Operating and service instructions
|
LMS 120
9
4.3. Quick parameter setting
The quick parameter setting function applies practical values for all parameters depending on the monitoring
system. This procedure is sufficient to commission the LMS 100 in full.
System defaults:
Nordic
Brandes
Swiss
Device defaults Standard
Isolation limit
Measure cycle
1 h
Loop limit
200
Ω
6.0 k
Ω
200
Ω
Horn
On
Tolerance
-
-
-
Tab. 3 (Default values)
4.3.1. Activating the service menu
To adopt these values, the service menu has to be activated as follows:
Fig. 6 (Auto settings)
4.3.2. Setting NORDIC, BRANDES or SWISS
After activating the service menu (see 4.3.1.), perform the following steps.
Procedure:
1.
System Defaults 11 is displayed
2.
Select NORDIC, BRANDES or SWISS
3.
Confirm selection, Setting channel defaults is displayed briefly, then again
System Defaults 11
4.
OK to Back 13 is displayed
5.
Auto Settings 10 is displayed
6.
OK to Save & Exit 90 is displayed
7.
Operation display 1 appears
4.3.3. Setting device to default
After activating the service menu (see 4.3.1.), perform the following steps.
Procedure:
1.
System Defaults 11 is displayed
2.
Device Defaults 12 is displayed
3.
Confirm selection, Setting channel defaults is displayed briefly, then again
System Defaults 12
4.
OK to Back 13 is displayed
5.
Auto Settings 10 is displayed
6.
OK to Save & Exit 90 is displayed
7.
Operation display 1 appears