background image

2

INSTALLATION

Check Equipment and Job Site
Unpack Unit

Move to final location. Remove carton taking care not to damage
unit.

Inspect Equipment

File claim with shipping company prior to installation if shipment

is damaged or incomplete. Locate unit rating plate on unit corner

panel. It contains information needed to properly install unit.
Check rating plate to be sure unit matches job specifications.

Install on a Solid, Level Mounting Pad

If conditions or local codes require the unit be attached to pad,

tiedown bolts should be used and fastened through knockouts
provided in unit base pan. Refer to unit mounting pattern in

Fig. 2 to determine base pan size and knockout hole location.
For hurricane tie downs, contact distributor for details and PE

Certification (Professional Engineer), if required.
On rooftop applications, mount on level platform or frame. Place
unit above a load--bearing wall and isolate unit and tubing set

from structure. Arrange supporting members to adequately

support unit and minimize transmission of vibration to building.
Consult local codes governing rooftop applications.
Roof mounted units exposed to winds above 5 mph may require

wind baffles. Consult the Service Manual -- Residential Split
System Air Conditioners and Heat Pumps for wind baffle

construction.

NOTE

: Unit must be level to within

±

2

°

(

±

3/8 in./ft.) per

compressor manufacturer specifications.

Clearance Requirements

When installing, allow sufficient space for airflow clearance,
wiring, refrigerant piping, and service. Allow 30 in. (762 mm)

clearance to service end of unit and 48 in. (1219.2 mm) above

unit. For proper airflow, a 6 in. (152.4 mm) clearance on 1 side of
unit and 12 in. (304.8 mm) on all remaining sides must be

maintained. Maintain a distance of 24 in. (609.6 mm) between
units. Position so water, snow, or ice from roof or eaves cannot

fall directly on unit.

VIEW

FROM TOP

3/8--IN. DIA. TIEDOWN KNOCKOUTS

IN BASEPAN (2) PLACES

UNIT BASE PAN

DIMENSIONS

in. (mm)

TIEDOWN KNOCKOUT LOCATIONS

in. (mm)

A

B

C

29--1/2 X 33

(749.3 X 838.2)

10–1/16

(255.6)

5–5/8

(142.9)

23–3/4

(603.3)

36–1/2 X 40

(927.1 X 1016)

9–5/8

(244.5)

6–13/16

(173.0)

28–3/4

(730.3)

A05177

Fig. 2

---

Tiedown Knockout Requirements

On rooftop applications, locate unit at least 6 in. above roof
surface.

Operating Ambient

The minimum outdoor operating ambient in cooling mode is
55

°

F/12.78

_

C without low ambient cooling enabled, and the

maximum outdoor operating ambient in cooling mode is

125

°

F/51.67

_

C. The maximum outdoor operating ambient in

heating mode is 66

°

F/18.89

_

C.

Elevate Unit

CAUTION

!

UNIT OPERATION HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Unit must be kept free of an accumulation of water and/or ice

in the basepan.

Elevate unit per local climate and code requirements to provide

clearance above estimated snowfall level and ensure adequate
drainage of unit. If using accessory support feet, use installation

instructions from kit for installation.

CAUTION

!

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
To prevent damage to the unit, ensure that it is located with

the supports such that the unit is stable in all circumstances

including adverse conditions.

Make Piping Connections

!

WARNING

PERSONAL INJURY / ENVIRONMENTAL HAZARD

Failure to follow this warning could result in personal injury

or death.
Relieve pressure and recover all refrigerant before system

repair or final unit disposal.
Use all service ports and open all flow--control devices,

including solenoid valves.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
If ANY refrigerant tubing is buried, provide a 6 in. (152.4

mm) vertical rise at service valve. Refrigerant tubing lengths

up to 36 in.(914.4 mm) may be buried without further

special consideration. Do not bury lines longer than 36 in.

(914.4 mm).

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
To prevent damage to unit or service valves, observe the

following:

S

Use a brazing shield.

S

Wrap service valves with wet cloth or use a heat sink

material.

264A

/265A

Содержание 264A

Страница 1: ...than 1 disconnect switch Lock out and tag switch with a suitable warning label IMPORTANT Maximum liquid line size is 3 8 in OD for all residential applications including long line IMPORTANT Always in...

Страница 2: ...B C 29 1 2 X 33 749 3 X 838 2 10 1 16 255 6 5 5 8 142 9 23 3 4 603 3 36 1 2 X 40 927 1 X 1016 9 5 8 244 5 6 13 16 173 0 28 3 4 730 3 A05177 Fig 2 Tiedown Knockout Requirements On rooftop applications...

Страница 3: ...mended No Recommended For tubing line sets between 80 and 200 ft 24 38 and 60 96 m and or 20 ft 6 09 m vertical differential refer to Residential Split System Longline Application Guideline Table 2 Re...

Страница 4: ...esult in equipment damage or improper operation Installation of filter drier in liquid line is required Install Liquid Line Filter Drier Indoor Refer to Fig 4 and install filter drier as follows 1 Bra...

Страница 5: ...ELD POWER WIRING A91056 Fig 6 Line Connections Connect Control Wiring Route 24v control wires through control wiring grommet and connect leads to control wiring See Thermostat Installation Instruction...

Страница 6: ...l regulations require that you do not vent refrigerant to the atmosphere Recover during system repair or final unit disposal Follow these steps to properly start up system 1 After system is evacuated...

Страница 7: ...wer will run an additional 90 seconds to increase system efficiency Heating On a call for heating a standard thermostat non communicating makes circuits R Y and R G Circuit R Y energizes contactor sta...

Страница 8: ...ed with a non communicating thermostat the utility relay should be wired between R and Y Low Ambient Cooling When this unit is operating below 55_F 12 78_C outdoor temperature provisions must be made...

Страница 9: ...emperature do not meet the above requirements an abbreviated 30 second de frost will occur QUIET SHIFT This feature must be enabled by selecting the 3rd position of the 3 position dip switch for a non...

Страница 10: ...control will energize the compressor contactor every 15 minutes If the thermal protector closes at the next 15 minute interval check the unit will resume operation If the thermal cutout trips for thr...

Страница 11: ...flow Control Fault 45 Outdoor unit control board has failed Control board needs to be replaced Brown Out 24 v 46 The control voltage is less than 15 5v for at least 4 seconds Com pressor and fan oper...

Страница 12: ...perating S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detec...

Отзывы: