ACCESSORY USAGE GUIDELINE

Accessory

REQUIRED FOR LOW---AMBIENT

COOLING APPLICATIONS

(Below 55

°

F / 12.8

°

C)

REQUIRED FOR

LONG LINE APPLICATIONS*

(Over 80 ft. / 24.38 m)

REQUIRED FOR

SEA COAST APPLICATIONS

(Within 2 miles / 3.22 km)

Accumulator

Standard

Standard

Standard

Ball Bearing Fan Motor

Yes

{

No

No

Compressor Start Assist Capacitor and

Relay

Yes

Yes

No

Crankcase Heater

Yes

Yes

No

Evaporator Freeze Thermostat

Yes

No

No

Hard Shutoff TXV

Yes

Yes

Yes

Isolation Relay

Yes

No

No

Liquid Line Solenoid Valve

No

See Long---Line Application

Guideline

No

Motor Master

®

Control or

Low Ambient Switch

Yes

No

No

Support Feet

Recommended

No

Recommended

* For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. (6.09 m) vertical differential, refer to Residential Split---System Longline

Application Guideline.

{

Additional requirement for Low---Ambient Controller (full modulation feature) MotorMaster

r

Control.

Accessory Description and Usage (Listed Alphabetically)

1. Ball--Bearing Fan Motor

A fan motor with ball bearings which permits speed reduction

while maintaining bearing lubrication.

Usage Guideline:

Required on all units when using MotorMaster

r

2. Compressor Start Assist -- Capacitor and Relay

Start capacitor and relay gives a ”hard” boost to compressor

motor at each start up.

Usage Guideline:

Required for reciprocating compressors in the

following applications:

Long line
Low ambient cooling
Hard shut off expansion valve on indoor coil
Liquid line solenoid on indoor coil

Required for single--phase scroll compressors in the
following applications:

Long line
Low ambient cooling

Suggested for all compressors in areas with a history of
low voltage problems.

3. Compressor Start Assist — PTC Type

Solid state electrical device which gives a ”soft” boost to the
compressor at each start--up.

Usage Guideline:

Suggested in installations with marginal power supply.

4. Crankcase Heater

An electric resistance heater which mounts to the base of the
compressor to keep the lubricant warm during off cycles.

Improves compressor lubrication on restart and minimizes the
chance of liquid slugging.

Usage Guideline:

Required in low ambient cooling applications.
Required in long line applications.
Suggested in all commercial applications.

5. Evaporator Freeze Thermostat

An SPST temperature--actuated switch that stops unit operation
when evaporator reaches freeze--up conditions.

Usage Guideline:

Required when low ambient kit has been added.

6. Isolation Relay

An SPDT relay which switches the low--ambient controller out of

the outdoor fan motor circuit when the heat pump switches to
heating mode.

Usage Guideline:

Required in all heat pumps where low ambient kit has
been added.

7. Liquid--Line Solenoid Valve (LLS)

An electrically operated shutoff valve which stops and starts

refrigerant liquid flow in response to compressor operation. It is

to be installed at the outdoor unit to control refrigerant off cycle
migration in the heating mode.

Usage Guideline:

An LLS is required in all long line heat pump

applications to control refrigerant off cycle migration in

the heating mode. See Long Line Guideline.

8. Low--Ambient Pressure Switch Kit

A long life pressure switch which is mounted to outdoor unit
service valve. It is designed to cycle the outdoor fan motor in

order to maintain head pressure within normal operating limits.
The control will maintain working head pressure at low--ambient

temperatures down to 0

_

F (--17.8

_

C)when properly installed.

Usage Guideline:

A Low--Ambient Pressure Switch or MotorMaster

r

Low--Ambient Controller must be used when cooling
operation is used at outdoor temperatures below 55

_

F

(12.8

_

C).

9. MotorMaster

r

Low--Ambient Controller

A fan--speed control device activated by a temperature sensor,

designed to control condenser fan motor speed in response to the
saturated, condensing temperature during operation in cooling

mode only. For outdoor temperatures down to --20

_

F (--28.9

_

C),

it maintains condensing temperature at 100

_

F

±

10

_

F (37.8

_

C

±

6.5

_

C).

Usage Guideline:

A MotorMaster

r

Low Ambient Controller or

Low--Ambient Pressure Switch must be used when
cooling operation is used at outdoor temperatures

below 55

_

F (12.8

_

C).

Suggested for all commercial applications.

223A

Содержание 225A

Страница 1: ...o date ratings information INDUSTRY LEADING FEATURES BENEFITS Efficiency S 15 SEER 11 2 13 0 EER 7 7 8 8 HSPF Nominal S Microtube Technologyt refrigeration system S Indoor air quality accessories available Sound S Sound level as low as 70 dBA Comfort S System supports Thermidistatt or standard thermostat controls Reliability S Puronr refrigerant environmentally sound won t deplete the ozone layer ...

Страница 2: ...w are critical to achieve rated capacity and efficiency Installation of this product should follow all manufacturing refrigerant charging and air flow instructions Failure to confirm proper charge and air flow may reduce energy efficiency and shorten equipment life STANDARD FEATURES Feature 18 24 30 36 42 48 60 Puron Refrigerant X X X X X X X 15 SEER X X X X X X X Scroll Compressor X X X X X X X L...

Страница 3: ...ximum allowable total equivalent length is up to 250 ft 76 2 m The maximum vertical separation is 200 ft 60 96 m when outdoor unit is above indoor unit and up to 80 ft 24 38 m when the outdoor unit is below the indoor unit Refer to Accessory Usage Guideline below for required accessories See Longline Application Guideline for required piping and system modifications Also refer to the table below f...

Страница 4: ...cludes Outdoor Air Temperature Sensor TSTATBBPHH01 B HybridHeatt Dual Fuel Thermostat Auto Changeover 7 Day Programmable F C Includes Outdoor Sensor TSTATXXSEN01 B TSTATBBPHP01 B Thermostat Auto Changeover 7 Day Programmable F C 2 Stage Heat 1 Stage Cool TSTATBBNHP01 C Thermostat Auto Changeover Non Programmable F C 2 Stage Heat 1 Stage Cool TSTATBBSHP01 Standard Programmable Thermostat Manual Cha...

Страница 5: ...ff cycles Improves compressor lubrication on restart and minimizes the chance of liquid slugging Usage Guideline Required in low ambient cooling applications Required in long line applications Suggested in all commercial applications 5 Evaporator Freeze Thermostat An SPST temperature actuated switch that stops unit operation when evaporator reaches freeze up conditions Usage Guideline Required whe...

Страница 6: ...to allow for drainage from unit base Usage Guideline Suggested in the following applications Heat pump installations in heavy snowfall areas Heat pump installations in snow drift locations Heat pump installations in areas of prolonged subfreezing temperatures All commercial installations 14 Sound Hood Wraparound sound reducing cover for the compressor Reduces the sound level by about 2 dBA Usage G...

Страница 7: ...able tables of the NEC ANSI NFPA 70 Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2 Time Delay fuse FLA Full Load Amps LRA Locked Rotor Amps MCA Minimum Circuit Amps RLA Rated Load Amps NOTE Control circuit is 24 V on all units and requires external power source Copper wire must be used from service disconnect to unit All motors com...

Страница 8: ...8 DIMENSIONS ENGLISH 225A ...

Страница 9: ...9 DIMENSIONS SI 225A ...

Страница 10: ...ANA060 FX4CN B F 060 225ANA048 FX4CN B F 060 225ANA042 FX4CN B F 048 225ANA036 FX4CN B F 042 225ANA030 FX4CN B F 036 225ANA024 FX4CNF030 225ANA018 FX4CNF018 BASED ON INDOOR ENT AIR AT 70ºF 21ºC AND AT RATED CFM 10 23 0 17 78 10 12 22 20 6 67 30 1 11 40 4 44 50 10 60 15 56 70 21 11 80 26 67 OUTDOOR TEMPERATURE ºF ºC 225A ...

Страница 11: ...arious examples Wall Wall Wall Wall 24 Service 6 152 4 mm 24 609 6 Service 24 609 6 Service 24 609 6 Service 24 609 6 Service 24 609 6 24 609 6 24 609 6 12 304 8 12 304 8 12 304 8 12 304 8 6 152 4 Note Numbers in mm A07833 225A ...

Страница 12: ...00 3 52 7 7 10100 2 32 3106440 225ANA018 B CSPH 2412A 353AAV036040 17700 12 0 15 0 17700 3 68 8 2 10200 2 38 3106441 225ANA018 B CSPH 2412A 353AAV036060 17500 12 0 15 0 17400 3 56 7 8 10100 2 32 3032807 225ANA018 B CSPH 2412A 355 A C AV042040 17400 11 7 14 8 17400 3 50 7 7 10100 2 30 3032808 225ANA018 B CSPH 2412A 355 A C AV042060 17400 11 7 14 8 17500 3 52 7 7 10100 2 30 3032809 225ANA018 B CSPH ...

Страница 13: ...4400 2 60 3032841 225ANA024 B CNPV 3014A TDR 23400 11 2 13 5 24000 3 60 8 4 15300 2 52 3032845 225ANA024 B CNPV 3017A 315 A J AV048090 23400 12 8 15 5 23600 3 72 8 5 14400 2 64 3106451 225ANA024 B CNPV 3017A 353AAV036040 23800 12 5 15 5 23600 3 86 8 8 14600 2 70 3106452 225ANA024 B CNPV 3017A 353AAV036060 24000 12 5 15 5 23600 3 86 8 8 14700 2 72 3106453 225ANA024 B CNPV 3017A 353AAV036080 23800 1...

Страница 14: ... 3 64 8 3 17400 2 50 3032948 225ANA030 B CNPH 3017A 315 A J AV036070 28800 12 5 15 5 29000 3 58 8 3 17300 2 48 3032949 225ANA030 B CNPH 3017A 315 A J AV048090 28800 13 0 15 5 29000 3 62 8 3 17200 2 50 3032950 225ANA030 B CNPH 3017A 315 A J AV060110 28800 13 0 15 5 29000 3 62 8 3 17200 2 50 3032951 225ANA030 B CNPH 3017A 315 A J AV066135 28800 13 0 15 5 29000 3 64 8 4 17200 2 50 3032952 225ANA030 B...

Страница 15: ...42 3033013 225ANA030 B CSPH 3612A 313 AV048070 29600 12 5 15 5 29800 3 76 8 5 17600 2 54 3033014 225ANA030 B CSPH 3612A 313 AV048090 29600 13 0 15 5 29600 3 82 8 6 17500 2 58 3032985 225ANA030 B CSPH 3612A 315 A J AV036070 29200 13 0 15 5 29400 3 72 8 4 17400 2 54 3032986 225ANA030 B CSPH 3612A 315 A J AV048090 29400 13 0 16 0 29200 3 74 8 4 17300 2 56 3032987 225ANA030 B CSPH 3612A 315 A J AV0601...

Страница 16: ...15 0 35000 3 54 8 2 21000 2 50 3033079 225ANA036 B CNPH 3617A 355 A C AV042080 34000 12 0 14 5 35200 3 50 8 0 21000 2 48 3033080 225ANA036 B CNPH 3617A 355 A C AV060080 34000 12 5 14 5 35000 3 54 8 2 21000 2 50 3033081 225ANA036 B CNPH 3617A 355 A C AV060100 34200 12 5 15 0 35000 3 54 8 2 21000 2 50 3033082 225ANA036 B CNPH 3617A 355 A C AV060120 34000 12 5 15 0 35000 3 54 8 2 20800 2 50 3033076 2...

Страница 17: ...SPH 3612A 355 A C AV060120 35000 13 0 15 5 35400 3 70 8 2 21000 2 58 3033101 225ANA036 B CSPH 3612A TDR 35200 12 0 14 0 36000 3 70 8 2 22200 2 52 3033039 225ANA036 B CSPH 4212A 313 AV024045 35200 12 0 14 5 36000 3 72 8 4 21600 2 54 3033040 225ANA036 B CSPH 4212A 313 AV048070 35200 12 5 15 0 36000 3 76 8 5 21400 2 58 3033041 225ANA036 B CSPH 4212A 313 AV048090 35600 13 0 15 5 35800 3 84 8 6 21200 2...

Страница 18: ...3 64 8 2 25200 2 62 3033215 225ANA042 B CNPH 4221A 315 A J AV066155 41500 12 5 15 0 41000 3 62 8 2 25200 2 62 3106553 225ANA042 B CNPH 4221A 353AAV036040 41500 12 0 14 5 42000 3 58 8 3 25800 2 58 3106554 225ANA042 B CNPH 4221A 353AAV036060 41500 12 0 14 5 42000 3 58 8 3 25800 2 56 3106555 225ANA042 B CNPH 4221A 353AAV036080 41500 12 0 14 5 42000 3 58 8 3 25800 2 58 3106556 225ANA042 B CNPH 4221A 3...

Страница 19: ...15 0 42000 3 70 8 2 25600 2 64 3106565 225ANA042 B CSPH 4212A 353AAV036040 42000 12 5 15 0 42000 3 72 8 6 26000 2 62 3106566 225ANA042 B CSPH 4212A 353AAV036060 42000 12 5 15 0 42000 3 70 8 5 26000 2 62 3106567 225ANA042 B CSPH 4212A 353AAV036080 42000 12 5 15 0 42000 3 70 8 5 26000 2 62 3106568 225ANA042 B CSPH 4212A 353AAV048080 42000 12 5 15 0 42000 3 68 8 5 25800 2 62 3106569 225ANA042 B CSPH ...

Страница 20: ...600 2 52 3033300 225ANA048 B CNPH 4821A 315 A J AV066155 46500 12 5 15 0 45000 3 60 8 2 28400 2 54 3106591 225ANA048 B CNPH 4821A 353AAV048080 46500 11 5 14 0 45500 3 56 8 2 29000 2 50 3106592 225ANA048 B CNPH 4821A 353AAV060100 46500 12 0 14 5 45000 3 60 8 2 28600 2 54 3106593 225ANA048 B CNPH 4821A 353AAV060120 46500 12 0 14 5 45000 3 62 8 2 28600 2 54 3033294 225ANA048 B CNPH 4821A 355 A C AV06...

Страница 21: ...60 B CAP 6021A TDR 56500 11 2 13 5 57500 3 64 8 3 35800 2 56 3033377 225ANA060 B CAP 6024A 313 AV060135 56500 11 5 14 0 57000 3 62 8 4 35400 2 58 3033359 225ANA060 B CAP 6024A 315 A J AV066135 56500 11 5 14 0 57000 3 66 8 3 35400 2 60 3033360 225ANA060 B CAP 6024A 315 A J AV066155 57000 12 0 14 0 57000 3 70 8 4 35200 2 62 3106604 225ANA060 B CAP 6024A 353AAV060120 56500 11 8 14 0 56500 3 66 8 5 35...

Страница 22: ... 64 1 14 18 74 14 22 1 30 17 67 13 79 1 49 16 65 13 38 1 70 15 78 13 03 1 90 15 10 12 76 2 05 63 17 2 18 30 14 08 1 15 17 31 13 64 1 32 16 31 13 21 1 51 15 34 12 79 1 72 14 53 12 44 1 91 13 89 12 16 2 05 62 16 7 18 05 17 89 1 15 17 20 17 20 1 32 16 39 16 39 1 51 15 61 15 61 1 71 14 94 14 94 1 91 14 41 14 41 2 05 57 13 9 17 99 17 99 1 15 17 20 17 20 1 32 16 39 16 39 1 51 15 61 15 61 1 71 14 94 14 9...

Страница 23: ...0 98 315 A J AV036070 CNPH 2417A 0 97 1 01 315 A J AV036070 CNPH 3017A 0 98 0 98 315 A J AV036070 CNPV 2414A 0 97 1 01 315 A J AV036070 CNPV 3014A 0 98 0 98 315 A J AV036070 CSPH 2412A 0 98 0 98 315 A J AV036070 CSPH 3012A 0 99 0 99 315 A J AV036070 CAP 2417A 0 97 0 97 315 A J AV048090 CAP 3017A 0 99 0 97 315 A J AV048090 CNPH 2417A 0 97 0 97 315 A J AV048090 COOLING INDOOR MODEL CAPACITY POWER FU...

Страница 24: ...120 CSPH 3012A 0 99 0 99 355 A C AV060120 CAP 2414A 0 98 1 02 313 AV024045 CAP 3014A 0 99 0 99 313 AV024045 CNPH 2417A 0 97 1 02 313 AV024045 CNPH 3017A 1 00 1 00 313 AV024045 CNPV 2414A 0 97 1 02 313 AV024045 CNPV 3014A 0 99 0 99 313 AV024045 CSPH 2412A 0 98 0 98 313 AV024045 CSPH 3012A 1 00 1 00 313 AV024045 See note on pg 26 225A ...

Страница 25: ...NPV 3621A 0 99 1 07 CSPH 3012A 0 99 1 08 CSPH 3612A 1 01 1 08 CAP 3014A 0 98 0 98 315 A J AV036070 CAP 3614A 0 99 0 99 315 A J AV036070 CNPH 3017A 0 99 0 99 315 A J AV036070 CNPH 3617A 0 99 0 96 315 A J AV036070 CNPV 3014A 0 98 0 98 315 A J AV036070 CSPH 3012A 0 99 0 99 315 A J AV036070 CSPH 3612A 1 00 0 96 315 A J AV036070 CAP 3017A 0 99 0 95 315 A J AV048090 COOLING INDOOR MODEL CAPACITY POWER F...

Страница 26: ...100 CNPH 3617A 0 99 0 96 355 A C AV060100 CNPV 3621A 0 99 0 96 355 A C AV060100 CSPH 3012A 0 99 0 96 355 A C AV060100 CSPH 3612A 1 01 0 97 355 A C AV060100 CNPH 3017A 0 99 0 95 355 A C AV060120 CNPH 3617A 0 99 0 95 355 A C AV060120 CSPH 3012A 0 99 0 95 355 A C AV060120 CSPH 3612A 1 00 0 96 355 A C AV060120 CAP 3017A 0 97 0 97 313 AV048070 CAP 3617A 0 99 0 99 313 AV048070 CNPH 3017A 0 99 0 99 313 A...

Страница 27: ... 3621A 0 97 1 10 CNPV 4217A 0 99 1 09 CNPV 4221A 0 98 1 09 CSPH 3612A 0 99 1 05 CSPH 4212A 1 00 1 06 CAP 3614A 0 96 1 02 315 A J AV036070 CNPH 3617A 0 96 1 02 315 A J AV036070 CNPH 4221A 0 98 0 99 315 A J AV036070 CSPH 3612A 0 98 1 00 315 A J AV036070 CSPH 4212A 0 99 1 00 315 A J AV036070 CAP 3617A 0 97 0 97 315 A J AV048090 CNPH 3617A 0 97 0 97 315 A J AV048090 COOLING INDOOR MODEL CAPACITY POWER...

Страница 28: ... 98 0 95 355 A C AV060100 CSPH 3612A 0 99 1 00 355 A C AV060100 CSPH 4212A 0 99 0 97 355 A C AV060100 CAP 4224A 0 97 0 97 355 A C AV060120 CNPH 3617A 0 96 0 98 355 A C AV060120 CNPH 4221A 0 98 0 95 355 A C AV060120 CSPH 3612A 0 99 0 97 355 A C AV060120 CSPH 4212A 0 99 0 97 355 A C AV060120 CAP 3614A 0 96 1 06 313 AV024045 CNPH 3617A 0 96 1 06 313 AV024045 CNPH 4221A 0 97 1 07 313 AV024045 CSPH 361...

Страница 29: ... 13 CSPH 4812A 1 00 1 13 CNPH 4221A 0 99 1 07 315 A J AV036070 CNPH 4821A 1 00 1 08 315 A J AV036070 CSPH 4212A 1 00 1 08 315 A J AV036070 CSPH 4812A 1 00 1 08 315 A J AV036070 CAP 4817A 1 00 1 04 315 A J AV048090 CNPH 4221A 0 99 1 03 315 A J AV048090 CNPH 4821A 1 00 1 04 315 A J AV048090 CNPV 4217A 1 00 1 08 315 A J AV048090 CSPH 4212A 1 00 1 04 315 A J AV048090 CSPH 4812A 1 00 1 04 315 A J AV048...

Страница 30: ...A 0 99 1 03 355 A C AV060100 CNPV 4821A 1 00 1 04 355 A C AV060100 CSPH 4212A 1 00 1 04 355 A C AV060100 CSPH 4812A 1 00 1 04 355 A C AV060100 CAP 4224A 0 98 1 06 355 A C AV060120 CAP 4824A 1 00 1 04 355 A C AV060120 CNPH 4221A 0 99 1 03 355 A C AV060120 CNPH 4821A 1 00 1 04 355 A C AV060120 CNPV 4824A 1 00 1 04 355 A C AV060120 CSPH 4212A 1 00 1 04 355 A C AV060120 CSPH 4812A 1 00 1 04 355 A C AV...

Страница 31: ...0 98 1 02 315 A J AV048090 CSPH 4812A 0 97 1 01 315 A J AV048090 CSPH 6012A 0 99 1 03 315 A J AV048090 CAP 4821A 0 96 1 00 315 A J AV060110 CAP 6021A 0 99 0 99 315 A J AV060110 CNPH 4821A 0 96 1 00 315 A J AV060110 CNPH 6024A 0 98 0 98 315 A J AV060110 CNPV 4821A 0 96 1 00 315 A J AV060110 CSPH 4812A 0 97 1 01 315 A J AV060110 CSPH 6012A 0 99 0 99 315 A J AV060110 CAP 4824A 0 96 1 00 315 A J AV066...

Страница 32: ...V 4821A 0 97 1 01 313 AV060110 CSPH 4812A 0 97 1 01 313 AV060110 CSPH 6012A 0 99 0 99 313 AV060110 CAP 4824A 0 97 1 01 313 AV060135 CAP 6024A 0 99 1 03 313 AV060135 CNPH 4821A 0 97 1 01 313 AV060135 CNPH 6024A 0 99 0 99 313 AV060135 CNPV 4824A 0 97 1 01 313 AV060135 CNPV 6024A 0 99 0 99 313 AV060135 CSPH 4812A 0 97 1 01 313 AV060135 CSPH 6012A 0 99 0 99 313 AV060135 See note on pg 26 225A ...

Страница 33: ... 80 5 35 48 70 48 70 5 89 45 32 45 32 6 47 57 13 9 59 79 59 79 3 99 57 30 57 30 4 40 54 64 54 64 4 85 51 80 51 80 5 35 48 71 48 71 5 89 45 32 45 32 6 47 COOLING INDOOR MODEL CAPACITY POWER FURNACE MODEL FX4CN B F 060 1 00 1 00 FE4ANB006 1 00 1 00 FV4BNB006 1 00 1 00 FY4ANB060 0 99 1 06 CAP 6021A 0 98 1 05 CAP 6024A 0 98 1 05 CNPH 6024A 0 98 1 05 CNPV 6024A 0 98 1 05 CSPH 6012A 0 99 1 06 CAP 6021A ...

Страница 34: ...1 18 7 70 7 07 1 23 9 77 8 91 1 29 12 01 10 66 1 35 14 50 13 20 1 42 17 32 17 32 1 51 20 39 20 39 1 61 23 82 23 82 1 74 675 5 83 5 36 1 18 7 81 7 18 1 23 9 91 9 03 1 28 12 16 10 80 1 33 14 72 13 39 1 40 17 57 17 57 1 48 20 69 20 69 1 58 24 18 24 18 1 70 HEATING INDOOR MODEL CAPACITY POWER FURNACE MODEL FX4CNF018 1 00 1 00 FE4ANF002 0 99 0 97 FF1ENP018 1 02 1 08 FF1ENP024 1 02 1 06 FV4BNF002 0 99 0...

Страница 35: ... 04 315 A J AV048090 CNPH 3017A 0 98 1 02 315 A J AV048090 CNPV 2417A 1 00 1 04 315 A J AV048090 CNPV 3017A 0 98 1 02 315 A J AV048090 CSPH 2412A 1 00 1 03 315 A J AV048090 CSPH 3012A 0 98 1 02 315 A J AV048090 CNPH 2417A 1 00 1 04 315 A J AV060110 HEATING INDOOR MODEL CAPACITY POWER FURNACE MODEL CNPH 3017A 0 98 1 02 315 A J AV060110 CSPH 2412A 1 00 1 03 315 A J AV060110 CSPH 3012A 0 98 1 03 315 ...

Страница 36: ...48090 CNPV 3617A 0 97 0 99 315 A J AV048090 CSPH 3012A 0 97 0 99 315 A J AV048090 HEATING INDOOR MODEL CAPACITY POWER FURNACE MODEL CSPH 3612A 0 97 0 96 315 A J AV048090 CAP 3621A 0 97 0 98 315 A J AV060110 CNPH 3017A 0 97 0 99 315 A J AV060110 CNPH 3617A 0 97 0 99 315 A J AV060110 CNPV 3621A 0 97 0 99 315 A J AV060110 CSPH 3012A 0 97 0 99 315 A J AV060110 CSPH 3612A 0 98 0 97 315 A J AV060110 CNP...

Страница 37: ...99 313 AV048070 CNPH 3017A 0 98 1 00 313 AV048070 CNPH 3617A 0 98 1 00 313 AV048070 CNPV 3017A 0 98 1 00 313 AV048070 CNPV 3617A 0 98 1 00 313 AV048070 CSPH 3012A 0 98 1 01 313 AV048070 CSPH 3612A 0 99 0 98 313 AV048070 CAP 3621A 0 98 0 97 313 AV048090 CNPH 3017A 0 97 0 99 313 AV048090 CNPH 3617A 0 97 0 99 313 AV048090 CNPV 3621A 0 97 0 99 313 AV048090 CSPH 3012A 0 97 0 99 313 AV048090 CSPH 3612A ...

Страница 38: ...J AV048090 CSPH 4212A 0 98 0 99 315 A J AV048090 CAP 3621A 0 97 1 02 315 A J AV060110 HEATING INDOOR MODEL CAPACITY POWER FURNACE MODEL CAP 4221A 0 98 1 01 315 A J AV060110 CNPH 3617A 0 97 1 03 315 A J AV060110 CNPH 4221A 0 97 0 99 315 A J AV060110 CNPV 3621A 0 97 1 03 315 A J AV060110 CNPV 4221A 0 97 0 99 315 A J AV060110 CSPH 3612A 0 98 1 00 315 A J AV060110 CSPH 4212A 0 99 0 99 315 A J AV060110...

