background image

11

Status Codes

Table 3 shows the status codes flashed by the amber status light.
Most system problems can be diagnosed by reading the status

code as flashed by the amber status light on the control board.
The codes are flashed by a series of short and long flashes of the

status light. The short flashes indicate the first digit in the status
code, followed by long flashes indicating the second digit of the

error code. The short flash is 0.25 second ON and the long flash

is 1.0 second ON. Time between flashes is 0.25 second. Time
between short flash and first long flash is 1.0 second. Time

between code repeating is 2.5 seconds with LED OFF.
Count the number of short and long flashes to determine the

appropriate flash code. Table 3 gives possible causes and actions
related to each error.

Example:

3 short flashes followed by 2 long flashes indicates a

32 code. Table 3 shows this to be low pressure switch open.

Table 3—Status Codes

OPERATION

FAULT

AMBER LED

FLASH CODE

POSSIBLE CAUSE AND ACTION

Standby – no call for

unit operation

None

On solid, no

flash

Normal operation

Cool/Heat Operation

None

1, pause

Normal operation

System Communica-

tions Failure

16

Communication with user interface lost. Check wiring to UI, indoor

and outdoor units

High Pressure Switch

Open

31

High pressure switch trip. Check refrigerant charge, outdoor fan

operation and coils for airflow restrictions.

Low Pressure Switch

Open

32

Low pressure switch trip. Check refrigerant charge and indoor air

flow

Control Fault

45

Outdoor unit control board has failed. Control board needs to be

replaced.

Brown Out

(24 v)

46

The control voltage is less than 15.5v for at least 4 seconds. Com-

pressor and fan operation not allowed until control voltage is a mini-

mum of 17.5v. Verify control voltage.

Outdoor Air Temp

Sensor Fault

53

Outdoor air sensor not reading or out of range. Ohm out sensor

and check wiring

Outdoor Coil Sensor

Fault

55

Coil sensor not reading or out of range. Ohm out sensor and check

wiring

Thermistors out of

range

56

Improper relationship between coil sensor and outdoor air sensor.

Ohm out sensors and check wiring.

Thermal Cutout

72

Compressor voltage sensed after start---up, then absent for 10 con-

secutive seconds while cooling demand exists. Possible causes are

internal compressor overload trip or loss of high voltage to com-

pressor without loss of control voltage.

Contactor Shorted

73

Compressor voltage sensed when no demand for compressor op-

eration exists. Contactor may be stuck closed or there is a wiring

error.

No 230V at Compres-

sor

74

Compressor voltage not sensed when compressor should be start-

ing. Disconnect may be open or contactor may be stuck open or

there is a wiring error.

Thermal Lockout

82

Thermal cutout occurs in three consecutive cycles. Unit operation

locked out for 4 hours or until 24v power recycled.

Low Pressure Lock-

out

83

Low pressure switch trip has occurred during 5 consecutive cycles.

Unit operation locked out for 4 hours or until 24v power recycled.

High Pressure Lock-

out

84

High pressure switch trip has occurred during 5 consecutive cycles.

Unit operation locked out for 4 hours or until 24v power recycled.

264A

/265A

Содержание 264A

Страница 1: ...than 1 disconnect switch Lock out and tag switch with a suitable warning label IMPORTANT Maximum liquid line size is 3 8 in OD for all residential applications including long line IMPORTANT Always in...

Страница 2: ...B C 29 1 2 X 33 749 3 X 838 2 10 1 16 255 6 5 5 8 142 9 23 3 4 603 3 36 1 2 X 40 927 1 X 1016 9 5 8 244 5 6 13 16 173 0 28 3 4 730 3 A05177 Fig 2 Tiedown Knockout Requirements On rooftop applications...

Страница 3: ...mended No Recommended For tubing line sets between 80 and 200 ft 24 38 and 60 96 m and or 20 ft 6 09 m vertical differential refer to Residential Split System Longline Application Guideline Table 2 Re...

Страница 4: ...esult in equipment damage or improper operation Installation of filter drier in liquid line is required Install Liquid Line Filter Drier Indoor Refer to Fig 4 and install filter drier as follows 1 Bra...

Страница 5: ...ELD POWER WIRING A91056 Fig 6 Line Connections Connect Control Wiring Route 24v control wires through control wiring grommet and connect leads to control wiring See Thermostat Installation Instruction...

Страница 6: ...l regulations require that you do not vent refrigerant to the atmosphere Recover during system repair or final unit disposal Follow these steps to properly start up system 1 After system is evacuated...

Страница 7: ...wer will run an additional 90 seconds to increase system efficiency Heating On a call for heating a standard thermostat non communicating makes circuits R Y and R G Circuit R Y energizes contactor sta...

Страница 8: ...ed with a non communicating thermostat the utility relay should be wired between R and Y Low Ambient Cooling When this unit is operating below 55_F 12 78_C outdoor temperature provisions must be made...

Страница 9: ...emperature do not meet the above requirements an abbreviated 30 second de frost will occur QUIET SHIFT This feature must be enabled by selecting the 3rd position of the 3 position dip switch for a non...

Страница 10: ...control will energize the compressor contactor every 15 minutes If the thermal protector closes at the next 15 minute interval check the unit will resume operation If the thermal cutout trips for thr...

Страница 11: ...flow Control Fault 45 Outdoor unit control board has failed Control board needs to be replaced Brown Out 24 v 46 The control voltage is less than 15 5v for at least 4 seconds Com pressor and fan oper...

Страница 12: ...perating S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detec...

Отзывы: