Hotspur 5 & 9 Issue 2 December 2017
9
Chimney Requirements
This appliance must not be fitted into a chimney serving another heating appliance. It is
most important that there is no obstruction in the flue or chimney. Please ensure that
any existing chimney is clear of obstruction and swept clean immediately before
installation of the new stove. If the chimney has been used for an open fire it is
recommended that it be swept for a second time having been used for a month
following installation.
A flue draught minimum of 12 Pascals to a maximum 18 Pascals is required for
satisfactory appliance performance. A properly built masonry or factory constructed
chimney (with a minimum vertical height of 5 metres) should ensure a consistent
draught (draw). 45° bends can be used in the flue run (maximum of four bends) you will
need to add an extra 1 metre of vertical flue height for each bend.
The flue draught should be checked under fire at high output and if it exceeds the
recommended maximum, a draught stabiliser must be fitted so that the rate of burning
can be controlled, and to prevent over firing (See section “Warning Notes”). If you have
any doubts about the suitability of your chimney, consult your local dealer/stockist or
engineer. If your flue draft is below the minimum recommendation then it may be
necessary to increase the vertical chimney height, add additional flue insulation or
possibly add a special cowl to the top of the chimney (e.g. anti down draft cowl to
eliminate wind induced down draft).
The outlet from the chimney should be above the roof of the building in accordance with
the provisions of Building Regulations Approved Document J.
If installation is into an existing chimney then it must be sound and have no cracks or
other faults which might allow fumes into the house. Older properties, especially, may
have chimney faults or the cross section may be too large i.e. more than 230 mm x 230
mm. Remedial action should be taken, if required, seeking expert advice, if necessary. If
it is found necessary to line the chimney then a flue liner suitable for solid fuel must be
used in accordance with Building Regulations Approved Document J.
If there is no existing chimney then either a prefabricated block chimney in accordance
with Building Regulations Approved Document J or a twin walled insulated stainless
steel flue to BS 4543 can be used. These chimneys must be fitted in accordance with
the manufa
cturer’s instructions and Building Regulations.
If a flexible liner is required the liner diameter must not be less than 5
” / 125mm for the
HOTSPUR 5 and 6” / 150mm for the Hotspur 9.
Any bend in the chimney or connecting fluepipe should not exceed 45°. 90° bends are
not permitted. For top flue installations it is possible to sweep through the appliance by
removing the internal baffles however it is recommended that you provide adequate
access (e.g. easily accessible soot door). For rear flue connection we recommend the
use of a tee section, the bottom of the tee should be capped to catch soot and debris.
Содержание Hotspur 5
Страница 6: ...Hotspur 5 9 Issue 2 December 2017 6 Dimensions Hotspur 5 Hotspur 9 ...
Страница 35: ...Hotspur 5 9 Issue 2 December 2017 35 ...
Страница 37: ...Hotspur 5 9 Issue 2 December 2017 37 ...