background image

10

APPLICATION DATA

UNIT SELECTION

Select equipment to either match or be slightly less than anticipated

peak load. This provides better humidity control, fewer unit cycles,

and less part- load operation.
For units used in spaces with high sensible loads, base equipment

selection on unit sensible load, not on total anticipated load. Adjust

for anticipated room wet bulb temperature to avoid undersizing

equipment.

UNIT MOUNTING (INDOOR)

Refer to unit Installation Instructions for further details.
Unit leveling

- For reliable operation, units should be level in all

planes.

Clearance

- Provide adequate clearance for airflow as shown in

Fig. 4.

Unit location

- Select a location which will provide the best air

circulation for the room.
These units should be positioned as high as possible on the wall for

best air circulation. The unit return and discharge should not be

obstructed by furniture, curtains, or anything which may cause unit

short cycling or air recirculation. Place the unit in the middle of the

selected wall (if possible). Use an outside wall, if available, to

make piping easier, and place the unit so it faces the normal

location of room occupants.

UNIT MOUNTING (OUTDOOR)

Refer to unit Installation Instructions for further details.
Unit leveling

- For reliable operation, units should be level in all

planes.

Clearance

- Minimum clearance, as shown in Fig. 5, must be

provided for airflow. The condensing units are designed for

free- blow application. Air inlets and outlets should not be

restricted.

Unit location

- A location which is convenient to installation and

not exposed to strong wind.
A location which can bear the weight of outdoor unit and where

the outdoor unit can be mounted in a level position.
Do not install the indoor or outdoor units in a location with special

environmental conditions. For those applications, contact your

Bryant representative.

MOUNTING TEMPLATE

Refer to unit Installation Instructions for further details.

The fan coil units are furnished with mounting to mark the location

of the wiring, and refrigeration line hole locations.

SUPPORT

Adequate support must be provided to support the weight of all fan

coils. Refer to the Physical Data section for fan coil weights, and

the base unit dimensional drawings for the location of mounting

brackets.

SYSTEM OPERATING CONDITIONS

Operating Range

Min / Max °F (°C)

Cooling

Heating

Outdoor DB

4 / 122 (-20 / 50)

4 / 86 (-20 / 30)

Indoor DB

63 / 90 (17 / 32)

32 / 86 (0 / 30)

Indoor WB

59 / 84 (15 / 29)

Non-Operating Temperature Range

Min / Max °F (°C)

Indoor/Outdoor DB

32 / 86 (0 / 30)

NOTE: Reference the Product Installation Instructions for more information.

METERING DEVICES

The outdoor unit (Sizes 09 - 18) has an electronic expansion valve

to manage the refrigerant flow of the fan coil connected. Sizes 24

and 30 have capillary tube metering devices in the outdoor unit.

DRAIN CONNECTIONS

Install drains to meet local sanitation codes. If adequate gravity

drainage cannot be provided, unit should be equipped with

accessory condensate pump. High wall fan coil unit condensate

pumps have a maximum lift of 10’ (3.05 m) for 9k and 12k units

and 25’ (7.62 m) for 18k and 30k units.
See physical dimension tables for drain sizes.

NOTE

:

High wall fan coil units have internal condensate traps.

A trap is not required.

Drain connections may be routed through alternate locations on

most fan coils as shown in Fig. 4.

Pipe holder

Pipe cover

Right piping

Left piping

Pipe cover

Right back piping

Left back piping

1

2

3

4

Fig. 6 – Piping Locations

REFRIGERANT LINES

General refrigerant line sizing:

1. The 538PR units are shipped with a full charge of R410A

refrigerant. All charges, line sizing, and capacities are
based on runs of 25 ft (7.6 m). For runs over 25 ft (7.6 m),
consult long- line section on this page for proper charge

adjustments.

2. Refrigerant lines should not be buried in the ground. If it is

necessary to bury the lines, not more than 36- in (914 mm)
should be buried. Provide a minimum 6- in (152 mm)
vertical rise to the service valves to prevent refrigerant

migration.

3. Both lines must be insulated. Use a minimum of 1/2- in.

(12.7 mm) thick insulation. Closed- cell insulation is
recommended in all long- line applications.

4. Special consideration should be given to isolating

interconnecting tubing from the building structure. Isolate
the tubing so that vibration or noise is not transmitted into

the structure.

Long Line Applications, 538PR Units:

1. No change in line sizing is required.
2. Add refrigerant per table below.

ADDITIONAL CHARGE TABLE

Unit
Size

Total Line

Length ft

Additional Charge, oz/ft.

ft (m)

Min

Max

10 - 25

(3 - 8)

>25 - 82

(8 - 25)

>82 - 164

(25 - 50)

9

10

82

None

0.16

12
18

98

24

0.32

0.32

30

164

Содержание 538PR

Страница 1: ...ily room addition S Special space requirements S When changes in the load cannot be handled by the existing system S When adding air conditioning to spaces that are heated by hydronic or electric heat and have no ductwork S Historical renovations or any application where preserving the look of the original structure is essential The ideal compliment to your ducted system when it is impractical or ...

Страница 2: ...ll indoor units service and maintenance expense is reduced due to easy to use cleanable filters In addition these high wall systems have extensive self diagnostics to assist in troubleshooting BUILT IN RELIABILITY Ductless split system indoor and outdoor units are designed to provide years of trouble free operation The high wall indoor units include protection against freeze up and high evaporator...

Страница 3: ...TO THE OUTDOOR UNIT B 1 1 Q A R SYSTEM TYPE Q HEAT PUMP VOLTAGE A 115 1 60 E 208 230 1 60 OUTDOOR UNIT 538 P MA 009 538 OUTDOOR UNIT P MODEL MA ALL MODELS NOMINAL CAPACITY 009 3 4TON 012 1TON 018 1 1 2TONS 024 2TONS 030 2 1 2TONS UNIT TYPE R OUTDOOR UNIT B MAXIMUM NUMBER OF FAN COIL UNITS THAT CAN BE CONNECTED TO THE OUTDOOR UNIT B 1 1 Use of the AHRI Certified TM Mark indicates a manufacturer s p...

Страница 4: ... Indoor Coil High Temp Protection in Heating Mode S Condenser High Temp Protection in Cooling Mode S Ease Of Service And Maintenance Cleanable Filters S Diagnostics S Liquid Line Pressure Taps S Application Flexibility Condensate Pumps A Crankcase Heater S Legend S Standard A Accessory INDOOR UNITS Fig 1 Condensate Pump Accessory On high wall fan coils the condensate pump has a lift capability of ...

Страница 5: ...6 7 1186 10 2 258 13 4 343 40 8 18 5 DIMENSIONS OUTDOOR Fig 3 Outdoor unit Model W in mm D in mm H in mm L1 in mm L2 in mm Operating Weight lb kg 9K 12K 32 0 810 12 2 310 22 0 558 20 9 530 11 4 290 82 5 37 4 18K 32 3 845 12 6 320 27 6 700 22 1 560 13 2 335 102 5 46 5 24K 37 2 945 15 6 395 31 9 810 25 1 640 15 9 405 137 6 62 4 30K 37 2 945 15 6 395 31 9 810 25 1 640 15 9 405 157 6 71 5 ...

Страница 6: ... 15m min 5 0 13m min 6 5 0 13m min 1 8m CEILING FLOOR Fig 4 Indoor Unit Clearance CLEARANCES OUTDOOR A D B Air outlet Air inlet C E Fig 5 Clearances Outdoor UNIT Minimum Value in mm A 24 609 B 24 609 C 24 609 D 4 101 E 4 101 ...

Страница 7: ... 550 Metering Device Electronic Expansion Valve Capillary Tube Charge Lb 2 76 2 76 2 76 2 76 4 19 5 18 6 62 Outdoor Coil Face Area Sq Ft 9 2 9 2 9 2 9 2 16 0 21 1 17 2 No Rows 2 2 2 2 2 3 3 Fins per inch 21 21 21 21 18 18 17 Circuits 4 4 4 4 6 8 6 Indoor Coil Face Area sq ft Sq Ft 2 2 2 2 2 2 2 2 2 6 3 7 3 7 No Rows 2 2 2 2 2 3 3 Fins per inch 20 20 20 20 20 18 18 Circuits 3 3 3 3 4 7 7 Compressor...

Страница 8: ... 8 69 8 66 7 62 6 53 5 81 Input 0 57 0 94 1 25 1 27 0 98 0 94 80 6F 27C 66 2F 19C TC 8 81 11 95 12 23 9 69 8 87 7 95 SC 7 49 8 32 8 63 7 85 6 64 6 04 Input 0 39 0 75 1 06 0 89 0 85 0 82 89 6F 32C 73 4F 23C TC 9 01 12 15 12 43 9 89 9 07 8 15 SC 7 7 8 53 8 84 8 06 6 85 6 25 Input 0 4 0 97 1 3 1 34 0 92 0 85 18 208 230V 69 8F 21C 59F 15C TC 12 58 15 24 16 25 11 04 8 32 6 78 SC 8 34 10 3 10 6 7 93 6 1...

Страница 9: ... 0 83 64 4F 18C TH 12 1 12 7 12 32 11 34 10 32 9 32 8 81 6 14 Input 0 83 1 37 1 4 1 26 1 22 1 27 1 01 0 91 69F 20 5C TH 12 3 12 6 12 12 11 32 10 21 9 12 8 43 6 49 Input 0 83 1 1 1 12 1 19 1 19 1 25 1 03 0 98 71 6F 22C TH 11 1 12 4 12 01 11 21 10 01 9 02 8 21 6 01 Input 0 85 1 15 1 16 1 21 1 23 1 31 1 05 1 18 208 230V 59F 15C TH 23 2 20 5 19 42 17 56 16 52 14 28 12 08 9 39 Input 1 58 1 49 1 48 1 58...

Страница 10: ...he base unit dimensional drawings for the location of mounting brackets SYSTEM OPERATING CONDITIONS Operating Range Min Max F C Cooling Heating Outdoor DB 4 122 20 50 4 86 20 30 Indoor DB 63 90 17 32 32 86 0 30 Indoor WB 59 84 15 29 Non Operating Temperature Range Min Max F C Indoor Outdoor DB 32 86 0 30 NOTE Reference the Product Installation Instructions for more information METERING DEVICES The...

Страница 11: ...esult in equipment damage or improper operation S Wires should be sized based on NEC and local codes S Use copper conductors only with a minimum 300 volt rating and 2 64 inch thick insulation CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation S Be sure to comply with local codes while running wire from indoor unit to outdoor unit S E...

Страница 12: ...34 27 42 34 27 46 5 40 33 50 45 39 50 45 39 Indoor Sound Pressure heating mode at different speeds dBa 40 33 26 41 34 27 40 33 26 41 34 27 45 39 32 47 44 38 47 44 38 Outdoor sound pressure level dBa 55 5 56 55 5 56 59 60 63 ELECTRICAL DATA UNIT SIZE OPER VOLTAGE MAX MIN COMPRESSOR OUTDOOR FAN INDOOR FAN MCA MAX FUSE CB AMP V PH HZ RLA V PH HZ FLA HP W V PH HZ FLA HP W 9K 127 104 115 1 60 5 3 115 1...

Страница 13: ...60 Range of cur rent Amps 0 17 10 0 17 10 0 07 10 0 07 10 0 17 10 0 23 10 0 23 10 Rated current Amps 0 17 0 17 0 07 0 07 0 17 0 23 0 23 Rated HP HP 0 027 0 027 0 027 0 027 0 077 0 08 0 08 Speed rev min 1300 1170 900 700 1300 1170 900 700 1300 1170 900 700 1300 1170 900 700 1300 1170 900 700 1250 1200 1100 900 250 1200 1100 900 Rated RPM rev min 1350 1350 1350 1350 1350 1350 1350 Max input W 25 25 ...

Страница 14: ...oltage AC115V CN16 Relative to the N terminal voltage DC 24V CN15 Maximum voltage DC5V CN6 Maximum output voltage AC115V CN4 Indoor fan interface Maximum voltage DC310V CN5 Stepper motor interface Maximum voltage between the lines DC12V P_1 Ground CN8 Room temperature sensor interface maximum voltage DC5V CN9 Pipe temperature sensor interface maximum voltage DC5V CN10A Display interface maximum vo...

Страница 15: ... 24V CN15 Maximum voltage DC5V CN6 Maximum output voltage AC230V CN4 Indoor fan interface Maximum voltage DC310V CN5 Stepper motor interface Maximum voltage between the lines DC12V P_1 Ground CN8 Room temperature sensor interface maximum voltage DC5V CN9 Pipe temperature sensor interface maximum voltage DC5V CN10A Display interface maximum voltage between the lines DC5V CN14 Stepper motor interfac...

Страница 16: ...r Voltage AC 230V CN11 Power Voltage AC230V CN16 Relative to the N terminal voltage DC 24V CN15 Maximum voltage DC5V CN6 Maximum output voltage AC230V CN4 Indoor fan interface Maximum voltage DC310V CN5 Stepper motor interface Maximum voltage between the lines DC12V P_1 Ground CN8 Room temperature sensor interface maximum voltage DC5V CN9 Pipe temperature sensor interface maximum voltage DC5V CN10...

Страница 17: ...output voltage AC230V CN4 Indoor fan interface Maximum voltage DC310V CN5 Stepper motor interface Maximum voltage between the lines DC12V P_1 Ground CN8 Room temperature sensor interface maximum voltage DC5V CN9 Pipe temperature sensor interface maximum voltage DC5V CN10A Display interface maximum voltage between the lines DC5V CN14 Stepper motor interface optional maximum voltage between the line...

Страница 18: ...e electric heating belt of chassis Fig 13 Wiring Diagram Size 30 208 230V INDOOR UNIT CONTROL BOARD INPUT or OUTPUT VALUE L_IN Power Voltage AC 230V CN11 Power Voltage AC230V CN16 Relative to the N terminal voltage DC 24V CN15 Maximum voltage DC5V CN6 Maximum output voltage AC230V CN4 Indoor fan interface Maximum voltage DC310V CN5 Stepper motor interface Maximum voltage between the lines DC12V P_...

Страница 19: ...hall have the ability to act as the temperature sensing location for room comfort The unit shall have the following functions as a minimum 1 An automatic restart after power failure at the same operating conditions as at failure 2 A timer function to provide a minimum 24 hour timer cycle for system Auto Start Stop 3 Temperature sensing controls shall sense return air temperature 4 Indoor coil free...

Страница 20: ...l bearings Motor shall be protected by internal thermal overload protection 3 Shaft shall have inherent corrosion resistance 4 Fan blades shall be non metallic and shall be statically and dynamically balanced 5 Outdoor fan openings shall be equipped with PVC metal mesh coated protection grille over fan D Compressor 1 Compressor shall be fully hermetic rotary type 2 Compressor shall be equipped wit...

Отзывы: