VIBROCONTROL 920
Setups
__________________________________________________________________________________
Page 18 / 33
VC920E / C102833.002 / V 13
Mode 5 Limit relays operating mode
Default value: 0
This parameter affects both limit relays.
Selection
Mode
0
Normally energized
1
Normally de-energized
Normally energized:
The relay de-energizes when the limit
is exceeded
Normally de-energized:
The relay energizes when the limit is
exceeded
Mode 6 LED 7-segment display
Default value: 0
With this parameter the duration and intensity of the LED seven-segment
display is set up.
Selection
Mode
0
after 3 minutes the LED display goes off.
1 ... 3
The display switches on with maximum
brightness. After 3 minutes the brightness
is reduced to the selected factor.
Larger number = Brighter display
4
Permanent display with maximum
brightness