background image

7

Check Charge

Factory charge amount and desired subcooling are shown on unit
rating plate. Charging method is shown on information plate

inside unit. To properly check or adjust charge, conditions must

be favorable for subcooling charging. Favorable conditions exist
when the outdoor temperature is between 70

_

F and 100

_

F

(21.11

_

C and 37.78

_

C), and the indoor temperature is between

70

_

F and 80

_

F (21.11

_

C and 26.67

_

C). Follow the procedure

below:
Unit is factory charged for 15ft (4.57 m) of lineset. Adjust charge

by adding or removing 0.6 oz/ft of 3/8 liquid line above or below

15ft (4.57 m) respectively.
For standard refrigerant line lengths (80 ft/24.38 m or less), allow

system to operate in cooling mode at least 15 minutes. If
conditions are favorable, check system charge by subcooling

method. If any adjustment is necessary, adjust charge slowly and

allow system to operate for 15 minutes to stabilize before
declaring a properly charged system.
If the indoor temperature is above 80

_

F (26.67

_

C), and the

outdoor temperature is in the favorable range, adjust system

charge by weight based on line length and allow the indoor

temperature to drop to 80

_

F (26.67

_

C) before attempting to

check system charge by subcooling method as described above.
If the indoor temperature is below 70

_

F (21.11

_

C), or the

outdoor temperature is not in the favorable range, adjust charge

for line set length above or below 15ft (4.57 m) only. Charge
level should then be appropriate for the system to achieve rated

capacity. The charge level could then be checked at another time

when the both indoor and outdoor temperatures are in a more
favorable range.

NOTE

: If line length is beyond 80 ft (24.38 m) or greater than

20 ft (6.10 m) vertical separation, See Long Line Guideline for
special charging requirements.

Heating Check Chart Procedure

To check system operation during heating cycle, refer to the
Heating Check Chart on outdoor unit. This chart indicates

whether a correct relationship exists between system operating

pressure and air temperature entering indoor and outdoor units. If
pressure and temperature do not match on chart, system

refrigerant charge may not be correct. Do not use chart to adjust
refrigerant charge.

GENERAL SEQUENCE OF OPERATION

STANDARD THERMOSTAT

Turn on power to indoor and outdoor units. Transformer is
energized with power supplied.

Cooling

On

a

call

for

cooling,

a

standard

thermostat

(non--communicating) makes circuits R--O and R--Y and R--G.

Circuit R--O energizes reversing valve, switching it to cooling
position. Circuit R--Y energizes contactor, starting outdoor fan

motor and compressor circuit. R--G energizes indoor unit blower
relay, starting indoor blower motor on high speed.
When a standard thermostat (non--communicating) is satisfied, its

contacts open, de--energizing contactor and blower relay.

Compressor and motors should stop.

NOTE

: If indoor unit is equipped with a time--delay relay circuit,

the indoor blower will run an additional 90 seconds to increase
system efficiency.

Heating

On a call for heating a standard thermostat (non--communicating)
makes circuits R--Y and R--G. Circuit R--Y energizes contactor,

starting outdoor fan motor and compressor. Circuit R--G

energizes indoor blower relay, starting blower motor on high
speed.
Should temperature continue to fall, R--W2 is made through

second--stage room thermostat. Circuit R--W2 energizes a relay,
bringing on first bank of supplemental electric heat and providing

electrical potential to second heater relay (if used). If outdoor

temperature falls below setting of outdoor thermostat (factory
installed), contacts close to complete circuit and bring on second

bank of supplemental electric heat.
When thermostat is satisfied, its contacts open, de--energizing
contactor and relay. All heaters and motors should stop after all

fan off delays.

HEAT PUMP SYSTEM FUNCTIONS

AND SEQUENCE OF OPERATION

The outdoor unit control system has special functions. The
following is an overview of the control functions.

SEQUENCE OF OPERATION
Cooling & Heating Operation

This product utilizes either a standard indoor thermostat or
Evolution communication User Interface. With a call for cooling,

the outdoor fan, reversing valve, and compressor are energized.
When the cooling demand is satisfied, the compressor and fan

will shut off. The reversing valve will remain energized until the

control board power is removed or a call for heating is initiated.

NOTE

: The outdoor fan motor will continue to operate for one

minute after compressor shuts off, when the outdoor ambient is
greater than or equal to 100

_

F/37.78

_

C.

With a call for heating, the outdoor fan and compressor are
energized. The reversing valve is de--energized in the heating

mode.

Communication and Status Function Lights

Green Communications (COMM) Light

(Evolution Control only)

A green LED (COMM light) on the outdoor board (see Fig. 11)

indicates successful communication with the other system

products. The green LED will remain OFF until communications
is established. Once a valid command is received, the green LED

will turn ON continuously. If no communication is received

within 2 minutes, the LED will be turned OFF until the next valid
communication.

Amber Status Light

An amber colored STATUS light is used to display the operation
mode and fault codes as specified in the troubleshooting section.

See Table 3 for codes and definitions.

NOTE

: Only one fault code will be displayed on the outdoor

unit control board (the most recent, with the highest priority).

Crankcase Heater Operation

The crankcase heater (when applicable) is energized during the
off cycle below 65

_

F/18.33

_

C.

Outdoor Fan Motor Operation

The outdoor unit control energizes outdoor fan any time the
compressor is operating (except defrost and intermittently during

low ambient cooling). The outdoor fan remains energized for 15
minutes if a pressure switch or compressor thermal protector

should open. Outdoor fan motor will continue to operate for one
minute after the compressor shuts off when the outdoor ambient

is greater than or equal to 100

_

F/37.78

_

C.

264A

/265A

Содержание 264A

Страница 1: ...than 1 disconnect switch Lock out and tag switch with a suitable warning label IMPORTANT Maximum liquid line size is 3 8 in OD for all residential applications including long line IMPORTANT Always in...

Страница 2: ...B C 29 1 2 X 33 749 3 X 838 2 10 1 16 255 6 5 5 8 142 9 23 3 4 603 3 36 1 2 X 40 927 1 X 1016 9 5 8 244 5 6 13 16 173 0 28 3 4 730 3 A05177 Fig 2 Tiedown Knockout Requirements On rooftop applications...

Страница 3: ...mended No Recommended For tubing line sets between 80 and 200 ft 24 38 and 60 96 m and or 20 ft 6 09 m vertical differential refer to Residential Split System Longline Application Guideline Table 2 Re...

Страница 4: ...esult in equipment damage or improper operation Installation of filter drier in liquid line is required Install Liquid Line Filter Drier Indoor Refer to Fig 4 and install filter drier as follows 1 Bra...

Страница 5: ...ELD POWER WIRING A91056 Fig 6 Line Connections Connect Control Wiring Route 24v control wires through control wiring grommet and connect leads to control wiring See Thermostat Installation Instruction...

Страница 6: ...l regulations require that you do not vent refrigerant to the atmosphere Recover during system repair or final unit disposal Follow these steps to properly start up system 1 After system is evacuated...

Страница 7: ...wer will run an additional 90 seconds to increase system efficiency Heating On a call for heating a standard thermostat non communicating makes circuits R Y and R G Circuit R Y energizes contactor sta...

Страница 8: ...ed with a non communicating thermostat the utility relay should be wired between R and Y Low Ambient Cooling When this unit is operating below 55_F 12 78_C outdoor temperature provisions must be made...

Страница 9: ...emperature do not meet the above requirements an abbreviated 30 second de frost will occur QUIET SHIFT This feature must be enabled by selecting the 3rd position of the 3 position dip switch for a non...

Страница 10: ...control will energize the compressor contactor every 15 minutes If the thermal protector closes at the next 15 minute interval check the unit will resume operation If the thermal cutout trips for thr...

Страница 11: ...flow Control Fault 45 Outdoor unit control board has failed Control board needs to be replaced Brown Out 24 v 46 The control voltage is less than 15 5v for at least 4 seconds Com pressor and fan oper...

Страница 12: ...perating S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detec...

Отзывы: