 86 0 30 Indoor WB 59 84 15 29 Non Operating Temperature Range Min Max F C Indoor Outdoor DB 32 86 0 30 NOTE Reference the Product Installation Instructions for more information METERING DEVICES The...

Страница 11: ...esult in equipment damage or improper operation S Wires should be sized based on NEC and local codes S Use copper conductors only with a minimum 300 volt rating and 2 64 inch thick insulation CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation S Be sure to comply with local codes while running wire from indoor unit to outdoor unit S E...

Страница 12: ...34 27 42 34 27 46 5 40 33 50 45 39 50 45 39 Indoor Sound Pressure heating mode at different speeds dBa 40 33 26 41 34 27 40 33 26 41 34 27 45 39 32 47 44 38 47 44 38 Outdoor sound pressure level dBa 55 5 56 55 5 56 59 60 63 ELECTRICAL DATA UNIT SIZE OPER VOLTAGE MAX MIN COMPRESSOR OUTDOOR FAN INDOOR FAN MCA MAX FUSE CB AMP V PH HZ RLA V PH HZ FLA HP W V PH HZ FLA HP W 9K 127 104 115 1 60 5 3 115 1...

Страница 13: ...60 Range of cur rent Amps 0 17 10 0 17 10 0 07 10 0 07 10 0 17 10 0 23 10 0 23 10 Rated current Amps 0 17 0 17 0 07 0 07 0 17 0 23 0 23 Rated HP HP 0 027 0 027 0 027 0 027 0 077 0 08 0 08 Speed rev min 1300 1170 900 700 1300 1170 900 700 1300 1170 900 700 1300 1170 900 700 1300 1170 900 700 1250 1200 1100 900 250 1200 1100 900 Rated RPM rev min 1350 1350 1350 1350 1350 1350 1350 Max input W 25 25 ...

Страница 14: ...oltage AC115V CN16 Relative to the N terminal voltage DC 24V CN15 Maximum voltage DC5V CN6 Maximum output voltage AC115V CN4 Indoor fan interface Maximum voltage DC310V CN5 Stepper motor interface Maximum voltage between the lines DC12V P_1 Ground CN8 Room temperature sensor interface maximum voltage DC5V CN9 Pipe temperature sensor interface maximum voltage DC5V CN10A Display interface maximum vo...

Страница 15: ... 24V CN15 Maximum voltage DC5V CN6 Maximum output voltage AC230V CN4 Indoor fan interface Maximum voltage DC310V CN5 Stepper motor interface Maximum voltage between the lines DC12V P_1 Ground CN8 Room temperature sensor interface maximum voltage DC5V CN9 Pipe temperature sensor interface maximum voltage DC5V CN10A Display interface maximum voltage between the lines DC5V CN14 Stepper motor interfac...

Страница 16: ...r Voltage AC 230V CN11 Power Voltage AC230V CN16 Relative to the N terminal voltage DC 24V CN15 Maximum voltage DC5V CN6 Maximum output voltage AC230V CN4 Indoor fan interface Maximum voltage DC310V CN5 Stepper motor interface Maximum voltage between the lines DC12V P_1 Ground CN8 Room temperature sensor interface maximum voltage DC5V CN9 Pipe temperature sensor interface maximum voltage DC5V CN10...

Страница 17: ...output voltage AC230V CN4 Indoor fan interface Maximum voltage DC310V CN5 Stepper motor interface Maximum voltage between the lines DC12V P_1 Ground CN8 Room temperature sensor interface maximum voltage DC5V CN9 Pipe temperature sensor interface maximum voltage DC5V CN10A Display interface maximum voltage between the lines DC5V CN14 Stepper motor interface optional maximum voltage between the line...

Страница 18: ...e electric heating belt of chassis Fig 13 Wiring Diagram Size 30 208 230V INDOOR UNIT CONTROL BOARD INPUT or OUTPUT VALUE L_IN Power Voltage AC 230V CN11 Power Voltage AC230V CN16 Relative to the N terminal voltage DC 24V CN15 Maximum voltage DC5V CN6 Maximum output voltage AC230V CN4 Indoor fan interface Maximum voltage DC310V CN5 Stepper motor interface Maximum voltage between the lines DC12V P_...

Страница 19: ...hall have the ability to act as the temperature sensing location for room comfort The unit shall have the following functions as a minimum 1 An automatic restart after power failure at the same operating conditions as at failure 2 A timer function to provide a minimum 24 hour timer cycle for system Auto Start Stop 3 Temperature sensing controls shall sense return air temperature 4 Indoor coil free...

Страница 20: ...l bearings Motor shall be protected by internal thermal overload protection 3 Shaft shall have inherent corrosion resistance 4 Fan blades shall be non metallic and shall be statically and dynamically balanced 5 Outdoor fan openings shall be equipped with PVC metal mesh coated protection grille over fan D Compressor 1 Compressor shall be fully hermetic rotary type 2 Compressor shall be equipped wit...

Отзывы: