Page 72
Bradford White Corp.
Fig. 95 – Lead Lag Central Heat Configuration
3. Change the 4 mA water temperature to match
the lowest water temperature setting on the
Building Automation System or multiple
boiler control.
4. Change the 20mA water temperature to match
the highest water temperature setting on the
Building Automation System or Multiple
boiler control.
Note - Bradford White offers “gateways” to
allow connections to BACnet, LON, and other
communications protocols. See Section 9.6.
Job n - Building automation or multiple
Boiler 4-20 ma modulation Control
(This is an individual function – do this on each of the controls.)
In this type of installation, the fan speed of each
boiler is changed or modulated by a source outside
of the boiler. All active burners must operate at the
same modulation rate while operating. The system
will not operate correctly if some of the burners
are being asked to operate at full rate while other
burners are operating at minimum rates.
Note - The system can also operate using 0 - 10V
dc using a converter (Bradford White part number
CA006100.)
1. On each controller in the system, check
terminals 5 and 6 on TB7 to ensure that the
System sensor is not connected. (For this type
of operation, the Lead/Lag system is disabled.)
2. Connect the 4-20 mA input to each controller
in the system.
• On the Primary controller in each boiler,
connect to terminals 3 and 4 on TB7.
• On the Secondary controller in each boiler,
connect to terminals 7 and 8 on TB7.
3. Enable a central heat call for each control
on the system. This function must be set up
for each controller separately. This function
operates outside of the Lead/Lag system.
How to get there – Central Heat Enable
Home Page <Press the icon for one of the controllers>
Brute Elite Primary Screen <Press Configure button>
Primary Configuration Menu <Select line - CH Central
Heat Configuration>
4. Fig. 96 shows the setup screen.
Fig. 96 - Central Heat Configuration
5. Enable the Central Heat function on the top
line. Give the CH function the priority using
the lower line.
Note - Bradford White offers “gateways” to
allow connections to BACnet, LON, and other
communications protocols. See Section 9.6.
Job o – Combustion Setup Procedure
(These are individual functions. Do the combustion setup for
each of the burners.)
In this section, we will explain how to set up the gas
valve so both burners in each boiler run efficiently
at both the High Fire and Low Fire conditions. As
we said, a boiler includes two controllers (Primary
and Secondary), which control two burners (Primary
and Secondary). See Fig. 97. Each burner has
a separate gas valve, and each of these must be
set up separately. Here’s a quick summary of the
procedure:
•
You shut off one controller/burner
combination, and work with the other.
•
You set the working burner to run at High Fire,
and adjust the gas valve to get the correct CO
2
reading.
•
Next you set the same burner to run at Low
Fire, and make another adjustment on the gas
valve to get the desired CO
2
reading.
•
When you are through, you shut off the
controller/burner you have been working with,
turn on the other controller/burner, and make
the same adjustments there.
Содержание BNTH1000
Страница 2: ...Bradford White Corp...
Страница 12: ...Page 8 Bradford White Corp Fig 6 Dimensions BNT 1700...
Страница 38: ...Page 34 Bradford White Corp Fig 21 Ladder Diagram...
Страница 39: ...Page 35 Brute Elite Boilers and Water Heaters Fig 22 Wiring Diagram...
Страница 40: ...Page 36 Bradford White Corp...
Страница 52: ...Page 48 Bradford White Corp Fig 51 Connection Terminals...
Страница 129: ...Page 125 Brute Elite Boilers and Water Heaters Fig 140 Machine Frame BNT1000 13 3 PARTS ILLUSTRATIONS...
Страница 130: ...Page 126 Bradford White Corp Fig 141 Rear Panel BNT1000 Fig 142 Rear Panel BNT1700...
Страница 131: ...Page 127 Brute Elite Boilers and Water Heaters Fig 143 Machine Frame BNT1700...
Страница 132: ...Page 128 Bradford White Corp Fig 144 Front Panels and Covers BNT1000 and BNT1700...
Страница 133: ...Page 129 Brute Elite Boilers and Water Heaters Fig 145 Burners and Combustion Chamber BNT1000...
Страница 134: ...Page 130 Bradford White Corp Fig 146 Burners and Combustion Chamber BNT1700...
Страница 136: ...Page 132 Bradford White Corp Fig 149 Burner Detail BNT1700...
Страница 137: ...Page 133 Brute Elite Boilers and Water Heaters Fig 150 Electronic Components Fig 151 Condensate Trap BNT1000...
Страница 138: ...Page 134 Bradford White Corp Fig 152 Condensate Trap BNT1700 Fig 153 Flow Switch BNT1000 and BNT1700...
Страница 139: ...Page 135 Brute Elite Boilers and Water Heaters This page intentionally left blank...
Страница 140: ...Page 136 Bradford White Corp This page intentionally left blank...