Page 71
Brute Elite Boilers and Water Heaters
When Outdoor Reset is enabled, and the outdoor
temperature falls between the maximum and
minimum outdoor temperatures (70° and 32° in
the example above), the setpoint will be adjusted
down by about 1° for every 2° increase in the
outdoor temperature. For example, if the outdoor
temperature rises by 10°, the Outdoor Reset function
will adjust the setpoint down by about 5°. (This
ratio between outdoor temperature and water
temperature is adjustable.)
When you set up the Outdoor Reset feature, you
can set the “turning points” on the adjusted setpoint
curve. If you go back to Fig. 91, the Outdoor Reset
screen, you see that the system records these values:
Enable -
Enable = Outdoor Reset feature turned on
Max. outdoor temp. -
If the outdoor temperature reaches this value
or above, the system will use the Low Water
Temp value as the setpoint. In the example
shown in Fig. 91, the Max. Outdoor Temp.
is set to 70°F. If the outdoor temperature is
70°F or above, the system will use 100°F
(the Low Water Temp.) as the setpoint.
Min. outdoor temp. -
If the outdoor temperature reaches this value
or below, the system will not compensate
for the outdoor temperature. In the example
shown in Fig. 91, the Min. Outdoor Temp.
is set to 32°F. If the outdoor temperature
reaches 32°F or below, the system will
use the normal Lead/Lag System setpoint
(120°F in this example).
Low water temp. -
If the outdoor temperature reaches the Max.
Outdoor Temp. or higher, the system will
use the Low Water Temp value as the new
setpoint. In the example shown in Fig. 91,
the Max. Outdoor Temp. is set to 70°F. If
the outdoor temperature reaches 70°F or
above, the system will use the Low Water
Temp. value (100°F) as the setpoint.
There is one other part of this system, and it is
located on a different screen:
LL CH setpoint -
On a system set up for Outdoor Reset, this
will be the maximum water temperature
setting. This is located on the main Lead/
Lag Configuration screen.
How to get there – Lead/Lag Master Configuration
Screen
Home Page <Press Lead/ Lag Master button> Lead/
Lag Screen <Press Configure button> Lead/ Lag Master
Configuration Screen
Job l - Building automation or multiple
Boiler Control thermostat Demand
(This is a Lead/Lag function – do this once for the whole Lead/
Lag system. Make the connections to the controller set up as
the Lead/Lag Master – usually the Primary controller on Boiler
1.)
1. Supply the controller which is acting as
the Lead/Lag Master (usually the Primary
controller on Boiler 1) with a thermostat
closure from the Building Automation
System or multiple boiler control. Connect to
terminals 5 and 6 on TB7.
2. Adjust the Lead Lag Central Heat setpoint.
How to get there – Lead/ Lag Central Heat Setpoint
Home Page <Press Lead/ Lag Master button> Lead/
Lag Screen <Press Configure button> Lead/ Lag Master
Configuration Screen
Line 2 = CH Setpoint
Note - Bradford White offers “gateways” to
allow connections to BACnet, LON, and other
communications protocols. See Section 9.6.
Job m - Building automation or multiple
Boiler 4-20 ma Setpoint Control
(This is a Lead/Lag function – do this once for the whole Lead/
Lag system.)
In this type of installation, the CH Setpoint is
changed or modulated by a source outside of the
boiler. The low limit of the 4-20 mA signal (4 mA)
sets the low limit of the setpoint, and the high limit
of the 4-20 mA signal (20 mA) sets the high limit of
the setpoint.
1. Supply the controller which is acting as
the Lead/Lag Master (usually the Primary
controller on Boiler 1) with the 4-20 mA input
from the Building Automation System or
multiple boiler control. Connect to terminals 3
and 4 on TB7.
2. On the Lead/Lag Master settings, change the
setpoint source to 4-20 mA.
How to get there – Lead/ Lag Setpoint Control
Home Page <Press Lead/ Lag Master button> Lead/
Lag Screen <Press Configure button> Lead Lag Master
Configuration Screen <Press Advanced Settings button>
<Press Left- or right-arrow button> Central Heat
Setpoint Source = 4-20 mA
Содержание BNTH1000
Страница 2: ...Bradford White Corp...
Страница 12: ...Page 8 Bradford White Corp Fig 6 Dimensions BNT 1700...
Страница 38: ...Page 34 Bradford White Corp Fig 21 Ladder Diagram...
Страница 39: ...Page 35 Brute Elite Boilers and Water Heaters Fig 22 Wiring Diagram...
Страница 40: ...Page 36 Bradford White Corp...
Страница 52: ...Page 48 Bradford White Corp Fig 51 Connection Terminals...
Страница 129: ...Page 125 Brute Elite Boilers and Water Heaters Fig 140 Machine Frame BNT1000 13 3 PARTS ILLUSTRATIONS...
Страница 130: ...Page 126 Bradford White Corp Fig 141 Rear Panel BNT1000 Fig 142 Rear Panel BNT1700...
Страница 131: ...Page 127 Brute Elite Boilers and Water Heaters Fig 143 Machine Frame BNT1700...
Страница 132: ...Page 128 Bradford White Corp Fig 144 Front Panels and Covers BNT1000 and BNT1700...
Страница 133: ...Page 129 Brute Elite Boilers and Water Heaters Fig 145 Burners and Combustion Chamber BNT1000...
Страница 134: ...Page 130 Bradford White Corp Fig 146 Burners and Combustion Chamber BNT1700...
Страница 136: ...Page 132 Bradford White Corp Fig 149 Burner Detail BNT1700...
Страница 137: ...Page 133 Brute Elite Boilers and Water Heaters Fig 150 Electronic Components Fig 151 Condensate Trap BNT1000...
Страница 138: ...Page 134 Bradford White Corp Fig 152 Condensate Trap BNT1700 Fig 153 Flow Switch BNT1000 and BNT1700...
Страница 139: ...Page 135 Brute Elite Boilers and Water Heaters This page intentionally left blank...
Страница 140: ...Page 136 Bradford White Corp This page intentionally left blank...