Operating and service instructions
|
LMS 120
12
4.4.3. Device settings
Devices settings are settings that relate to the general functions of the LMS 120. The menu structure is displayed in
Fig. 7 on page 10.
Measure cycle
- menu 41
The
measure cycle
of the fully automatic measurement is set here. In the event of an alarm message, the duration
of the fault can be assessed by multiplying the measure cycle with the number of errors saved. (see 4.5. Alarm
menu; page 13)
Example;
Measure cycle:
6 h
Error number:
(092)
Fault since:
92 x 6 h = 552 h = 23 days
Possible settings:
2min, … , 30min, 1h, … 24h
Buzzer
- menu 42
The LMS 120 issues an acoustic signal in the event of faults in the monitoring system. This signal can be
deactivated.
Possible settings: On, Off
Self-test
- menu 43
The LMS 120 conducts a self-test after every start. If it is suspected that the LMS 120 is not working correctly, a
manual self-test should be started. To this end, the
key in the Self-test menu has to be pressed.
The following message is shown in the display after successfully completing the self-test.