Страница 39: ...7A 0 99 1 07 313 AV024045 CNPH 4221A 0 99 1 05 313 AV024045 CSPH 3612A 1 00 1 03 313 AV024045 CSPH 4212A 1 00 1 02 313 AV024045 CAP 3617A 0 98 1 04 313 AV048070 CNPH 3617A 0 98 1 06 313 AV048070 CNPH 4221A 0 99 1 03 313 AV048070 CNPV 3617A 0 98 1 06 313 AV048070 CNPV 4217A 0 99 1 02 313 AV048070 CSPH 3612A 0 99 1 02 313 AV048070 CSPH 4212A 1 00 1 01 313 AV048070 CAP 3621A 0 98 1 01 313 AV048090 CA...

Страница 40: ...J AV060110 CNPH 4821A 1 00 1 04 315 A J AV060110 CNPV 4221A 0 99 1 05 315 A J AV060110 CNPV 4821A 1 00 1 04 315 A J AV060110 HEATING INDOOR MODEL CAPACITY POWER FURNACE MODEL CSPH 4212A 1 00 1 04 315 A J AV060110 CSPH 4812A 1 00 1 04 315 A J AV060110 CAP 4224A 0 99 1 06 315 A J AV066135 CAP 4824A 1 00 1 04 315 A J AV066135 CNPH 4221A 0 98 1 03 315 A J AV066135 CNPH 4821A 1 00 1 03 315 A J AV066135...

Страница 41: ...SPH 4212A 1 00 1 05 355 A C AV060120 CSPH 4812A 1 00 1 04 355 A C AV060120 CAP 4817A 1 00 1 05 313 AV048070 CNPH 4221A 1 00 1 10 313 AV048070 CNPH 4821A 1 00 1 05 313 AV048070 CNPV 4217A 1 00 1 08 313 AV048070 CSPH 4212A 1 00 1 06 313 AV048070 CSPH 4812A 1 00 1 05 313 AV048070 CAP 4221A 0 99 1 06 313 AV048090 CAP 4821A 1 00 1 03 313 AV048090 CNPH 4221A 0 99 1 06 313 AV048090 CNPH 4821A 1 00 1 03 3...

Страница 42: ...AV060110 CAP 4824A 0 97 1 05 315 A J AV066135 CAP 6024A 0 97 1 03 315 A J AV066135 CNPH 4821A 0 97 1 05 315 A J AV066135 CNPH 6024A 0 97 1 03 315 A J AV066135 CNPV 4824A 0 97 1 05 315 A J AV066135 CNPV 6024A 0 97 1 03 315 A J AV066135 CSPH 4812A 0 97 1 04 315 A J AV066135 HEATING INDOOR MODEL CAPACITY POWER FURNACE MODEL CSPH 6012A 0 97 1 02 315 A J AV066135 CAP 4824A 0 97 1 04 315 A J AV066155 CA...

Страница 43: ...4 56 84 4 46 66 32 66 32 4 65 75 63 75 63 4 90 HEATING INDOOR MODEL CAPACITY POWER FURNACE MODEL FX4CN B F 060 1 00 1 00 FE4ANB006 1 00 1 00 FV4BNB006 1 00 1 00 FY4ANB060 1 02 1 07 CAP 6021A 1 01 1 06 CAP 6024A 1 01 1 06 CNPH 6024A 1 01 1 07 CNPV 6024A 1 01 1 07 CSPH 6012A 1 01 1 05 CAP 6021A 1 00 1 05 315 A J AV060110 CNPH 6024A 1 00 1 06 315 A J AV060110 CSPH 6012A 1 01 1 05 315 A J AV060110 CAP...

Страница 44: ...n resistant Fan blades will be statically and dynamically balanced Condenser fan openings will be equipped with steel wire safety guards Compressor Compressor will be hermetically sealed Compressor will be mounted on rubber vibration isolators Condenser Coil Condenser coil will be air cooled Coil will be constructed of aluminum fins mechanically bonded to copper tubes which are then cleaned dehydr...

Отзывы: