Installation Instructions

264A / 265A

PREFERRED

SERIES HEAT PUMP

WITH PURON

®

REFRIGERANT

SIZES 018 TO 060

1--1/2 TO 5 NOMINAL TONS

SAFETY CONSIDERATIONS

Improper

installation,

adjustment,

alteration,

service,

maintenance, or use can cause explosion, fire, electrical shock, or

other conditions which may cause death, personal injury, or
property damage. Consult a qualified installer, service agency, or

your distributor or branch for information or assistance. The

qualified installer or agency must use factory--authorized kits or
accessories when modifying this product. Refer to the individual

instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.

Have fire extinguisher available. Read these instructions

thoroughly and follow all warnings or cautions included in
literature and attached to the unit. Consult local building codes

and National Electrical Code (NEC) for special requirements.

Recognize safety information. This is the safety--alert symbol

!

!

When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand these signal words: DANGER, WARNING, and

CAUTION. These words are used with the safety--alert symbol.

DANGER identifies the most serious hazards which

will

result in

severe personal injury or death. WARNING signifies hazards

which

could

result in personal injury or death. CAUTION is

used to identify unsafe practices which

may

result in minor

personal injury or product and property damage. NOTE is used to
highlight suggestions which

will

result in enhanced installation,

reliability, or operation.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Before installing, modifying, or servicing system, main

electrical disconnect switch must be in the OFF position.

There may be more than 1 disconnect switch. Lock out and

tag switch with a suitable warning label.

IMPORTANT

: Maximum liquid--line size is 3/8--in. OD for all

residential applications including long line.

IMPORTANT

: Always install the factory--supplied liquid--line

filter drier. Obtain replacement filter driers from your distributor
or branch.

INSTALLATION RECOMMENDATIONS

NOTE

: In some cases noise in the living area has been traced

to gas pulsations from improper installation of equipment.

1. Locate unit away from windows, patios, decks, etc. where

unit operation sound may disturb customer.

2. Ensure that vapor and liquid tube diameters are appropri-

ate for unit capacity.

3. Run refrigerant tubes as directly as possible by avoiding

unnecessary turns and bends.

4. Leave some slack between structure and unit to absorb vi-

bration.

5. When passing refrigerant tubes through the wall, seal

opening with RTV or other pliable silicon--based caulk.
(See Fig. 1.)

6. Avoid direct tubing contact with water pipes, duct work,

floor joists, wall studs, floors, and walls.

7. Do not suspend refrigerant tubing from joists and studs

with a rigid wire or strap which comes in direct contact
with tubing. (See Fig. 1.)

8. Ensure that tubing insulation is pliable and completely

surrounds vapor tube.

9. When necessary, use hanger straps which are 1 in. (25.4

mm) wide and conform to shape of tubing insulation. (See

Fig. 1.)

10. Isolate hanger straps from insulation by using metal

sleeves bent to conform to shape of insulation.

INSULATION

VAPOR TUBE

LIQUID TUBE

OUTDOOR WALL

INDOOR WALL

LIQUID TUBE

VAPOR TUBE

INSULATION

CAULK

Avoid contact between tubing and structure

NOTE:

THROUGH THE WALL

HANGER STRAP

(AROUND VAPOR

TUBE ONLY)

JOIST

1

 (25.4 mm)MIN.

SUSPENSION

A94028

Fig. 1

---

Connecting Tubing Installation

When outdoor unit is connected to factory--approved indoor unit,

outdoor unit contains system refrigerant charge for operation with
ARI rated indoor unit when connected by 15 ft/4.57 m. of

field--supplied or factory accessory tubing. For proper unit
operation, check refrigerant charge using charging information

located on control box cover and/or in the Check Charge section

of this instruction.

Содержание 264A

Страница 1: ...than 1 disconnect switch Lock out and tag switch with a suitable warning label IMPORTANT Maximum liquid line size is 3 8 in OD for all residential applications including long line IMPORTANT Always in...

Страница 2: ...B C 29 1 2 X 33 749 3 X 838 2 10 1 16 255 6 5 5 8 142 9 23 3 4 603 3 36 1 2 X 40 927 1 X 1016 9 5 8 244 5 6 13 16 173 0 28 3 4 730 3 A05177 Fig 2 Tiedown Knockout Requirements On rooftop applications...

Страница 3: ...mended No Recommended For tubing line sets between 80 and 200 ft 24 38 and 60 96 m and or 20 ft 6 09 m vertical differential refer to Residential Split System Longline Application Guideline Table 2 Re...

Страница 4: ...esult in equipment damage or improper operation Installation of filter drier in liquid line is required Install Liquid Line Filter Drier Indoor Refer to Fig 4 and install filter drier as follows 1 Bra...

Страница 5: ...ELD POWER WIRING A91056 Fig 6 Line Connections Connect Control Wiring Route 24v control wires through control wiring grommet and connect leads to control wiring See Thermostat Installation Instruction...

Страница 6: ...l regulations require that you do not vent refrigerant to the atmosphere Recover during system repair or final unit disposal Follow these steps to properly start up system 1 After system is evacuated...

Страница 7: ...wer will run an additional 90 seconds to increase system efficiency Heating On a call for heating a standard thermostat non communicating makes circuits R Y and R G Circuit R Y energizes contactor sta...

Страница 8: ...ed with a non communicating thermostat the utility relay should be wired between R and Y Low Ambient Cooling When this unit is operating below 55_F 12 78_C outdoor temperature provisions must be made...

Страница 9: ...emperature do not meet the above requirements an abbreviated 30 second de frost will occur QUIET SHIFT This feature must be enabled by selecting the 3rd position of the 3 position dip switch for a non...

Страница 10: ...control will energize the compressor contactor every 15 minutes If the thermal protector closes at the next 15 minute interval check the unit will resume operation If the thermal cutout trips for thr...

Страница 11: ...flow Control Fault 45 Outdoor unit control board has failed Control board needs to be replaced Brown Out 24 v 46 The control voltage is less than 15 5v for at least 4 seconds Com pressor and fan oper...

Страница 12: ...perating S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detec...

Отзывы: