Directions for use

Automatic  controls  are  safety  devices  and  shall  not  be 
opened. The manufacturer’s responsibility and guarantee 
are invalid if the control is unduly opened. 

A  regulation  shutdown  must  occur  every  24hours  to 
enable the unit to check its own efficiency (systems for 
non permanent operation)

Connect and disconnect the unit only after switching off 
the power supply

Avoid exposing the unit to dripping water

Ventilation  and  the  lowest  temperature  ensures  the 
longest life of the control

Electrical Installation

Live and Neutral should be connected correctly; a mistake 
could cause a dangerous situation.

Before  starting  the  system  check  cables  carefully  for 
incorrect installation

The earth terminal of the control, the metal frame of the 
burner and the earth on the mains supply must be well 
connected

OPERATION DATA - HONEYWELL CONTROL BOX 

CONTINUED...

Operation

At  every  start,  the  control  unit  proceeds  to  a  self-checking 
of  its  own  components.  During  the  pre-purge  or  waiting 
time (TW) the internal circuit makes a test of the flame signal 
amplifier. Extraneous light or fault in the amplifier will result 
in  the  simulation  of  a  flame  which  will  prevent  the  control 
from starting.

At the end of the waiting or pre-purge time, the gas valve is 
energised and the ignition device is operated. In this way, the 
safety time (TS) begins.

If  a  flame  is  detected  during  the  safety  time,  the  ignition 
device is inhibited and the gas valve remains energised.

If  the  control  does  not  detect  any  flame  signal  during  the 
safety time, at the end of safety time (TS), the unit proceeds 
to lockout and the gas valve and ignition device are switched 
off.

If the established flame signal is lost, (during the safety time 
or  during  operation  thereafter)  this  will  cause  the  ignition 
device to be reactivated within 1 second.

If  the  burner  does  not  light  within  25  seconds  of  ignition 
reactivation, the heater will enter failure lockout mode and 
must be reset. 

OPERATION DATA 

HONEYWELL VALVE:

The VK series gas control have been specially developed for 
application in domestic appliances. The Honeywell Gas Valve 
is a multi-functional control which incorporates an adjustable 
direct acting pressure regulator. It is designed for operation 
on 220/240V.

Standard Specifications 

1/2” G Female Pipe Thread connection

Ambient Temperature Range of 0°C to 60°C

Compact Size: 86.5mm x 63.5mm x 65.9mm

50mb Pressure Rating

1/2” x 1/2” (BSP- G) Inlet and Outlet

Earthing terminal – 0.24” spade tab

Tamper resistant screws

Top mounted coils that can be field replaced

TECHNICAL DATA

Max inlet working pressure

50 mbar

Installation group 

Group 2

Operating Temperature

0°C to 60°C

Voltage Ratings

220/240VAC
50/60Hz .52A

Adjust Regulator Pressure

Unscrew the regulator cover.

Unscrew the outlet plug to measure the outlet regulator 
pressure by using manometer.

Adjust  the  pressure  by  turning  the  regulator  screw 
clockwise or anti wise.

Adjust the pressure according to appliance specification.

Inlet Pressure

Outlet Pressure

Regulator

IMPORTANT

Remember to place the regulator cover, outlet and inlet back 
on.

!

Содержание SMART-HEAT TUNGSTEN 300

Страница 1: ...ediately call your gas supplier or fire department Do not store or use gasoline or other flamable vapor and liquids in the vicinity of this or any other appliance An LP cylinder not connected for use...

Страница 2: ...S MANUAL CAREFULLY before installing or servicing this product U Improper installation operation or maintenance can result in death severe injury or property damage U Installation must be carried out...

Страница 3: ...ION 12 LEAKAGE TEST 12 HEAT DEFLECTOR INSTALLATION INSTRUCTIONS 13 CEILING MOUNT POLE INSTALLATION INSTRUCTIONS 13 OPERATING INSTRUCTIONS 14 TURNING THE APPLIANCE ON 14 TURNING THE APPLIANCE OFF 14 MA...

Страница 4: ...the heater until all connections have been leak tested by an authorized person U Inspect the hose assembly before each use of the appliance U The hose assembly must be replaced prior to the appliance...

Страница 5: ...pane LPG NATURAL GAS Manufactured by BROMIC HEATING PTY LTD 1 SUTTOR ST SILVERWATER NSW 2128 SYDNEY AUSTRALIA CSA Approval No 2345658 2345658 2345658 2345658 Gas Consumption 26 000 BTU 26 000 BTU 43 0...

Страница 6: ...ilation U without stagnant areas U where gas leakage and products of combustion are rapidly dispersed by wind and natural convection Any enclosure in which the appliance is used shall comply with one...

Страница 7: ...rances refer below Note When Installing with No protective cover the following installation clearances shall apply Minimum height to combustible materials Model A B C 300 Series 3ft 3ft 8ft 500 Series...

Страница 8: ...U Slide Gas Connector and Wiring Harness inside the centre of the arm and have them exit through the shaped cut out on top surface of the arm U Ensure that the arm faces downwards at a 55 angle U Posi...

Страница 9: ...the arm can slide into place TIP Do not install the mounting pin at this point Step 5 Connect the CSA approved flexible connector to the Gas Valve Outlet Fitting U Position heater and hose so that the...

Страница 10: ...llowing the instructions below IMPORTANT Electrical connections must be completed by trained and authorized electrical technicians only For Honeywell Control U Using a pair of needle nose pliers grip...

Страница 11: ...with the symbol 8 Connect gas inlet fitting to mains gas supply in accordance with local gas installation code and gas supply installation section of manual Leak test with soapy water 9 Fix Front cov...

Страница 12: ...ose may be subject to accidental damage POWER SUPPLY INSTALLATION WARNING This heater is equipped with a three prong grounding plug for your protection against shock hazard and should be plugged direc...

Страница 13: ...2 Assemble pole to the mounting bracket using the M8x100mm and M19x100mm bolts and fix using nuts and washers as supplied 3 Assemble both lower paddles to the pole back to back 4 Fix Heater to Lower p...

Страница 14: ...ny evidence of excessive wear or if the hose is damaged The replacement hose assembly must be CSA approved with 3 8 SAE flared ends To Check the Gas Hose remove control housing cover by removing 8 scr...

Страница 15: ...oration of the mains power supply Features U Compliance with CSA standard for automatic gas burner flame monitoring and control systems U Compliance with EN 298 European standard for automatic gas bur...

Страница 16: ...alve remains energised If the control does not detect any flame signal during the safety time at the end of safety time TS the unit proceeds to lockout and the gas valve and ignition device are switch...

Страница 17: ...he ground terminal of the control the metal frame of the burner and the ground on the mains supply must be well connected Operation When a call for heat is received from the thermostat supplying 24 vo...

Страница 18: ...0 V 2 x 5 5 VA Electrical connection Molex System connection coil or Option Connection box with integrated cable Installation position Solenoid at any position between vertical and hori zontal axis OP...

Страница 19: ...Ionisation HONEYWELL Red 230 V Blue Purple Purple Note If any of the original wire as supplied with the heater must be replaced it must be replaced with 18AWG 90 C type UL approved wire or its equival...

Страница 20: ...V 2 White S 1 T H V 1 Red Orange Yellow Green TRANSFORMER WHITE RODGERS Note If any of the original wire as supplied with the heater must be replaced it must be replaced with 18AWG 90 C type UL approv...

Страница 21: ...1 T H V 1 Red Orange Yellow Green TRANSFORMER DUNGS Note If any of the original wire as supplied with the heater must be replaced it must be replaced with 18AWG 90 C type UL approved wire or its equiv...

Страница 22: ...REPLACEMENT PARTS 1 2 3 4 5 9 10 11 24 8 12 23 6 22 7 17 13 16 19 20 15 13 14 19 White Rodger Honeywell...

Страница 23: ...080030 11 Wiring Harness Ignitor Assembly Honeywell BH8080012 BH8080013 12 Inner Skin BH8080031 BH8080032 13 Wall Bracket Assembly BH8080001 BH8080001 14 Honeywall Control BH8080015 BH8080015 15 Honey...

Страница 24: ...alled on this site 300 ________ 500 ________ What type of gas is used Propane Natural Gas Is Are the heater s exposed to salt air or any other corrosive or chemical atmosphere Yes No Does the heater s...

Страница 25: ...until at least 6 W C for natural gas or 11 W C for propane precedes heater s control assembly 3 Clean orifice 4 Provide adequate ventilation of by products 5 Replace manifold 6 Increase gas pressure...

Страница 26: ...APPENDIX A...

Страница 27: ...APPENDIX A CONTINUED...

Отзывы: