Page 70
Bradford White Corp.
2. Set the outdoor reset and warm weather
shutdown parameters as desired.
How to get there – Outdoor Reset Screen and Warm
Weather Shutdown Screen
Home Page <Press View Lead/ Lag button> Lead/ Lag
Screen <Press Lead/ Lag Master button> Lead/ Lag
Screen <Press Configure button> Lead/ Lag Master
Configuration Screen <Press Advanced Settings button>
Select the Outdoor Reset Screen or the Warm Weather
Shutdown Screen
fig. 92 – outdoor reset
For a detailed explanation of the Outdoor
Reset function, see the section titled “About
Outdoor Reset” which follows.
fig. 93 – Warm Weather Shutdown
When enabled, the Warm Weather Shutdown
feature will turn off the Central Heating
functions when the outdoor temperature
exceeds the setpoint. This prevents the system
from running when there is no need for heat.
Enable -
These options determine how quickly
the system shuts down after the outdoor
temperature rises above the setpoint. The
options are Shutdown immediately/ After
demand ends/ Disabled.
Setpoint -
If the outdoor temperature is higher than
this, the system will shut off the Lead/Lag
Central Heating functions.
about outdoor reset
The Outdoor Reset feature calculates a correction
for the Lead/Lag setpoint depending on the outdoor
temperature. This allows the system to adjust for
changes in the outdoor temperature and run more
efficiently.
The Show Line button at the bottom of the Outdoor
Reset screen displays a curve which shows
how the system will behave at different outdoor
temperatures. See Fig. 94.
fig. 94 – Show line Screen
The display shown above show the action of the
system with one possible group of settings. The
green line shows the setpoint used by the system.
• Without Outdoor Reset, this would be a
constant 120°F (or whatever value you chose),
regardless of the outdoor temperature. The
green line in the graph would run straight
across the display.
•
However, with the Outdoor Reset feature
turned on, the system will adjust for changes
in the outdoor temperature. Let’s take a
detailed look at behavior of the setpoint,
shown by the green line in the display. For
cold outdoor temperatures (below 32°F), the
setpoint remains unchanged (120°F). As the
temperature begins to rise above 32°F, the
Outdoor Reset function causes the setpoint to
be lowered. At these warmer temperatures,
the heating load on the system is not as great,
so the system does not have to reach as high
a temperature to handle the load. As you can
see from the display, at an outdoor temperature
of about 70°F, the system stops adjusting the
setpoint. Above 70°F, the setpoint is constant
at 100°F.
Содержание BNTH1000
Страница 2: ...Bradford White Corp...
Страница 12: ...Page 8 Bradford White Corp Fig 6 Dimensions BNT 1700...
Страница 38: ...Page 34 Bradford White Corp Fig 21 Ladder Diagram...
Страница 39: ...Page 35 Brute Elite Boilers and Water Heaters Fig 22 Wiring Diagram...
Страница 40: ...Page 36 Bradford White Corp...
Страница 52: ...Page 48 Bradford White Corp Fig 51 Connection Terminals...
Страница 129: ...Page 125 Brute Elite Boilers and Water Heaters Fig 140 Machine Frame BNT1000 13 3 PARTS ILLUSTRATIONS...
Страница 130: ...Page 126 Bradford White Corp Fig 141 Rear Panel BNT1000 Fig 142 Rear Panel BNT1700...
Страница 131: ...Page 127 Brute Elite Boilers and Water Heaters Fig 143 Machine Frame BNT1700...
Страница 132: ...Page 128 Bradford White Corp Fig 144 Front Panels and Covers BNT1000 and BNT1700...
Страница 133: ...Page 129 Brute Elite Boilers and Water Heaters Fig 145 Burners and Combustion Chamber BNT1000...
Страница 134: ...Page 130 Bradford White Corp Fig 146 Burners and Combustion Chamber BNT1700...
Страница 136: ...Page 132 Bradford White Corp Fig 149 Burner Detail BNT1700...
Страница 137: ...Page 133 Brute Elite Boilers and Water Heaters Fig 150 Electronic Components Fig 151 Condensate Trap BNT1000...
Страница 138: ...Page 134 Bradford White Corp Fig 152 Condensate Trap BNT1700 Fig 153 Flow Switch BNT1000 and BNT1700...
Страница 139: ...Page 135 Brute Elite Boilers and Water Heaters This page intentionally left blank...
Страница 140: ...Page 136 Bradford White Corp This page intentionally left blank...